309559 01 TR TR 608 top2 6080100 TR 609 top2 6090100 L N 230-240V~ 3 µ 50-60Hz R10a -25T 2 1 16(4)A 250V~ GB Installation and operating instructions Digital time switch D GB F I E NL TR 609 top2 MENU OK 3 Ext1 2 1 max. 100 m N L L Connection of different external wires is permitted TR 609 top2
Contents Basic safety instructions 3 Display and keys Operating instructions 4 Connection/installation 5 Overview of menu selection 6 Initial start-up Reset 7 Menu item PROGRAMM Program switching time 8 Check/modify switching time 10 Delete switching time 11 Pulse time programming 12 Cycle time programming 14 Menu item TIME/DATE 15 Menu item MANUAL 16 Override and permanent switching 16 Menu item OPTIONS 18 Enter PIN code 19 External input 20 OBELISK top2 memory card 22 Technical data 23 Service address/hotline 24 2
Basic safety instructions GB WARNING Danger of death through electric shock or fire! Installation should only be carried out by a qualified electrician! The device is designed for installation on DIN top hat rails (in accordance with EN 60715) Corresponds to type 1 BSTU in accordance with IEC/EN 60730-2-7 / IEC/EN 60730-1 Power reserve (10 years) is reduced if memory card is inserted (in battery operation) Designated use The time switch can be used for lighting, bell systems, ventilation etc. Only use in enclosed dry spaces Do not use on safety devices, e.g. escape route doors, fire safety equipment etc. Disposal Dispose of device and batteries separately in an environmentally sound manner 3
Screen and keys Operating instructions Date display Time display Channel status ON = On AM PM OFF = Off Weekdays from 1 to 7 1. Read text lines Text represents query 2. Make a decision MENU MENU OK OK Activate screen Open menu Cancel menu ESC (1 step back) Store selection Confirm selection YES Confirmation NO Amend/ change Options are displayed Press OK Press 4
Connection/installation WARNING Warning, danger of death through electric shock! Must be installed by qualified electrician! Disconnect power source. Cover or shield any adjacent live components. 45 cable Ensure device cannot be switched on! Check power supply is disconnected. Plug-in terminal Earth and bypass. GB Connect cable Strip cable by 8 mm (max. 9 mm). Insert cable at 45 in the open terminal (2 cables per terminal position possible). Only with flexible wires: To open the plug-in screwless terminal, press screwdriver downwards. Plug-in screwless terminal NC contact Test tap 5
Overview of menu selection MENU 19 05 11 ON 35 9:40 1 PROGRAM TIME/DATE MANUAL OPTIONS NEW CHECK MODIFY TIME DATE SU-WI PERM ON PERM OFF OVERRIDE ON OPERATING HOURS EXTERNAL INPUT* LANGUAGE END DELETE WEEK DAY TIMER* PIN END FORME DATE HOLIDAY FACTORY SETTINGS FORME TIME RANDOM* INFO END END END * only with TR 609 top2 6
Initial start-up GB Set date, time and summer/ winter time rule Press required key and display follows on screen (see figure). RESET Press the 4 buttons simultaneously. You can choose between RETAIN PROGRAM and DELETE PROGRAM. ENGLISH RETAIN PROGRAM FORME DATE 3 1 0 5 1 1 YEAR MONTH DAY DELETE PROGRAM FORME TIME 24 h HOUR MINUTE SU-WI EUROPE or or SU-WI GB/IRL/P SU-WI FIN/GR/TR SU-WI CDN SU-WI USA ok SU-WI IRAN SU-WI NEW ZEALAND 19 05 11 ON 35 9:40 1 SU-WI OWN RULE NO SU-WI 7
PROGRAM Program switching time Example: Switch on sports hall lighting from Mon Fri, 7:30 to 12:00 hrs Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Confirm by pressing OK. SWITCH is displayed. Confirm by pressing OK. Select ON (for switch-on times). Confirm by pressing OK. The display shows HOUR. Use the + or keys to enter hour, minute, (07:30) and confirm by pressing OK. MONDAY is displayed. Confirm by pressing OK. COPY is displayed. Confirm by pressing OK. ADD TUESDAY is displayed. Confirm by pressing OK and also confirm the days Wed, Thurs, Fri by pressing OK. Continue with to SAVE is displayed. Confirm by pressing OK. Repeat all steps for the switch-off time however instead of selecting ON with select OFF and enter 12:00 for hour and minute. 8
MENU PROGRAM NEW GB SWITCH PULSE CYCLE END ON HOUR ON 7.30 MINUTE MONDAY TUESDAY WEDNESDAY COPY SAVE ADD TUESDAY... SAVE 84 memory locations are available (TR 609 top2). 9
Check/modify switching time Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Use to select CHECK. Confirm by pressing OK. Confirm SWITCH by pressing OK. The first of the entered switching times is displayed. Confirm by pressing OK. NEXT is displayed. MENU PROGRAM NEW CHECK MODIFY DELETE SWITCH MONDAY NEXT Change individual switching times Press to select MODIFY. Confirm by pressing OK. The display shows SWITCH. Confirm by pressing OK. The display shows the first time switch MONDAY. Confirm by pressing OK. The display shows CHANGE HOUR. Use the+ or keys to enter hour and minute and confirm by pressing OK. TUESDAY... MODIFY CHANGE HOUR CHANGE MINUTE CHANGE BLOCK DELETE... DELETED 10
Delete switching time GB Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Press to select DELETE. Confirm by pressing OK. The display shows SWITCH. Confirm by pressing OK. MONDAY is displayed. Confirm by pressing OK. The display shows DELETE BLOCK. Confirm by pressing OK. The display shows DELETED. MENU PROGRAM NEW DELETE SWITCH MONDAY DELETE BLOCK DELETED DELETE MONDAY DELETED With CLEAR MONDAY etc. individual days can also be cleared. 11
Pulse time programming (only with TR 609 top2) Example: Switch on pause signal on Monday 8:05 hrs for 5 sec Press MENU. PROGRAM is displayed. Confirm by pressing OK. NEW is displayed. Confirm by pressing OK. SWITCH is displayed. Select PULSE by pressing u. Confirm by pressing OK. ON is displayed. Confirm by pressing OK. The display shows HOUR. Use the + or keys to enter hour, minute, second (8:05) and confirm by pressing OK. PULSE LENGTH is displayed. Use the + or keys to enter the duration of the pulse in minutes and seconds (5 sec). Confirm by pressing OK. MONDAY is displayed. Confirm by pressing OK. COPY is displayed. Press to select SAVE. Confirm by pressing OK. 12
MENU PROGRAM NEW SWITCH PULSE CYCLE END GB ON HOUR ON 8.05 MINUTE SECOND PULSE LENGTH IN MINUTES Length 5 sec PULSE LENGTH IN SECONDS MONDAY TUESDAY WEDNESDAY COPY SAVE ADD TUESDAY... SAVE 13
Cycle time programming In addition to switch-on and switch-off times (switching time) and short time pulses (pulse) cycle times (cycle) can also be programmed. The pulse length (+ pulse pause) is limited to 17 hrs, 59 min, 59 sec Cycle times refers to cyclically repetitive time functions such as fan controls, urinal rinses etc. Example: Switch on water rinsing Monday from 8:00 to 20:30 hrs every 15 min for 20 sec (8:00 00 8:00 20 On; 8:15 00 8:15 20 On; 8:30 00 8:30 20 On etc.) Cycle programming Start cycle: Monday 8:00 hrs Pulse length: 20 sec Pause length: 14 min 40 sec Cycle end: Monday 20:30:00 hrs Observe the number of maximum electrical switching cycles when using the cycle function. 14
TIME/DATE In the menu TIME/DATE the TIME, DATE, SUMMER WINTER RULE, WEEKDAY etc. can be entered/changed in the submenus. Press MENU using u select DATE/TIME and follow the indications on the display. GB MENU TIME/DATE TIME SET DATE SU-WI WEEKDAY FORM DATE FORME TIME END HOUR YEAR SU-WI MONDAY 31 12 11 EUROPE 24 h MINUTE 20 10:15 MONDAY SU-WI 1 2 / 3 1 / 1 1 GB/IRL/P 02.05 DAY 11 12 31 02.05... 12 h AM PM 15
MANUAL In the MANUAL menu manual switch functions are applied. In the submenus MANUAL, PERMA- NENT ON/OFF, TIMER*, HOLIDAY, RANDOM the manual switching can be activated/programmed. Press MENU using u select MANUAL and follow the indications on the display. MENU MANUAL PERM ON PERM OFF OVERRIDE TIMER* HOLIDAY RANDOM* END ON PERM On 20 15:30 PERM On 20 PERM OFF END OVERRIDE On 20 15:30 TIMER On or. Off HOURS On 10 12:30 ON or OFF HOLIDAY START YEAR On 2011 RANDOM 1 RANDOM 2 * only with TR 609 top2... 16
Override and permanent switching Override and permanent switching can be set using the menu in MANUAL or in normal mode (automatic screen) by direct keystroke (see figures). GB Activate override Briefly press key. Activate permanent switching Press key for 2 sec. Cancel override/permanent switching Briefly press key again. Override Reversing the channel status to the next automatic or programmed switching. Permanent switching As long as a permanent switching (on or off) is activated, the programmed switching times are ineffective. 17
OPTIONS In the menu OPTIONS the submenus OPERATING HOUR, LANGUAGE, PIN, EXTERNAL INPUT, FACTORY SETTINGS as well as INFO can be requested. Press MENU using u select OPTIONS and follow the indications on the display. MENU OPTIONS OPERATING HOUR EXT INPUT* LANGUAGE PIN FACTORY INFO SETTINGS END SHOW HOUR DELETE NOT ACTIVE BUTTON DEUTSCH NO PIN or. WITH PIN LOAD FACTORY SETTINGS TR 609 TOP2 ENGLISH CURRENT PIN 0 0 0 0 0 0, 0 SERVICE SWITCH NEW PIN 0 2 0 5 1 1 END SAVED END... * only with TR 609 top2 18
Enter PIN code The PIN-Code is set in OPTIONS via the menu. If you have forgotten your PIN call the Theben Hotline. MENU OPTIONS GB OPERATING HOUR EXT INPUT LANGUAGE PIN ok WITH PIN NO PIN FACTORY SETTINGS CURRENT PIN INFO NEW PIN END 19
External Input (only with TR 609 top2) For the channel an EXTERNAL INPUT (see figure) can be set with different functions. Press MENU using u select EXT INPUT and follow the indications on the display. 3 submenus can be selected: Inactive, push button (function), switch (function) INACTIVE: The external input has no function PUSH BUTTON: Override (manual switching), timer (Countdown timer) can be selected. SWITCH: Permanently on, permanently off can be selected. Note: If a function is activated via an external push button or switch, EXTERNAL is displayed. 20
MENU OPTIONS GB OPERATING HOUR EXT INPUT* INACTIVE BUTTON* SWITCH OVERRIDE TIMER PERM ON PERM OFF TIMER ON HOUR MINUTE SECOND * Use push button without glow lamp 21
OBELISK top2 memory card Use memory card (see fig.) Insert memory card in the time switch. Read / read out saved switching times and device settings in the time switch or start Obelisk program. Remove memory card OBELISK top2 (No. 9070404) after copying Avoid mechanical stress or dirtying with other storage/transport methods. Copy OBELISK Time switch This copies the switching program (all standard and special programs) and optionally all time switch (e.g. Position, offset, external input, time format etc..) from the memory card in the time switch. Copy TIME SWITCH OBELISK This copies all switching programs and settings from the time switch to the memory card OBELISK COPY OBELISK -> TIME SWITCH TRANSCRIBE OK COPY TIME RUN SWITCH -> OBELISK OBELISK OVERWRITE OK CHECK OBELISK 22
Technical data Operating voltage: 230 240 V~, +10 %/-15 % Frequency: 50 60 Hz Power consumption: ca. 0,4 W Standby min.: ca. 0,4 W Switch output: switching of choice of external wires is permitted Contact: two way switch Gap: <3 mm (µ) Contact material: AgSnO 2 Max switching capacity: 16 A, 250 V~, cos ϕ = 1; 4 A, 250 V~, cos ϕ = 0,6 Min. switching capacity: 10 ma/230 V AC 100 ma/12 V AC/DC Incandescent lamp load: 1000 W Halogen lamp load: 1000 W Fluorescent lamp load: uncorrected, series corrected 1000 VA parallel correction 120 W (18µF) Compact fluorescent lamps: 40 W LED lamps: <2 W output, max. connection total of 10 W, >2 W < 8 W output, max. connection total of 25 W Permissible ambient temperature: 25 C... +55 C Protection class: II in accordance with EN 60730-1 subject to designated installation Protection rating: IP 20 nach EN 60529 Time accuracy: ±0,5 s/day at 25 C Power reserve: 10 years (lithium cell) at +20 C Pollution degree: 2 Rated impulse withstand voltage: 4 kv Max. switching cycles with 16 A resistive load: 50,000 23 GB
Service address/hotline Service address Theben AG Hohenbergstr. 32 72401 Haigerloch GERMANY Telephone +49 (0) 74 74/6 92-0 Fax +49 (0) 74 74/6 92-150 Hotline Telephone +49 (0) 74 74/6 92-369 Fax +49 (0) 74 74/6 92-207 hotline@theben.de Addresses, telephone numbers etc. www.theben.de The current OBELISK top2 PC software and the online version of the operating manual are available at www.theben.de 24