Instruction Manual: IM E

Similar documents
Eaton Innovative TechnologyT XT50/100 surge protective device

Instruction Manual IM E Table of Contents

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

Eaton SPD Series. for Mounting External to Electrical Distribution Equipment. Instruction Manual IM E Effective March 2014 Rev.

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400

Eaton SPD Series. Instruction Manual IM E Effective June 2014 Rev. 2

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

for the SPV Installation and Operation Manual Instruction Manual IM E Contents

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

Surge Protective Devices Installation, Operation and Maintenance Manual. ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual

Installation and Operation Manual

Hubbell Surge Protective DeviceS

Installation Instructions & User Manual

GE Digital Energy. Power Quality

BSPD Surge Protective Devices

Always "On" UPS Systems Inc. USER MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

R-LB R-LX Series Installation, Operation & Maintenance Manual

SSMx24 Series 240 ka Per Phase Peak Surge Current ANSI/UL1449 UL Fourth Edition

TPS3 09. Surge Protective Device. User Manual - USA

Installation and Operation Manual

Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions

Total Home Surge Protection for Point-of-Entry. FirstSurge TM. User Manual - Canada (English)

Installation Instructions & User Manual POWERWARE TVSS ZONESENTINEL. AC Panel Transient Voltage Surge Suppressors

Instruction Bulletin Boletín de instrucciones Directives d'utilisation , Rev. 02, 03/2016

PHOENIX CONTACT Features

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

S66 Series Electronic Fan Speed Control

400 Series 460 Surge Protective Device Installation, Operation and Maintenance Manual

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

Solar Combiner Enclosure

HydroGuard 4 to 20 ma Output Module. For use with HydroGuard Water Quality Monitor and Controller

CurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Surge Protective Devices. Installation & Operation Manual. NEMA 12 (Steel) NEMA 1 (Non-Metallic) Model 350

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures)

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

IntelliBrite Controller (For IntelliBrite Pool, Spa and Landscape Lighting Fixtures) Installation and User s Guide

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Multi Unit Enclosed Meter

Specifications 1 Installation Procedures 2 Wiring Diagrams 3 Installation Checklist 5 Maintenance 5 Warranty Information 6 Material Return Policy 6

Application Techniques CENTERLINE 2100 Motor Control Centers

P216 Series Condenser Fan Speed Controller

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

Specifications, Installation, and Operating Instructions

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

Upgrading Legacy Iso-Gard Line Isolation Monitors and Remote Indicators

Backpanel Attaching Hardware. Molded-in Threaded Housing for Mounting. Enclosure. Enclosure. Backpanel. Fuse Holder with Series Fuse

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

* * Agilent Power Distribution Unit (PDU) Installation Guide

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

EX-RC1 Remote I/O Adapter

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

PowerLogic High Density Metering System 1-Meter Enclosure

FDS / FDS-R / FDS-PS

Installation Notes TII Model 341 Protector

Measure Ø-N, Ø-Ø, Ø-Gnd with voltmeter to confirm application voltage prior to installation.

Instruction Manual. Multilin TM 8 Series Retrofit Kit * A1* GE Grid Solutions LISTED

PV Rapid Shutdown device

Eaton s SPD Series for integration into electrical distribution equipment

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

ICS Entrance Management Sign Installation Guide. Version 1.0

SureTest Model ST 1D Instructions

Entry Level Assessment Blueprint Electrical Occupations

PanelFAST. Setting a new standard for immediate product availability with Square D Ready to Install (RTI) Panelboards

THE SURGE PROTECTION SOLUTION

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

SURFACE CONTROLTrack INSTALLATION INSTRUCTIONS

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

User Manual - Canada. TPS3 03 DC For DC Photovoltaic Applications. Surge Protective Device

300 Series 330/320 Surge Protective Device Installation, Operation and Maintenance Manual

OPLC Installation Guide

VRp Three-Phase Precision AC Voltage Regulator

MARWELL CORPORATION Manufacturer of UL Listed Meter Socket Adapters

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout

General Description. Product Application. Eaton Innovative Technology Special Applications

Multilin EPM 4600 Metering Solution

Quick Start Guide TS A

Differential Liquid/Gas Pressure Transmitter

Analog Monitor Installation Manual

A0-10 ANALOG OUTPUT. Instruction Manual April 2001 NALOG OUTPUT

OilCop Component Wiring Installation Manual

Quick Start Guide TS 870 ATS

Analog Input Installation Manual

TransGuard. Electrical Transient Suppression Filter Systems. Installation, Operation and Maintenance Manual PN ,

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

Enphase S-Series Microinverter and Engage Cable Safety

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

Transcription:

Innovative Technology TVSS Products The I.T. Equalizer Installation Instruction Manual: IM01005011E Rev. 2 May 2009 Contents Page 1 Introduction... 1 1.1 Scope... 1 1.2 I.T. Equalizer Catalog Numbering System... 1 1.3 Safety Precautions... 2 2 Installation... 3 2.1 Before Installation... 3 2.2 Wiring Diagrams... 4 2.3 Disconnecting the ATN Filter... 5 2.4 Installing... 5 2.5 Conduit Installation... 6 2.6 Mounting the SPD... 6 2.7 Wiring SPD to Electrical System... 7 2.8 Power Up and System Checkout... 7 2.9 Form C Relay Contact Connections... 8 The I.T. Equalizer Effective Date 5/2009 For more information visit: www.itvss.com

IM01005011E I.T. Equalizer Installation Register Your Warranty On-Line at http://www.itvss.com/ Notice: Product improvements and enhancements are continuous; therefore the specifications and information contained in this document may change without notice. Eaton Corporation shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material. No part of this document may be reproduced for publication, or translated to another language without the prior written consent of Eaton Corporation. Innovative Technology is a registered trademark of Eaton Corporation. All other trademarks, trade names, service marks and logos referenced herein belong to their respective owners. Page A Rev. 2 5/2009

I.T. Equalizer Installation IM01005011E 1 INTRODUCTION 1.1 Scope This installation manual contains the information necessary to install Eaton Corporation s line of I.T. Equalizer Surge Protective Devices (SPDs) for the following electrical system wiring configurations: Single Phase (1P) Split Phase (1S) 3 Phase Wye (Star) (3Y) 3 Phase High-Leg Delta (3D) 3 Phase No Neutral (NN) If you require further information regarding a particular installation, contact Power Quality Technical Support at 1-800-809-2772. 1.2 I.T. Equalizer Catalog Numbering System EQX 160 N - 3Y101 Model EQX= Equalizer Per Phase Peak Surge Current (ka) 040 =40 080 =80 160 = 160 Optional Upgrade N =ATN Active Tracking Network Filter Configuration & Voltage Ranges (Vac) 1P101 = Single-Phase 100, 110, 120, 127 1P201 = Single-Phase 200, 208, 220, 230, 240, 277 1S101 = Split-Phase 100/200, 110/220, 120/240 3Y101 = Three-Phase Wye (Star) 100/174, 110/190, 120/208, 127/220 3Y201 = Three-Phase Wye (Star) 220/380, 230/400, 240/415, 277/480 3Y300 = Three-Phase Wye (Star) 305/525, 347/600 3D101 = Three-Phase High Leg Delta 120/240 NN201 = Three-Phase Delta 200, 208, 220, 230, 240 NN400 = Three-Phase Delta 380, 400, 415, 440, 480 NN501 = Three-Phase Delta 525, 600 In this example, Catalog Number EQX160N-3Y101 identifies a Equalizer with the following features and ratings: Surge Current Rating of 160 ka UL 1283 Tracking EMI/RFI Filter Three-Phase WYE Configuration Voltage Range of 100 to 220 Vac Rev. 2 5/2009 Page 1

IM01005011E I.T. Equalizer Installation 1.3 Safety Precautions A licensed/qualified electrician must complete all instructions and measurements described in this instruction in accordance with the U.S. National Electrical Code, state and local codes, or other applicable country codes. The U.S. National Electrical Code and state and local requirements (or other applicable country codes) supersede this instruction. Read and understand all instructions before beginning installation. WARNING! The use of the word WARNING in this manual denotes a potential hazard associated with the use of this equipment. It calls attention to a procedure, practice, or condition, or the like, which if not correctly performed or adhered to, could result in personal injury or death. CAUTION The use of the word CAUTION in this manual denotes a potential hazard associated with the use of this equipment. It calls attention to a procedure, practice, condition, or the like, which if not correctly performed or adhered to, could result in damage to the equipment. WARNING! SHOCK HAZARDS: IMPROPER INSTALLATION CAN CAUSE DEATH, INJURY AND/OR EQUIPMENT DAMAGE. Follow all warnings and cautions. Completely read and understand the information in this document before attempting to install or operate this equipment. IMPROPER WIRING COULD CAUSE DEATH, INJURY, AND/OR EQUIPMENT DAMAGE. Only licensed/qualified electricians who are trained in the installation and service of electrical devices are to service this equipment. USE APPROPRIATE SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC FLASH PROTECTION. Page 2 Rev. 2 5/2009

I.T. Equalizer Installation IM01005011E 2 INSTALLATION 2.1 Before Installation Perform or plan the following before installing the SPD: 1. Locate your electrical system s applicable wiring diagram in Section 2.2. 2. Verify that your electrical system s voltage and wiring configuration matches that of the SPD as shown on its label. 3. De-energize the SPD, and follow safe work practices to avoid an electrical shock hazard. 4. Ensure that a Neutral to Ground/Earth bond is present at the SPD. Note that the SPD may be damaged if not connected to ground. 5. Measure the voltage between Neutral and Ground. If this voltage is greater than 5 Vac, then a problem may exist in the electrical system. The SPD can still be installed under this condition, but a licensed/qualified electrician should be consulted to correct the problem. 6. For SPDs that contain an Active Tracking Network (ATN) filter, this filter needs to be disconnected if the SPD is to be connected to an electrical panel feeding medical patient care equipment or containing a ground fault circuit interrupting (GFCI) main breaker. Disconnect the ATN filter per Section 2.3. 7. The SPD can be mounted in any position. If necessary, the cover may be rotated 180 degrees to improve readability of the label. When removing the cover, be careful not to damage the indicator light circuit board or wiring attached to the cover. 8. Isolated Ground: The SPD s ground wire is internally bonded to its housing. If the electrical system utilizes an isolated ground, then the SPD s housing must also be isolated from ground using insulated conduit fittings, and its ground wire must be connected to the system s isolated ground bus. 9. Plan to use weatherproof (corrosion resistant) conduit and fittings to maintain the enclosure s NEMA 4 (IP66) or 4X rating. 10. Plan to install the SPD as close as possible to the electrical panel. Long lead lengths and sharp bends between the SPD and the panel will degrade the performance of the SPD. 11. Plan to install a circuit breaker of the appropriate rating and class as listed in Table 2-1. Rev. 2 5/2009 Page 3

IM01005011E I.T. Equalizer Installation 2.2 Wiring Diagrams Single Phase (1P101, 1P201) Split Phase (1S101) PHASE A PHASE A Use Interrupt Device if connected to Phase B NOT Neutral NEUTRAL NETURAL or PHASE B GROUND CIRCUIT INTERRUPT DEVICE GROUND PHASE B CIRCUIT INTERRUPT DEVICE SPD Solid bond between Ground/Earth and Neutral at service entrance or serving isolation transformer SPD 3-Phase Wye (Star) (3Y101, 3Y201, 3Y300) PHASE A PHASE B PHASE C 3-Phase Delta (No Neut.) (NN201, NN400, NN501) PHASE A PHASE B PHASE C NEUTRAL CIRCUIT INTERRUPT DEVICE CIRCUIT INTERRUPT DEVICE GROUND GROUND Solid bond between Ground/Earth and Neutral at service entrance or serving isolation transformer SPD SPD 3-Phase Delta (High-Leg) (3D101) PHASE A PHASE B (High Leg) PHASE C NEUTRAL CIRCUIT INTERRUPT DEVICE GROUND Solid bond between Ground/Earth and Neutral at service entrance or serving isolation transformer SPD Page 4 Rev. 2 5/2009

I.T. Equalizer Installation IM01005011E 2.3 Disconnecting the ATN Filter When part of the SPD, the ATN filter should be disconnected when the SPD is connected to an electrical panel feeding medical patient care equipment or containing a ground fault circuit interrupting (GFCI) main breaker. The ATN filter provides enhanced Neutral to Ground/Earth protection that may cause nuisance tripping of breakers that are part of the above-mentioned applications. Note: The following procedure only disables the ATN filter. Other protection circuits are not affected. 1. Remove front cover, being careful not to damage the indicator light circuit board and wiring attached to the cover. 2. Locate a green/yellow loop of wire protruding from the encapsulation. Using a wire-cutting tool cut this wire in the center of the loop. 3. Cap off the ends of each wire using UL listed wire nuts. 4. Reinstall cover. 2.4 Installing The SPD must be connected to the electrical system through circuit breakers of the appropriate current rating as specified in Table 2-1. Mount the circuit breakers as close as possible to the system s phase voltage connections. For Single Phase applications (refer to Section 2.2, Single Phase Diagram), note that if the Neutral wire is used as Phase B, then an additional breaker must be used for that phase. Table 2-1. Wire and Circuit Breaker Requirements Equalizer Models EQX 40, 80, 160 Wire Size #10 AWG (6mm 2 ) Stranded Wire Included Circuit Interupt Device Required for Installation Max. Current Rating Type 30 ampere singlethrow circuit 30 Amps breaker Rev. 2 5/2009 Page 5

IM01005011E I.T. Equalizer Installation 2.5 Conduit Installation When planning the conduit installation, avoid using 90 elbows and keep the conduit run as short and straight as possible. See Figure 2-1. When applicable, use weatherproof (corrosion resistant) conduit and fittings to maintain the enclosure s NEMA 4 or 4X rating. If the system utilizes an isolated ground, then the SPD s housing must be isolated from ground using insulated conduit fittings. Feed the wires from the SPD through the conduit and install the conduit between the SPD and electrical panel. Figure 2-1. Conduit Installation Guidelines Avoid sharp bends in wiring and longer than necessary wire lengths Keep wire lengths as short and straight as possible 2.6 Mounting the SPD The SPD should be mounted in a location that provides the shortest possible wire length to the system s electrical connections. Excessive wire length and sharp bends will degrade the SPD s performance. Using appropriate hardware, mount the SPD to the wall or other supporting surface using the SPD s mounting holes. Mounting dimensions and weight are shown in Figure 2-2. Figure 2-2. Equalizer Series for 40, 80, and 160 ka Models 8.00 (203.2) 7.00 (177.8) 0.75 (19.1) Internally Threaded Co nduit Fitting Weight: 5 lb Dimensions: Inches (mm) 2.00 (50.8) 5.05 (128.3) 3.06 (77.7) Page 6 Rev. 2 5/2009

I.T. Equalizer Installation IM01005011E 2.7 Wiring SPD to Electrical System Important! When connecting the wires from the SPD to the electrical system, cut the wires as necessary to keep them as short as possible. In addition, to maximize the SPD s performance, also twist and bind the wires together to reduce the impedance of the wire. 1. Locate your electrical system s applicable wiring diagram in Section 2.2. Reference this wiring diagram as necessary in Steps 2, 3, and 4. 2. Connect the Ground wire from the SPD to the system s Ground bus bar. Important! If the system utilizes an isolated ground, then its ground wire must be connected to the system s isolated Ground bus. 3. Connect the Neutral wire from the SPD to the system s Neutral bus bar (not required for 3-Phase Delta systems NN201, NN400, and NN501). 4. Connect each Phase wire from the SPD through the circuit breaker installed in Section 2.4 to the system s corresponding Phase voltage connection. Tip: To ensure that the front panel phase voltage LEDs glow evenly, be sure that the phase wires are attached to their associated phase (A to A, B to B, and C to C). The wires or terminals of the SPD are marked with the intended phase for the electrical system (A, B, or C). Use a phase rotation meter to identify the electrical system s phase sequence prior to wiring the SPD DO NOT trust existing markings. 5. If the SPD s Form C relay is to be utilized for remote alarm purposes, proceed to Section 2.9 for detailed wiring information. 6. Recheck all connections, and then install the SPD s cover. 2.8 Power Up and System Checkout 1. Apply system power and observe that the LED(s) on the front of the SPD should glow. One LED should glow for each Phase voltage being monitored. Should there be a significant difference in brightness, check the phase rotation of the panel and ensure that the SPD s Phase wires are connected to the correct phase. Slight differences in brightness DO NOT indicate a faulty device, rather specification tolerance differences of the indicator circuit s components. LED brightness symmetry and/or level do not indicate the SPD s operational status. 2. The SPD s Form C relay should energize with all phase voltages present. Rev. 2 5/2009 Page 7

IM01005011E I.T. Equalizer Installation 2.9 Form C Relay Contact Connections The SPD s Form C relay provides dry contacts that are labeled N/O (Normally Open), N/C (Normally Closed), and COM (Common) with the relay energized. The relay contacts are rated 125 Vac at 0.5 A, or 30 Vdc at 1 A (60 W or 125 VA). This relay operates in a fail-safe mode, causing it to energize only when all phase voltages are present; in turn, causing its N/O and N/C contacts to be open and closed, respectively. By connecting a remote alarm to these contacts, the alarm can be made to activate when the relay de-energizes if one of the system phase voltages is lost. Connect the SPD s Form C relay contacts to a remote alarm device as follows: 1. De-energize the SPD, and follow safe work practices to avoid an electrical shock hazard. 2. If not already done, open or remove the cover of the SPD, taking care not to damage the indicator light circuit board and wiring attached to the cover. 3. Punch or drill a 0.5" (12.7 mm) diameter hole, centered at 1.125" (28.5 mm) from the lip of the box (cover opened/removed) in a location that will not interfere with the cover clamps or screws. And then install the supplied watertight strain relief (e.g. Heyco 3208). Important! Be cautious to capture and remove all metal shavings during the drilling process to avoid possible short circuits. 4. Using a small flat-blade screwdriver, connect a customer-supplied alarm device to the Form C relay s COM and N/C or N/O terminals as required. Note that the relay terminals accept AWG #26 (0.16 mm 2 ) to #16 (0.5 mm 2 ) wire. Be sure to follow applicable U.S. NEC Articles (or other applicable country codes). Also, follow rules of wiring class used when determining routing of alarm leads. To maintain NEMA 4 (IP66) rating, use appropriate cable and watertight strain relief. In the example shown in Figure 2-3, the Form C relay will de-energize if one of the Phase voltages is lost, causing the alarm to activate. 5. Replace the SPD cover. 6. When the SPD is powered, and with all phase voltages present, the Form C relay should energize causing it contacts to move to their normal position. Figure 2-3. Typical Alarm Wiring ALARM Low Power Indicator Light or Horn Computer Based Control System Alarm Annunciating Circuit PLC Alarm Power Source (125 Vac @ 0.5A or 30 Vdc @ 1A Max.) N/C N/O COM FORM C REL AY TERMINALS (Located on Indicator Light Circuit Board) Page 8 Rev. 2 5/2009

I.T. Equalizer Installation IM01005011E Notes: Rev. 2 5/2009 Page 9

Eaton Corporation 1000 Cherrington Parkway Moon Township, PA 15108-4312 USA http://www.itvss.com 2007 Eaton Corporation For additional information please call: All Rights Reserved Power Quality Technical Support Center Publication No. IM01005011E 1-800-809-2772 Rev. 2 May 2009