APPLICATION NOTES H-coupling

Similar documents
AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3

DEIF A/S. Description of options. Option P1, Event and alarm printer Automatic Gen-set Controller. Description of option. Functional description

APPLICATION NOTES Translations

Option X4 Additional Operator Panel AOP-2 Description of option Functional description

Option P1 Event and alarm printer Description of option Functional description Parameter list

DEIF A/S. Description of options. Option C2, Generator add-on protection package Automatic Gen-set Controller. Description of option

DEIF A/S. Description of options. Option C1 Generator add-on protection package Multi-line 2 version 2. Description of options. Functional description

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options

Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3

MULTI-LINE 2 APPLICATION NOTES

Option H10, Multi-line 2 unit with USB service port. To be used when the multi-line 2 unit service port is USB type

Option H3 Serial communication Profibus DP

Inverter Interface Interface examples Wiring examples Communication topology

Getting started - USW 3.x Software download from internet Software installation Device setup Data backup

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version:

Genset control and protection with safety system

Advanced Graphical Interface, AGI 100

MULTI-LINE 2 DESCRIPTION OF OPTIONS

Option M2 Configurable engine control cards Multi-line 2 version B SW version 2.4X.X

Option H8.x and H12.x External I/O modules Description of option Functional description

DEIF A/S. Description of options. Option H4 Serial comm. CAT CCM communication Multi-line 2 version 2. Description of option Functional description

APPLICATION NOTES DELOMATIC 4, DM-4 GAS/HYDRO

QUICK START GUIDE Paralleling and Protection Unit PPU 300

CODESYS v. 2.3, Ethernet driver for AGI 3xx Use the CODESYS Ethernet driver in the AGI Creator Set up the CODESYS for use with the AGI Creator

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Generator Protection Unit GPU 300

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version:

General introduction Part 2, chapter 11

EAP 300 REMOTE ANNUNCIATOR INSTALLATION MANUAL. r.0454a

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Installation Manual. Multi Power Controller MPC-1 multi-line D

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Compact Genset Controller, CGC 200 Mounting Terminals and wiring Commissioning, using the Utility Software and/or the front panel

M-Logic Internal Logic Controller Description of M-Logic Functional description List of possible selections for logics

INSTALLATION INSTRUCTIONS

Genset Controller Unit Model EMS - GC10. Installation Manual Section

Input Power Selector Switch. Product Manual (Revision NEW) Original Instructions for use with Generator Set Control Assembly

APPLICATION NOTES. Advanced Graphical Interface - AGI Internal PLC (CODESYS V3) SHENDONG

Delomatic 4, DM-4 Land DATA SHEET

MULTI-LINE 2 DESCRIPTION OF OPTIONS. Option N Modbus TCP/IP SMS/ alarms NTP time synchronisation. Document no.: D SW version:

MULTI-LINE 2 DESCRIPTION OF OPTIONS. Option N Modbus TCP/IP SMS/ alarms NTP time synchronisation. Document no.: C SW version:

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences

for Energy and Power meters AEM and APM with Modbus interface

Basic Gen-set Controller G (UK) SW version 2.1X.X. Terminal strip overview

Operating instructions IO-Link master CabinetLine AL19xx

Wiring Instructions for Replacement of 2301A Load Sharing and Speed Controls with 2301D Load Sharing and Speed Controls

APPLICATION NOTES. HEADING INDICATOR SYSTEMS using XDi-N indicators. Document no.: A

Application Note (Revision NEW) Original Instructions EGCP-3 LS Using an EGCP-3 in a Single-Phase Zig Zag Generator Application

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

PPM Protection and Power Management DATA SHEET

Application Note (Revision NEW) Original Instructions. Upgrading DRFDs to SPCs

EGCP-3 LS Revision R Software Revision M. Application Note (Revision NEW, 6/2009) Original Instructions

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

Installation Instructions

Delomatic 4, DM-4 Marine & Offshore DATA SHEET

Replacement of GCP-10 Series with easygen-1500 Application Note

Engines & Gen-sets N, page 1 of 6

Application Note (Revision NEW) Original Instructions. Wiring Instructions for 2301A Controls Replacing Caterpillar 2301 Controls

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

Engine & Genset Controls Z, page 1 of 12

Automatic Sustainable Controller, ASC Mounting Board slot positions Terminal strip overview I/O lists Wiring

TYPE APPROVAL CERTIFICATE

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

RVDT Setup and Polarity Checking Tool for EG Governors. Product Manual (Revision B) Original Instructions T87444

INSTALLATION INSTRUCTIONS

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

AGC 200 Advanced Gen-set Controller DATA SHEET

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Siemens Industrial s

DATA SHEET Automatic Genset Controller, AGC-3

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

Galaxy Shore Connection 500 kva. Operation 04/

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY

ProTech-SX Simplex System. Product Manual 26546V2 (Revision A) Original Instructions , Volume 2 Programming and Configuration

AGC 200 Automatic Advanced Gen-set Controller DATA SHEET

SPARE PART ONLY. Basic Gen-set Controller Multi-line H SW version 2.31.X or later. Data sheet. Standard functions

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Basic Gen-set Controller multi-line F SW version 2.31.X or later

DELOMATIC - MULTI-FUNCTION SYSTEM PART 2 INSTALLATION INSTRUCTION

Generator Paralleling Controller, GPC-3 Gas Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Part No. Z , IA Nov OPERATION MANUAL. High Voltage Digitalmeter A

EGCP-3 LS Revision L. Application Note (Revision NEW, 12/2006) Original Instructions

Source-Transfer Application Guide

Generator Paralleling Controller, GPC-3 Regulation modes Generator protection (ANSI) M-Logic (Micro PLC) Busbar protection (ANSI) Display General

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

LVDT Test Device. Product Manual (Revision B) Original Instructions. Testing and Calibration of LVDT Feedback Devices on PG Governors

PPU Power Management (PPM)

1395 Node Adapter Board Troubleshooting

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DATA SHEET. AGC PM Automatic Genset Controller, Plant Management

Transcription:

APPLICATION NOTES H-coupling Application description Functional description Wiring Basic setup Flowcharts Document no.: 4189340548A SW version 3.3X.X or later

Table of contents 1. WARNINGS AND LEGAL INFORMATION... 3 LEGAL INFORMATION AND RESPONSIBILITY... 3 ELECTROSTATIC DISCHARGE AWARENESS... 3 SAFETY ISSUES... 3 DEFINITIONS...3 2. APPLICATION SETUP... 4 DEFINITIONS...4 3. APPLICATION DESCRIPTION... 5 SYSTEM OVERVIEW... 5 REQUIRED HARDWARE... 6 4. FUNCTIONAL DESCRIPTION... 7 DISPLAY... 8 5. WIRING... 10 AGC MAINS... 10 AGC DG... 12 BTB... 14 6. BASIC SETUP... 16 POWER PLANT CONFIGURATOR... 16 AOP-1 SETUP... 17 7. FLOWCHARTS... 18 FIXED POWER TO MAINS 18... 18 MAINS FAILURE (MAINS 17)... 19 DEIF A/S Page 2 of 19

1. Warnings and legal information This chapter includes important information about general legal issues relevant in the handling of DEIF products. Furthermore, some overall safety precautions will be introduced and recommended. Finally, the highlighted notes and warnings, which will be used throughout this handbook, are presented. Legal information and responsibility DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the generator set controlled by the unit, the company responsible for the installation or the operation of the set must be contacted. The units are not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost. Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary. Safety issues Installing the unit implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment. Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death. Definitions Throughout this document a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text. Notes The notes provide general information which will be helpful for the reader to bear in mind. Warnings The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed. DEIF A/S Page 3 of 19

2. Application setup Setup of the power management application is done in the below listed menus and in the PC utility software. Even small changes in these menus can change the sequences a lot and will give you the possibility to customise the application to fulfil your needs. The functionality and influence of the application will be described briefly for each of the menus. The menus to take into consideration are: AGC mains Menu 8180 Menu 8020 Menu 8190 Menu 7080 AGC bus tie Menu 2300 AGC gen. Menu 8000 Menu 8010 Menu 8020 Function MB TB BTB GB AGC mains AGC bus tie AGC gen. Section Static section Dynamic section Common set point USW Definitions Description Mains Breaker. Tie Breaker. Bus Tie Breaker. Generator Breaker. Controlling an MB and a TB. Controlling a BTB. Controlling a gen-set and a GB. Part of the total application which is separated by one or two open BTBs. An application can contain up to 9 sections. Part of the total application which is separated by one or two open BTBs. There will be no closed BTBs within this section itself. Part of the total application which is separated by one or two open BTBs. There may be one or more closed BTBs within this section A set point which has to be identical for all AGC units to ensure correct functionality. A common set point is broadcasted on the CAN communication between the AGC units and will be changed back to the original set point. Utility software. The PC tool used to configure the AGC controllers. Pleas refer to the option G5 manual for detailed descriptions. DEIF A/S Page 4 of 19

3. Application description System overview This document describes what is needed to make a control system to an emergency power plant consisting of two mains connections, 4 diesel generators and one bus coupler connected like shown on the single line diagram below. The drawing shows 4 generators, but the system supports up to 16 generators. The system will be made with the following functionalities: 1. Section 1 will be operating in automatic mains failure (AMF) mode. 2. Section 2 will be in fixed power mode with automatic shift to automatic mains failure (AMF) in case of a mains failure. 3. Test mode will be a full test on each mains individually. 4. Additional display units (DU-2) with an AOP-1 for each mains unit. DEIF A/S Page 5 of 19

Required hardware To support this application, the following hardware is required: Mains breaker and tie breaker control 2 AGC mains units with standard display and the following options: Option G5 (power management) Option J1 (display cable) Option X2 (additional display unit) Option X3 (AOP-1) Regarding mains protection, please refer to the requirements from the local utility company. Gen-set control 4 AGC units with standard display and the following options: Option D1 (AVR control) Option G4 or G5 (power management) Option J1 (display cable) Additional options regarding generator protection should be added, if needed. The required interface for the governor and AVR should be taken into consideration. Please refer to the document Interfacing DEIF equipment to governors and AVRs. Bus coupler control 1 AGC bus tie unit with the following options: Option G4 or G5 (power management) Option X2 (display) Option J1 (display cable) The AGC bus tie unit can be replaced by a uni-line relay type FAS-113DG. Please refer to the data sheet for specific information about the possible options selection and order specification. DEIF A/S Page 6 of 19

4. Functional description In normal conditions, the application will work as 2 separate sections and the mains supervision will be done on each mains independently of the other. In case of a mains failure on one of the mains connections the gen-sets in each system will supply the load. However, in case of low available power the system will be allowed to close the BTB and use the gen-sets in the other system as well. Fixed power to mains When the plant is started, the gen-sets will be started, synchronise to prioritised mains, ramp up and produce power according to the fixed power set point. Test mode When activated, the test mode will be a full test on each mains individually. Start and stop engines The AGC will control the start and stop of the engine. This is done automatically or controlled by the operator in Semi-auto or Manual. Synchronisation of breakers Synchronisation of the breakers is done automatically according to the plant mode, or it can be done in Semi-auto by the operator. Mains failure sequence Normal condition (DGs are not running): - Mains supply OK - MB17 and MB18 closed - TB17 and TB18 open - BTB33 open - All gen-sets stopped Mains failure on mains 17 (auto switch adjusted to static section menu 8184): - MB17 is tripped - DG1 and DG2 are started, the first to be ready will close its GB on the black busbar, and the other GB will be synchronised - TB17 will be closed Load increases above the limit of 2 gen-sets: - BTB33 is closed - DG3 is started and synchronised - If needed, DG4 is started and synchronised Mains restored on mains 17: - MB17 is synchronised and closed (mains parallel = ON menu 8182) - TB17 is opened - All GBs and BTB33 are opened - Gen-sets will cool down and stop DEIF A/S Page 7 of 19

Fixed power to mains - Start is activated - The needed gen-sets are started and synchronised to mains - If more than 2 gen-sets are needed, BTB33 is closed and additional gen-sets are started and synchronised (depends on settings) - The gen-sets ramp up to the fixed power set point Display The display of the AGC used in this application looks like this: Generator unit BTB unit DEIF A/S Page 8 of 19

Mains unit AOP-1 DEIF A/S Page 9 of 19

5. Wiring The purpose of this chapter is to show the signals that are required as a minimum to run this application. The required signals are marked with an arrow. AGC mains DEIF A/S Page 10 of 19

For guidelines regarding wiring, please refer to the Installation Instructions. DEIF A/S Page 11 of 19

AGC DG DEIF A/S Page 12 of 19

For guidelines regarding wiring, please refer to the Installation Instructions. DEIF A/S Page 13 of 19

BTB DEIF A/S Page 14 of 19

DEIF A/S Page 15 of 19

6. Basic setup Power plant configurator DEIF A/S Page 16 of 19

AOP-1 setup DEIF A/S Page 17 of 19

7. Flowcharts Fixed power to mains 18 DEIF A/S Page 18 of 19

Mains failure (mains 17) DEIF A/S reserves the right to change any of the above DEIF A/S Page 19 of 19