FY Series Digital PID Controller Operation Manual FY400 FY700 FY800 FY900 FY600

Similar documents
FY Series Microprocessor PID Controllers

PXR Series Advanced Self-Tuning Temperature and Process Controllers

Digital Indicating Controllers. JC Series. High performance controllers...at the lowest prices anywhere! Toll Free

DC1010 DC1020 DC1030 DC1040

FY100 FY101 FY400 FY600 FY700 FY800 FY900 FA200 FA211 TAIE COMMUNICATION MANUAL DIGITAL PID CONTROLLER. March, 2009 FY_COMM_EN_V1.

- SELF-TUNING PID ALGORITHM - INTUITIVE COLOR DISPLAY WITH TEXT MESSAGING - UNIVERSAL PROCESS AND TC/RTD INPUTS - MULTI- FUNCTION RAMP- DWELL/PROCESS

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

DIGITAL INDICATING CONTROLLER

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

Digital Controller-Version II ES100X/P. Ordering Information. Intelligent Digital Controller and Programmer

OLS VT10 SERIES STANDARD DUAL DISPLAY PID AUTOTUNE RAMP-TO-SETPOINT ULC, UL, CE (4810) AUTO / MANUAL 15 SECURITY OPTIONS UNIVERSAL INPUT

ABB Instrumentation. Specification DataFile COMMANDER 100. the-easy-to use 1. /8 DIN controller with extensive application capabilities

MLC 9000 Bus Compatible PID

SX90 Process Controller

/8 DIN Motorized Valve Controller

Universal Process Controller

Drawings. Model UT35A Digital Indicating Controller (UT35A-NNN-xx-xx/x) SD 05P01D41-05EN. External Dimensions. Panel Cutout Dimensions.

Single Loop Controller Models R35, R36

Chapter. Modbus. In This Chapter...

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

UDC1200 and UDC1700 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

MRC 7000 Proven Recording Reliability that Became the Industry Standard!

Temperature, Process &

Single Loop Controller Model R15

Universal power supply

MODCELL 2050R Single Loop Controllers

Paperless Recorder VGR-B100. Series

Temperature/Process Controllers Manual

Single Loop Controller SDC15

JUMO Quantum PID100/PID200/PID300

DPST-NO None 2 channels Auto-reset Inverse (+/-) 24 VAC/VDC 4 G9SB-2002-A 1 channel or 2

The CAL range of temperature controllers

MODEL: SC100. Single Loop Controller Series. MULTI-FUNCTION PID CONTROLLER (color LCD with touch-panel) MODEL: SC100 [1]0 [2][3]

Description Model Specification Base Unit E5AK-AA2 AC Standard model

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

NX-series Temperature Control Unit NX-TC

Control IT. /16 DIN Controller/Alarm Unit. Data Sheet SS/C50_7 C50. C50 the 1 /16 DIN controller to suit your simplest applications

PLC PL User Manual

Tempco Instruction Manual

2. Terminal arrangement TEMPERATURE CONTROLLER KT2 COMMUNICATION INSTRUCTION MANUAL. (Fig. 2-1)

UDC1200 & UDC1700 Universal Digital Controllers Series Micro-Pro Specifications

ProVU 4 Advanced Temperature & Process Controller

TIMERS FOR ALL APPLICATIONS

Temperature/Process Meter

/8 DIN Universal Process Indicator

I-7520: RS-232 to RS-485. Input: RS-232 protocol Output:RS-485/RS-422 Speed: Self Tuner 'inside, auto switching baud rate, 300~ BPS

Main contacts Auxiliary contact Number of input channels Rated voltage Model Category 24 VAC/VDC 3PST-NO SPST-NC 1 channel or 2 channels possible

FICHA TÉCNICA DE PRODUTO

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL

SINGLE-CHANNEL PROCESS INDICATOR series 8001

Wall-/Pipe Mounted Universal Process Indicator

deltadue series DIN rail mounting modules for control and data acquisition

2. Actuator B: Ball type P: Pin type F: Flat type

RS485 MODBUS Module 6RO

SRZ. Instruction Manual. Module Type Controlle r. [For PLC Communication] IMS01T13-E1 RKC INSTRUMENT INC.

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

G9SA. Ordering Information. Safety Relay Unit. The G9SA Series Offers a Complete Line of Compact Units. H Several types of 45-mm wide Units are

Communicative controller for VAV systems

P/N /02 Rev. C ECO # Model 1440 Microprocessor-based Temperature Controller Installation and Operation Manual

TECHNICAL DATA SHEET. ProVU 4 Advanced Temperature Controller. Features. Description

ATR121 Controller with Dual Setpoint

PID with. Controllers W A T L O W CPC400 SERIES. Multi-Loop

Neon pr. ph/ ORP measurement. Applications. Description

i8 Series from $240 1/8 DIN Temperature/Process & PID Controllers

S-Line HIGH BRIGHTNESS AND ACCURACY DIGITAL LED INDICATORS MODULAR INDICATORS / TOTALIZERS WITH UNIVERSAL ANALOG INPUT

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

C160 Wall-/Pipe Mounted Universal Process Indicator

NF760 Batch Controller

SYSMAC Remote Transistor Module

Yokogawa Advanced Controllers

isma-b-fcu FCU Hardware User Manual Global Control 5 Sp. z o.o. Warsaw, Poland

A16. Separate Construction with Cylindrical 16-dia. Body. Pushbutton Switch (Detachable) (Lighted/Non-Lighted) (Cylindrical 16-dia.

Trident and Trident X2 Digital Process and Temperature Panel Meter

Distributed Multi-Channel Controller DMC10

MODEL: R1M-D1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

Series Temperature Controller Instruction Sheet

RB100/RB400 RB500/RB700 RB900

PRODUCT FAMILY: SOLO Controllers Number: AN-LC-009

Solid-state Timer. Ordering Information. Ultra-slim Timer for G2R Relay Socket. H3RN-jj. Accessories (Order Separately) Connecting Socket

Digital Panel Meters Modular signal s conditioner Type USC-DIN

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Instructions for Switched TPC Series Control Consoles

Module Type Controller SRX Temperature Control Module for PROFIBUS X-TIO-G Instruction Manual

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)

Controllers & Indicators User Guide

Zenex-ultra Ultra Precision (0.01 C) Self-Tune PID Temperature Controller with Programmable Timer

Eclipse Combustion Universal Digital Controller

MODEL: R1M-P4. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

E2Q4 Square Proximity Sensor

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

INSTRUCTION MANUAL FOR PC LINK UNIT CLT-20S

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

MODEL: R1M-GH. PC Recorders R1M Series

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

USER'S GUIDE FX-485ADP COMMUNICATION ADAPTER FX0N-485ADP COMMUNICATION ADAPTER

Englisch. Operating Manual. Temperature controller 2-, 3-point- and continuous R ba_ma_r11xx-10_60-ma1-xx

HAT162 ATS CONTROLLER USER MANUAL

MODEL: R1M-A1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

Transcription:

FY Series Digital PID Controller Operation Manual FY101 90X90mm FY100 15X110mm FY400 FY00 FY800 FY900 FY600 48x48mm 2X2mm 48X96mm 96X96mm 96X48mm (DIN 1/) (DIN 3/) (DIN 1/8) (DIN 1/4) (DIN 1/8) February, 200 FY_OPER_EN_V6 TAIE

CONTENT 1 Notice before start- up Page 3 2 Specifications Page 4 3 Terminal arrangement 3.1 FY400 Terminals Page 6 3.2 FY600 Terminals Page 3.3 FY00 Terminals Page 8 3.4 FY800 Terminals Page 9 3.5 FY900 Terminals Page 10 3.6 FY100 Terminals Page 11 3. FY101 Terminals Page 12 4 External dimension and panel cutout 4.1 FY100-FY101 Page 13 4.2 FY400-FY900 Page 5 Parts description Page 6 Operations 6.1 Power On.. Page 6.2 Change the Value (SV) Page 6.3 Change The Alarm Value Page 6.4 Autotuning (AT).. Page 1 6.5 Programmable RAMP / SOAK.. Page 18 Operation levels.1 Levels diagram. Page 19.2 Lock function.... Page 19 8 Parameters 8.1 Level 1 (User Level) Page 20 8.2 Level 2 (PID Level) 8.2.1 Level 2 parameters display / hiding condition..... Page 21 8.2.2 Description of parameters Page 22 8.3 Level 3 (Input Level) Page 23 8.4 Level 4 (SET Level) 8.4.1 How to hide parameters (Use SET1~SET) Page 25 8.4.2 Special functions (Use SET8 / SET9 / SET0).. Page 26 8.4.3 Remote SV type selection Page 2 8.4.4 Output mode selection (Use OUTY) Page 2 8.4.5 Modify caution Page 2 8.5 Program Level 8.5.1 Description of parameters Page 28 1

8.5.2 Description of operation Page 29 9 Input type table Page 30 10 Alarm 10.1 Alarm time Page 32 10.2 SETA Page 32 10.3 Alarm mode Page 33 11 Heater Break Alarm(HBA). Page 34 11.1 HBA Wiring Example.... Page 34 11.2 HBA Function Description.... Page 34 11.3 HBA setting procedure.. Page 35 11.4 Parameters for HBA function...... Page 35 11.5 Activated conditions of HBA.. Page 36 11.6 Remarks..... Page 36 11. CT specifications 11..1 SC-80T Specifications..... Page 3 11..2 SC-100T Specifications.. Page 3 11..3 SC-80T Linear Diagram... Page 38 12 Error codes Page 39 13 Modify input type: TC, RTD 13.1 FY400~FY900 Page 40 13.2 FY100~FY101 Page 41 Modify input type: Linear Input (ma,v).1 FY400~FY900 Hardware Page 43.2 FY100~FY101 Hardware Page 44.3 Calibration Page 45 Modify output type: Relay, SSR, 4~20mA Page 46 Modify output mode: OUT1/ALARM, OUT1/OUT2 Page 46 1 Applications 1.1 RAMP & SOAK.. Page 4 1.2 TTL Communication SV output and RATE function Page 48 1.3 1 Phase angle control (By SCR module) Page 49 1.4 1 Phase angle control (By TRIAC)... Page 50 1.5 3 Phase angle control ( By DIODE/SCR module).. Page 51 1.6 1 Zero crossing control (By SCR Module).. Page 52 1. 1 Zero crossing control (By TRIAC). Page 53 1.8 3 Zero crossing control (By SCR module) Page 54 1.9 3 Zero crossing control (By TRIAC) Page 55 1.10 3 wires proportional motor valve control.. Page 56 1.11 Wiring diagram of PC Communication. Page 5 2

1. Notice before start-up FY series controller has got the CE approvals as below: LVD D/N EN61010-1 EMC EN 55 022 1994 /A1 1995/ A2 199 EN 61 000-3-2 1995 / -3-3 1995 EN 61 000-4-2 1995 / -4-3 1996 / -4-5 1995 / -4-6 1996 / -4-8 1993 / -4-11 1996/ EN 50 204 1995 Please confirm the specification of controller is to totally with your requirement before using it, also read this manual in detail. Danger 1. Danger! Electric Shock! DON'T touch AC power wiring terminals when controller has been powered! Keep the power off until all of the wirings are completed! Warning 1. Please confirm the AC power wiring to controller is correct, otherwise it would be caused aggravated damage on controller. ( FY400 connecting with Pin 1 and 6, FY100/FY101/FY600/00/800/900 with Pin 1 and 2). 2. Be sure to use the rated power supply (AC85~265V or DC24V), otherwise it would be caused aggravated damage on controller. 3. Please confirm wires are connected with correct terminal (Input, Output). 4. Use M3 screw-compatible crimp-on terminals with an insulation sleeve, as shown below 3.2mm 3.2mm Torque : 0.4 N.m (4kgf.cm) 5. Avoid installing controller in following spaces: I. A place where the ambient temperature may reach beyond the range from 0 to 50 II. A place where the ambient humidity may reach beyond the range from 20 to 90% RH. III. A place where the controller likely to come into contact with water, oil, chemicals, steam and vapor. IV. A place where the controller is subject to interface with static electricity, magnetism and noise. 6. For thermocouple (TC) input, use shield compensating lead wire.. For RTD input, use shield wires which have low resistance and no resistance difference between the 3 wires. 3

1. Specifications Standard spec. Model FY400 FY600 FY00 FY800 FY900 FY100 FY101 Dimension 48X48mm 96X48mm 2X2mm 48X96mm 96X96mm 15X110mm 90X90mm Supply voltage AC 85~265V DC ~50V (Option) AC 85~265V Frequency 50 / 60 HZ Power consumption approx 3VA approx 4VA approx 3VA approx 4VA approx 4VA approx 4VA approx 3VA Accuracy 0.2 % FS 1digit Sample time 250ms TC K, J, R, S, B, E, N, T, W5Re/W26Re, PLII, U, L Output 1 Input RTD PT100,JPT100,JPT50 ma dc 4~20mA,0~20mA mv / V dc 0~1V,0~5V,0~10V,1~5V,2~10V -10~10mV,0~10mV,0~20mV,0~50mV,10~50mV Decimal point position Relay Voltage pulse ma dc Voltage dc Alarm 1 Control algorithm 0000, 000.0, 00.00, 0.000 Available for linear input (ma / mv / V) SPST type SPDT type SPST type SPDT type SPDT type SPDT type SPDT type 3A, 220V, electrical life:100,000 times or more (under rated load) For SSR drive. ON : 24V, OFF : 0V, max load current : 20mA 4~20mA, 0~20mA. Maximum load resistance:560 0~5V, 0~10V, 1~5V, 2~10V. Max load current:20ma 3A, 220V, electrical life:100,000 times or more (under rated load) PID PI PD P ON / OFF(P=0) FUZZY PID range P: 0.0 ~ 200.0 % I: 0~3600s D: 0~900s Isolation Output terminals(control output, alarm, transmission) and input terminals are isolated separately Isolated resistance 10M or more between input and case (ground) at DC 500 V 10M or more between output and case (ground) at DC 500 V Dielectric strength 1000V AC for 1 minute between input terminal and case (ground) 00V AC for 1 minute between output terminal and case (ground) Operating 0~50 temperature Humidity range 20~90%RH Weight 0g 225g 225g 225g 300g 130g 80g Display Height PV:mm PV:mm PV:mm PV:mm PV:mm SV:mm SV:mm SV:10mm SV:mm SV:10mm 4

Optional Spec. Model FY400 FY600 FY00 FY800 FY900 FY100 FY101 Output 2 For heating and cooling control use. Relay, SSR, 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V Alarm 2 Alarm 3 Heater Break Alarm (HBA) Transmission Available Available Available Available Available Available Not SPST type SPDT type SPST type SPDT type SPDT type SPDT type available 3A, 220V, electrical life:100,000 times or more (under rated load) Not Available Available Available Available Available Not available SPST type SPST type SPST type SPST type SPST type available 3A, 220V, electrical life:100,000 times or more (under rated load) Display range of heater current : 0.0~99.9A, Accuracy : 1%FS Included CT : SC-80-T (5.8mm dia, 0.0~80.0A) or SC-100-T (12mm dia, 0.0~99.9A) Alarm relay : AL1 Available for PV or SV transmission 4~20mA, 0~20mA, 0~1V, 0~5V, 0~10V, 1~5V, 2~10V Remote SV 4~20mA, 0~20mA, 0~1V, 0~5V, 0~10V, 1~5V, 2~10V Communication Protocol : MODBUS RTU, MODBUS ASCII, TAIE RS232, RS485, TTL Baud rate: 2400, 4800, 9600, 19200, 38400 bps. Data bits : 8, Stop bit : 1 or 2bit, Odd or Even parity. Water/Dust proof IP65 Special control output (OUT1) Model FY400 FY600 FY00 FY800 FY900 FY100 FY101 1 zero crossing control(1 SSR) 3 zero crossing control(3 SSR) Motor valve control 1 phase angle control(1 SCR) 3 phase angle control(3 SCR) Available Not available Available Not available Not available Available Available Not available Not available Available Not Not available available Not available Available Available Not available Not available Available Not Not available available Programmable RAMP/SOAK Model PFY400 PFY600 PFY00 PFY800 PFY900 PFY100 PFY101 Programmable 2 patterns with 8 segments each. RAMP/SOAK The 2 patterns can be linked together as segments use. 5

3. Terminal arrangement 3.1 FY400 Terminals ( 48mm x 48mm, DIN 1/ ) H.CT Input 11 CT 12 2 3 2 3 13 11 12 G1 K1 G2 11 11 11 K2 12 12 12 13 13 6

3.2 FY600 Terminals ( 96mm x 48mm, DIN 1/8 ) 1 2 3 4 5 11 12 13 6 8 9 10 1 18 19 20 H.CT Input CT 6 1 1 1 18 18 18 19 19 19 20 20 20 6 12 13 6 K2 8 G2 8 9 10 9 10 K1 G1

3.3 FY00 Terminals ( 2mm x 2mm) 1 8 2 9 3 4 1 18 10 11 H.CT Input 5 19 12 6 20 13 CT 21 5 6 3 4 11 11 11 12 12 12 13 13 13 3 4 COM NO 8 9 18 19 3 4 5 6 1 19 G1 G2 20 PROT 1 18 G1 K1 G2 K2 NC 10 9 20 10 21 PROT 1 1 8

3.4 FY800 Terminals ( 48mm x 96mm, DIN 1/8 ) 1 2 3 4 5 11 12 13 6 8 9 10 1 18 19 20 H.CT Input CT 6 1 1 1 18 18 18 19 19 19 20 20 20 6 12 13 6 K2 8 G2 8 9 10 9 10 K1 G1 9

10 3.5 FY900 Terminals ( 96mm x 96mm, DIN 1/4 ) 6 6 1 2 3 4 5 6 8 9 10 21 22 23 24 25 26 2 28 29 30 1 18 19 20 1 18 19 20 1 18 19 20 39 40 G1 G2 40 31 33 39 PROT G1 K1 G2 K2 6 8 9 10 36 31 32 33 34 35 PROT RG1 RG2 TG1 TG2 40 31 33 35 3 39 PROT G1 K1 G2 K2 40 31 32 33 34 39 PROT G3 K3 35 36 31 32 33 31 32 11 12 13 1 18 19 20 31 32 33 34 35 36 3 38 39 40 H.CT Input CT

3.6 FY100 Terminals ( 15mm x 110mm ) 11

3. FY101 Terminals ( 90mm x 90mm ) 12

4. External dimension and panel cutout Unit mm 13

4.3 FY400-900 44.5+0.5 FY400 0 44.5+0.5 65 90.5+0.5 FY600 0 44.5+0.5 111 68.5+0.5 FY00 94 68.5+0.5 89 44.5+0.5 FY800 1 90.5+0.5 65 90.5+0.5 96 1 90.5+0.5 FY900 96 111

5. Parts description FY400 FY600 FY800 FY00 / FY900/ FY100/101 1 2 External Interface Unit 8 9 10 11 12 13 8 11 8 9 12 5 9 10 1 2 3 5 6 Y1 Y2 AT AL1 AL2 PRO 9 10 11 12 1 2 13 10 4 3 6 8 12 13 4 11 1 2 3 5 6 3 4 5 6 SYMBOL NAME FUNCTION PV Measured value (PV) display SV value (SV) display Displays PV or various parameter symbols (Red) Displays SV or various parameter set values (Green) SET key Used for parameter calling up and set value registration A/M Auto/Manual key Switches between Auto(PID) output mode and Manual output mode. Shift key Shift digits when settings are changed Down key *Program hold Up key *Program run Decrease numbers (-1000,-100,-10,-1) * Program hold Programmable controller Decrease numbers (+1000,+100,+10,+1) * Program run Programmable controller OUT1 OUT1 lamp Lights when OUT1 is activated (Green) OUT2 OUT2 lamp Lights when OUT2 is activated (Green) AT Auto tuning lamp Lights when Auto tuning is activated (Orange) AL1 Alarm 1 lamp Lights when Alarm 1 is activated (Red) AL2 Alarm 2 lamp Lights when Alarm 2 is activated (Red) AL3 Alarm 3 lamp Lights when Alarm 3 is activated (Red) MAN Manual output lamp Lights when manual output is activated (Orange) PRO *Program running lamp OUT1% OUT% bar-graph display *Flashes when program is running Programmable controller Output% is displayed on 10-dot LED.

6. Operations 6.1 Power On Controller will display as below All LED and segment displays will be lighted Display input type (K2) Display range (0.0~400.0) Ready for use 6.2 Change the Value (SV) Change SV from 0.0 to 100.0 SET 6.3 Change the Alarm Value Change AL1 value to 5.0 (AL1 active, if PV exceeds SV over 5.0) Press SET key to display parameter AL1 Press key to change AL1 value Press key increase AL1 value Press SET key store the new value of AL1 * The are total alarm mode types, please referred with alarm mode in page 30 * To change alarm mode, press SET + key 5 seconds to enter Level 3 (Input Level) and then change ALD1/ALD2/ALD3 value.

6.4 Autotuning (AT) Use AT function to automatically calculate and set the optimize PID value for your system. Press SET key to display parameter AT. SV Autotuning ATVL=0 (Overshoot ) PV Press key Press key Press SET key to change AT setting change AT to YES Start auto tuning (AT lamp will be lighted on) Autotuning ATVL=20 * ATVL to prevent overshoot occurred during autotuning process. To set ATVL,press SET key 5 seconds to enter Level 2 (PID Level) and then change the value. SV SV - 20 PV 100% Output% 0% ON OFF ON OFF 100% Output% 0% ON OFF ON OFF ON / OFF Control (Autotuning) PID Control (After Autotuning) ON / OFF Control (Autotuning) PID Control (After Autotuning) Autotuning failure Possible cause 1 ATVL is too big. (If not sure set ATVL=0) Possible cause 2 Calculation time is too long. ( PID parameter manually) 1

6.5 Programmable RAMP / SOAK (Only available for PFY model) *For detail of the programmable instruction, please refer with page 25. Assume the temperature profile is as below (use total 4 segments ) SV 200 120 1 hour 30 minutes 50 minutes Please operate conroller as following steps: 1 hour and 20 minutes Press SET key to display SV_1 SV_1 to 200.0 TM_1 to 01.00 (1 hour) OUT1 to 100.0 SV_2 to 200.0 TM_2 to 00.30 (30 minutes) OUT2 to 100.0 SV_3 to 120.0 TM_3 to 00.50 (50 minutes) OUT3 to 100.0 SV_4 to 120.0 TM_4 to 01.20 (1 hour and 20 minutes) OUT4 to 100.0 Press key to run program (PRO LED start lighting) 18

. Operation levels.1 Levels diagram Level 1 (User Level) SET LCK = 0000 SET SET Level 2 (PID Level) Level 3 (Input Level) LCK = 1111 SET SET Level 4 (SET Level) A/M SET.2 Lock function To use lock function, please set parameter LCK in level 2. LCK Levels entering available Parameters which can be Level 1 Level 2 Level 3 Level 4 changed (User) (PID) (Input) (SET) ------ All parameters (Factory set value) ------ All parameters ------ ------ All parameters except level 3 ------ ------ Parameters in level 1 ------ ------ SV and LCK ------ ------ Only LCK 19

8. Parameters 8.1 Level 1 (User Level) PV SV 20

8.2 LEVEL 2 (PID Level) To enter level 2, press SET key 5 seconds in level 1 8.2.1 Level 2 parameters display / hiding condition 1. Press SET key 5 seconds to enter level 2. 2. LCK to 1111 3. Press SET key and key 5 seconds, to enter level 4 ( level). 4. OUTY to 0 (Single output-p1). 1. Press SET key 5 seconds to enter level 2. 2. LCK to 1111 3. Press SET key and key 5 seconds, to enter level 4 ( level). 4. OUTY to (Dual output - P1/P2). Single output - P1 Dual output - P1/P2 P1 0 P1 0 P1 0 P2 0 P1 0 P2 0 P1 0 P2 0 P1 0 P2 0 21

8.2.2 Description of parameters LCK Levels entering available Parameters which can be Level 1 Level 2 Level 3 Level 4 changed (User) (PID) (Input) (SET) ------ All parameters (default value) ------ All parameters ------ ------ All parameters except level 3 ------ ------ Parameters in level 1 ------ ------ SV and LCK ------ ------ Only LCK 22

8.3 LEVEL 3 (Input Level) To enter level 3, set LCK to 0000 and then press SET key + Shift( ) key 5 seconds. 23

24

8.4 Level 4 (SET level) To enter level 4, set LCK to 1111 and then press SET key + Shift( ) key 5 seconds. Press SET Key Press SET Key SET SET SET SET SET Display/hiding parameters Special functions Remote SVOutput mode ting selection 8.4.1 How to hide parameters (Use SET1~SET) PV SV 0 1 *For the description of Level 1 parameters, please refer with page 1. *For the description of Level 3 parameters, please refer with page 20. SET Display / hiding Level SET Display / hiding Level 1_ 1 Level 1 5_ 1, Level 3 1_ 2 Level 1 5_ 2, Level 3 1_ 3 Level 1 5_ 3,, Level 3 1_ 4 Level 1 5_ 4,,, Level 3 2_ 1 Level 1 6_ 1 Level 3 2_ 2,, Level 3 6_ 2 Level 3 2_ 3, Level 3 6_ 3 Level 3 2_ 4, Level 3 6_ 4 Level 3 3_ 1 Level 3 _ 1 Level 3 3_ 2 Level 3 _ 2 Level 3 3_ 3 Level 3 _ 3 Level 3 3_ 4 Level 3 _ 4 Level 3 4_ 1 Level 3 4_ 2 Level 3 4_ 3 Level 3 4_ 4, Level 3 25

8.4.2 Special functions (Use SET8 / SET9 / SET0) SET 8 8_ 1 0 : Program not repeat 1 : Program repeat 8_ 2 0 : No power failure option 1 : With power failure option 8_ 3 0 : Program starts from 0 1 : Program starts from PV 8_ 4 0 : Reserved (Don t change it) Remark Only available for programmable controller SET 9 9_ 1 0 : Reserved (Don t change it) Remark 9_ 2 9_ 3 9_ 4 0 : Timer Unit = Hour : Minute 1 : Timer Unit = Minute : Second 0 : Disable transmission 1 : SV Transmission 0 : Disable transmission 1 : PV Transmission Only available for programmable controller Used for transmission output 0_ 1 0_ 2 SET 0 0 : TTL Communication (Slave) 1 : TTL Communication (Master) 0 : Hide parameter RATE Remark Used for TTL communication 0_ 3 1 : Display parameter RATE AL3 will be replaced by RATE 0 : Disable Remote SV function Used for Remote SV 1 : Enable Remote SV function function 0_ 4 0 : use output relay b contact when motor valve closed 1 : use output relay a contact when motor valve closed Used for 3 wire proportional motor valve control 26

Please don't operate SET 8_4 otherwise the controller's process will be in confusion. If SET8.4 is set to 1, the controller will enter into Single Display mode, the PV LED will not display any values. The SV LED will display both the parameter value and the setting value alternately as shown in the diagram below. PV SV Displayed alternately To rectify the problem please press the SHIFT KEY ( 0000. ) and change the setting value to 8.4. 3 Remote SV type selection INP2=0 None INP2=1 10~50mV / 4~20mA / 1~5V / 2~10V INP2=2 0~50mV / 0~20mA / 0~5V / 0~10V INP2=4 CT input Remote SV function is not available for programmable controller 8.4. 4 Output mode selection (Use OUTY) OUTY=0 Single output (OUT1) OUTY=1 Dual output (OUT1 / OUT2) OUTY=2 Reserved OUTY=3 3 wire proportional motor valve control OUTY=4 1 Phase angle control (1 SCR) OUTY=5 3 Phase angle control (3 SCR) 8.4.5 Modify caution If change parameter BAUD, BITS, RUCY, OUTY the power must be reset 2

8.5 Program Level (Only displayed in programmable controller) 8.5.1 Description of parameters LEVEL 1 Program Pattern Range 0~2 Program Segment display ( Pattern _ Segment ) Program countdown display Range 0~99 hour 59 min ting value of Seg.1 Range LSPL~USPL time for Seg.1 Range 0~99 hour 59 min Output Limit of Seg.1 Range 0~100% If OUT=0 program will end. ting value of Seg.5 time for Seg.5 Output Limit of Seg.5 ting value of Seg.6 time for Seg.6 Output Limit of Seg.6 ting value of Seg.2 ting value of Seg. time for Seg.2 time for Seg. Output Limit of Seg.2 Output Limit of Seg. ting value of Seg.3 ting value of Seg.8 time for Seg.3 time for Seg.8 Output Limit of Seg.3 Output Limit of Seg.8 ting value of Seg.4 Return LEVEL 1 time for Seg.4 Output Limit of Seg.4 28

8.5.2 Description of operation 1. There are 2 patterns can be used each pattern contains 8 segments. 2. Terminologies Pattern 3. Operating A program consists of some steps. Ramp status The status with changing SV. Soak status The status with fixed SV. I. "KEY" function (no changing parameter) II. (RUN) (HOLD) Start program procedure PRO LED in panel start flicking. Suspend program procedure PRO LED in panel will stop flicker but still light on. + SET(JUMP) Jump to previous segment. + SET (RESET) Reset program procedure PRO LED in panel will off. Alarm Function ALD1 = 0 (Segment end alarm) AL1 = 2 (It means when segment 2 end,al1 will act) ALT1 = 00:10 (Relay on time is 10 seconds). In this case when program proceeds to segment 2 end the relay of AL1 will be on 10 seconds. III. END function The Controller doesn t have END order, so if program procedure is less than 8 segments, please set the last segment s OUT to 0. Program will end in this segment. Otherwise it will proceed 8 or segments. IV. Linking Function PTN=1 proceed pattern 1 contains 8 segments. PTN=2 proceed pattern 2 contains 8 segments. PTN=0 linking proceed pattern 1 and 2 totally segments. (Please set PTN1 and PTN2 at first and then set PTN to 0) V. Other function( refer to LEVEL 4) SET 8_1=1 Program repeats. SET 8_2=0 No power failure function. SET 8_2=1 Enable power failure function. (When power shut down and on again the controller will start from the segment which is near PV) SET 8_3=0 Program starts from 0. SET 8_3=1 Program starts from PV. SET 9_2=0 Timer Unit = Hour : Minute SET 9_2=1 Timer Unit = Minute : Second 29

9. Input type table (INP1 selection) TYPE CODE RANGE 0.0 ~ 200.0 / 0.0 ~392.0 K J R S 0.0 ~ 400.0 / 0.0 ~52.0 0 ~ 600 / 0 ~1112 0 ~ 800 / 0 ~2 0 ~ 1000 / 0 ~1832 0 ~ 1200 / 0 ~2192 0.0 ~ 200.0 / 0.0 ~392.0 0.0 ~ 400.0 / 0.0 ~52.0 0 ~ 600 / 0 ~1112 0 ~ 800 / 0 ~2 0 ~ 1000 / 0 ~1832 0 ~ 1200 / 0 ~2192 0 ~ 00 / 0 ~2912 0 ~ 9 / 0 ~32 0 ~ 00 / 0 ~2912 0 ~ 9 / 0 ~32 B 0 ~ 1820 / 0 ~3308 E N T W5Re/W26Re PL U L 0 ~ 800 / 0 ~2 0 ~ 900 / 0 ~52 0 ~ 1200 / 0 ~2192 0 ~ 1300 / 0 ~232-199.9 ~ 400.0 /-199.9 ~52.0-199.9 ~ 200.0 / -199.9 ~392.0 0.0 ~ 350.0 / 0.0 ~662.0 0 ~ 2000 / 0 ~3632 0 ~ 2320 / 0 ~4208 0 ~ 1300 / 0 ~232 0 ~ 1390 / 0 ~2534-199.9 ~ 600.0 / -199.9 ~999.9-199.9 ~ 200.0 / -199.9 ~392.0 0.0 ~ 400.0 / 0.0 ~52.0 0 ~ 400 / 0 ~52 0 ~ 800 / 0 ~2 30

TYPE CODE RANGE -199.9 ~ 600.0 / -199.9 ~999.9 JIS PT100 DIN PT100 JIS PT50-199.9 ~ 400.0 / -199.9 ~52.0-199.9 ~ 200.0 / -199.9 ~392.0 0 ~ 200 / 0 ~392 0 ~ 400 / 0 ~52 0 ~ 600 / 0 ~1112-199.9 ~ 600.0 / -199.9 ~999.9-199.9 ~ 400.0 / -199.9 ~52.0-199.9 ~ 200.0 / -199.9 ~392.0 0 ~ 200 / 0 ~392 0 ~ 400 / 0 ~52 0 ~ 600 / 0 ~1112-199.9 ~ 600.0 / -199.9 ~999.9-199.9 ~ 400.0 / -199.9 ~52.0-199.9 ~ 200.0 / -199.9 ~392.0 0 ~ 200 / 0 ~392 0 ~ 400 / 0 ~52 0 ~ 600 / 0 ~1112 AN1-10 ~ 10mV / -1999~9999 AN2 0 ~ 10mV / -1999~9999 AN3 0 ~ 20mV / -1999~9999 AN4 0 ~ 50mV / -1999~9999 AN5 10 ~ 50mV /-1999~9999 The initial setting in factory is K2. 31

10. Alarm 10.1 Alarm time (ALT1/ALT2/ALT3) ALT1=0 Flicker alarm ALT1=99.59 Continued alarm ALT1=00.01 ~ 99.58 Alarm on delay time 10.2 SETA *SETA is in Level 3 (Input level) If SETA_1=1 AL1 relay will be action reversely } When "b" contact If SETA_2=1 AL2 relay will be action reversely (normal close) is If SETA_3=1 AL3 relay will be action reversely needed If SETA_4=0 program run alarm If SETA_4=1 program end alarm Only available for } programmable controller 32

10.3 Alarm mode (ALD1 / ALD2 / ALD3) ( :SV :Alarm set value) 01 Deviation high alarm with hold action* OFF ON HIGH PV 06 Process low alarm with hold action* ON LOW OFF HIGH PV Deviation high alarm Process low alarm 11 OFF ON HIGH PV ON LOW OFF HIGH PV 02 12 03 13 04 05 Deviation low alarm with hold action* ON LOW OFF LOW ON Deviation low alarm ON LOW ON OFF LOW OFF OFF ON ON HIGH HIGH OFF HIGH ON HIGH ON OFF OFF Deviation high/low alarm with hold action* Deviation high/low alarm Band alarm HIGH HIGH Process high alarm with hold action* PV PV PV PV PV PV 0 1 08 18 00 10 Segment End alarm (Only for Programmable controller) (1) ALD1~3, set 0 (2) ALD1~3=Alarm Segment (3) ALT1~3 defines as follows: 0 99.59 others Program Run alarm (Only for Programmable controller) ON OFF ON No alarm OFF ON OFF AL System failed alarm* (ON) AL System failed alarm* (OFF) AL Heater Heater Break Break Alarm Alarm (HBA) Please refer with HBA Function function description Description in page Page34 31. 09 (HBA) Process high alarm OFF LOW ON HIGH PV *Hold action: When Hold action is ON,the alarm action is suppressed at start-up until the measured value(pv) enters the non-alarm range. *System failed: It means that the controller display error message with one of following : UUU1 or NNN1 or CJCE 33