DeviceNet Module. User Manual. 1 Important User Information. 2 Installation

Similar documents
Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

Install the DeviceNet Module using the following procedure:

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure:

Ethernet/IP Module. User Manual. Contents

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Profinet Module. User Manual. Contents

Copyright: December 2017 Nidec Issue: E

- 15G0078B110 - PROFIBUS MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Copyright: December 2017 Nidec Issue: E

MCD 200 Series. MCD 200 DEVICENET Module OPERATING INSTRUCTIONS. MCD 200 DEVICENET Module. Order Code: 175G9002. Adjustment.

Instructions. Modbus RTU Card (WSIQ-COM-MB)

ETHERNET/IP & PROFINET MODULE

PROFINET MODULE. Communications module. User Guide. This manual is to be given to the end user en / a. Power. Error. Status.

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

Installation Guide EtherNet/IP Module

1. Introduction. 2. Installation MODBUS INTERFACE

Installation Guide Modbus TCP Module

ASTAT XB/XBm Remote Operator

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents

Installation Guide PROFINET Module

OPERATING INSTRUCTIONS MCD

Installation Guide EtherNet/IP Module

G3 Series DeviceNet TM Technical Manual

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

Diagnostics (Physical)

Copyright December 2017 Nidec Issue: D

MPCR Series DeviceNet Technical Manual

DeviceNet Drive Profile CFW-09

Opal Pro to DeviceNet. Opal Pro MS6 SERIES. DeviceNet Interface Users Manual. Revision Page 1

Powered Roller Controller for DeviceNet

1. Introduction. 2. Installation INSTALLATION INSTRUCTIONS: MCD USB MODULE

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output

2002 Series DeviceNet Technical Manual

Section 1 Caution Statements... 3 Section 2 Introduction Section 3 Basic Setup Procedure... 5 Section 4 Installation... 6

INTEGRATED MICROSTEPPING MOTOR DRIVER AND HIGH PERFORMANCE MACHINE/PROCESS CONTROLLER

USERS IMS2 SERIES SOFT STARTERS

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

CDN572-5 DEVICENET SPECIFICATIONS

CONTENTS IMS2 SERIES A. 2.1 Overview Feature List Part Number Format... 3

L5351 DeviceNet Communications Interface

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

SMART RELAY SRW 01 V4.0X

DeviceNet Expansion Board

Diagnostics (Logical) Diagnostics (Physical)

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1

CONTENTS. Basic Setup Procedure Section 1 Caution Statements Programming and Operation IMS2 SERIES H

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008

Softstarters Type PSTX Fieldbus communication, Anybus CompactCom DeviceNet

Section 0.0 Warnings... 2 Section 1.0 Quick Set-up... 3 Section 2.0 Description Section 3.0. Section 4.0. Section 5.0. Section 6.0. Section 7.

Section 0.0 Warnings... 3 Section 1.0 Quick Set-up... 4 Section 2.0 Description Section 3.0. Section 4.0. Section 5.0. Section 6.0. Section 7.

Motors Automation Energy Transmission & Distribution Coatings. Profibus DP SRW 01. User s Manual

Operation manual. HDOM-Profibus-V0. More options please visit;

Series SD6 with DeviceNet (Addendum)

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

METTLER TOLEDO DNB User Manual

01325T -- Robot Welder

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

MicroNode I/O TM DeviceNet AI User Manual

efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor Start-up Guide DeviceNet Adapter Module NDNA-02

- 15G0078B130 - USB MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

DeviceNet System Installation manual rev. 3.0

Installation Instructions for DeviceNet E50 Limit Switches

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Compact Multiprotocol I/O Module for Ethernet 16 Universal Digital Channels, Configurable as PNP Inputs or 2 A Outputs TBEN-L4-16DXP

Advanced User Guide. SE77-DeviceNet. Commander SE. Part Number: Issue Number: 1.

SE-330 SERIES (NEW REVISION) DEVICENET INTERFACE

1. Warnings Introduction Mechanical Installation Electrical Installation Application Examples...

DeviceNet for Capacitance Diaphragm Gauge

DeviceNet - ODVA Conformance Test Results

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET

Allen-Bradley Automation

INSTRUCTION MANUAL WCS-Interface Module, DeviceNet

GSE Scale Systems A div of SPX Corporation

CODESYS 3 Programmable Gateway for the BL67 I/O System Multiprotocol Ethernet gateway for PROFINET, EtherNet/IP and Modbus TCP BL67-PG-EN-V3

BL compact fieldbus station for DeviceNet 16 Configurable Digital PNP Channels BLCDN-8M12LT-8XSG-PD-8XSG-PD

Optidrive Applications Support Library

BL compact fieldbus station for DeviceNet 16 Configurable Digital PNP Channels BLCDN-16M8L-8XSG-P-8XSG-P

DeviceNet Communication Manual

VersaMax IP Input Module

DeviceNet Conformance Test Result

PROFIBUS Gateway for MCD 3000 Series Soft Starters. User Manual

DeviceNet - ODVA Conformance Test Results

BL compact fieldbus station for DeviceNet 4 Analog Inputs for Current or Voltage and 8 Configurable Digital PNP Channels BLCDN-8M12L-4AI-VI-8XSG-PD

SE-330/SE-330AU/SE-330HV DEVICENET INTERFACE

Installation and maintenance instructions

EL731 DEVICENET INTERFACE

MGate 5105-MB-EIP Quick Installation Guide

FC 300 DeviceNet and Allen Bradley Control logix 5550

CDN067 DEVICENET SPECIFICATIONS

G3 Series PROFIBUS DP Technical Manual

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

Serial PROFIBUS Interface

Transcription:

User Manual 1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning. It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice. 2 Installation CAUTION Remove mains and control voltage from the soft starter before attaching or removing accessories. Failure to do so may damage the equipment. 2.1 Installation Procedure 1. Remove control power and mains supply from the soft starter. 2. Fully pull out the top and bottom retaining clips on the module. 3. Line up the module with the comms port slot. 4. Push in the top and bottom retaining clips to secure the module to the starter. 5. Set the DeviceNet Module Node Address (MAC ID) and Data Rate. 6. Apply control power to the soft starter. 7. Insert the network connector into the module and power up the DeviceNet network. 1 2 3 10178.B DET-817 1

Configuration CAUTION Network designs must decrease the maximum allowable cumulative dropline length by 400 mm for every module installed on the network. Failure to do so may result in network communication errors and decreased reliability. Example: ODVA specifies a maximum cumulative dropline length of 156 m on a network operating at 125 kb/s. If six modules were installed on this network, the total cumulative dropline length would need to be decreased to 153.6 m. Remove the module using the following procedure: 1. Take the module off-line. 2. Disconnect all external wiring from the module. 3. Remove control power and mains supply from the soft starter. 4. Fully pull out the top and bottom retaining clips on the module. 5. Pull the module away from the soft starter. 3 Configuration The DeviceNet Module is a Group 2 slave device, using a predefined master/slave connection set. I/O data is produced and consumed using polled I/O messaging. The soft starter must be added to the DeviceNet manager project using the EDS file and configuration/management software tool. This file is available from www.ge.com/ex/industrialsolutions. In order to operate successfully, the correct EDS file must be used. (device.bmp) is also available. 4 Adjustment Changes to the rotary switch settings take effect when the DeviceNet network is next powered up. An on-screen graphics bitmap file The factory default settings for the rotary adjustment switches are: DATA RATE 500 kb PGM 250 kb 125 kb NODE ADDRESS ( 00-63, PGM ) 2 4 0 6 PGM MSD 2 4 0 6 8 LSD The Data Rate and Node Address (MAC ID) must be set locally on the module. These cannot be set using DeviceNet management software. When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on PGM position, the module uses the previously used valid on-line Data Rate and Node Address (MAC ID). 03550.B 2 DET-817

Connection 5 Connection ASTAT XB/XBm: For the DeviceNet Module to accept fieldbus commands, a link must be fitted across terminals A1-02 on the soft starter. ASTAT XL: Input links are required across the stop and reset inputs if the soft starter is being operated in Remote mode. In Local mode, links are not required. ASTAT XL: Parameter Comms in Remote selects whether the soft starter will accept Start and Stop commands from the Serial Network Master while in Remote Mode. See the soft starter user manual for parameter details. ASTAT XB/XBm ASTAT XL 1 1 2 2 03202.B Rd Wh Bu Bk 11604.B 3 V + CAN_H Shield CAN_L V - 3 V+ CAN_H Shield CAN_L V ASTAT XB/XBm ASTAT XL (Auto mode) A1, 02: Stop 56, 57: Stop 58, 57: Reset DeviceNet Module DeviceNet Module Standard connection onto DeviceNet network Standard connection onto DeviceNet network 3 DET-817 3

6 LEDs The Module LED indicates the condition of the power supply and module operation. The Network LED indicates status of the communication link between the DeviceNet Module and the network Master. LED State Description Off Network power off 1 (Module) Green Normal operation Red Unrecoverable fault 2 Red/Green Self Test mode flashing Off Duplicate MAC ID test has not been (Network) completed Green Online but no connection with Master flashing Green Online and allocated to a Master Red flashing One or more timed out I/O connections Red Failed communication between module and Master Red/Green flashing Communication faulted and received an Identity communication faulted request When a communications failure occurs, the soft starter may trip if the Communication Timeout parameter for the network is set greater than zero. When communication is restored, the soft starter must be reset. 7 DeviceNet Polled I/O Structure Once the EDS file has been loaded, the DeviceNet Module must be added to the scanner list with parameters shown in the following table: Parameter Value I/O connection type Polled Poll receive size 14 bytes Poll transmit size 2 bytes Once the soft starter, module and Master have been set up, configured and powered up, the Master will transmit 2 bytes of data to the module and receive 14 bytes of data from the module. LEDs 4 DET-817

DeviceNet Polled I/O Structure Master > Slave polled I/O output data is as follows: Byte Bit Function 0 0 0 = Stop command 1 = Start command 1 0 = Enable Start or Stop command 1 = Quick Stop (ie coast to stop) and disable Start command 2 0 = Enable Start or Stop command 1 = Reset command and disable Start command 3 to 7 Reserved 1 0 to 1 1 0 = Use soft starter remote input to select motor set 1 = Use primary motor set when starting 2 2 = Use secondary motor set when starting 2 3 = Reserved 2 to 7 Reserved 1 Only available on ASTAT XL soft starters. 2 Ensure that the programmable input is not set to Motor Set Select before using this function. Slave > Master polled I/O input data is as follows: Some soft starters do not support some functions. Byte Bit Function Value 0 0 Trip 1 = Tripped 1 Warning 1 = Warning 2 Running 0 = Unknown, not ready, ready to start or tripped 1 = Starting, running, stopping or jogging 3 Reserved 4 Ready 0 = Start or stop command not acceptable 1 = Start or stop command acceptable 5 Control from Net 1 = Always except in Program mode 6 Local/Remote 0 = Local control 1 = Remote control 7 At reference 1 = Running (full voltage at the motor) 1 0 to 7 Status 0 = Unknown (menu open) 2 = Starter not ready (restart delay or thermal delay) 3 = Ready to start (including warning state) 4 = Starting or running DET-817 5

DeviceNet Polled I/O Structure Byte Bit Function Value 5 = Soft stopping 7 = Trip 8 = Jog forward 9 = Jog reverse 2 0 to 7 Trip/Warning code See Trip Codes on page 7 3 0 Initialised 1 = Phase sequence bit is valid (bit 1) after first start 1 Phase sequence 1 = Positive phase sequence detected 2 to 7 Reserved 4 1 0 to 7 Motor current (low Current (A) byte) 5 1 0 to 7 Motor current (high byte) 6 0 to 7 Current %FLC (low byte) 7 0 to 7 Current %FLC (high byte) 8 0 to 7 % Motor 1 temperature Current as a percentage of soft starter FLC setting (%) Motor 1 thermal model 9 0 to 7 % Motor 2 Motor 2 thermal model temperature 10 0 to 7 % Power factor Percentage power factor (100 = power factor of 1) 11 0 to 7 Power (low byte) Power low byte, scaled by power scale 12 0 to 3 Power (high nibble) Power high nibble, scaled by power scale 4 to 5 Power scale 0 = Multiply power by 10 to get W 1 = Multiply power by 100 to get W 2 = Power (kw) 3 = Multiply power by 10 to get kw 6 to 7 Reserved 13 0 to 3 Digital Input state For all inputs, 0 = open, 1 = closed (shorted) 0 = Start 1 = Stop 2 = Reset 3 = Input A 4 to 7 Reserved 1 For models QLxxB0053D and smaller this value will be 10 times greater than the value displayed on the keypad. 6 DET-817

8 Trip Codes Code Trip Type DeviceNet Module ASTAT XB ASTAT XBm Trip Codes 0 No trip 11 Input A trip 20 Motor overload 21 Heatsink overtemperature 23 L1 phase loss 24 L2 phase loss 25 L3 phase loss 26 Current imbalance 28 Instantaneous overcurrent 29 Undercurrent 50 Power loss 54 Phase sequence 55 Frequency 60 Unsupported option (function not available in inside delta) 61 FLC too high 62 Parameter out of range 70 Miscellaneous 75 Motor thermistor 101 Excess start time 102 Motor connection 104 Internal fault x (where x is the fault code detailed in the table below) 113 Starter communication (between module and soft starter) 114 Network communication (between module and network) 115 L1-T1 shorted 116 L2-T2 shorted 117 L3-T3 shorted 118 Motor 2 overload 119 1 Time-overcurrent (Bypass overload) 121 Battery/clock 122 Thermistor circuit 1 For ASTAT XL, time-overcurrent protection is only available on internally bypassed models. ASTAT XL DET-817 7

Parameter Object 8.1.1 Internal Fault x The table below details the internal fault code associated with trip code 104. Internal fault Message displayed on the keypad 70 ~ 72 Current Read Err Lx 73 ATTENTION! Remove Mains Volts 74 ~ 76 Motor Connection Tx 77 ~ 79 Firing Fail Px 80 ~ 82 VZC Fail Px 83 Low Control Volts 84 ~ 98 Internal fault X Contact your local supplier with the fault code (X). Only available on ASTAT XL soft starters. For parameter details, see the soft starter User Manual. 9 Parameter Object The DeviceNet Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and downloaded (read) using DeviceNet management software. When the DeviceNet Module is powered up, it automatically obtains parameter information from the soft starter. Detail Value Comment (Hex) Class 0F Parameter object address Instance 1 ~ xxx xxx = maximum soft starter parameter number Attribute ID 01 Always 0x01 Get Service 0E Read single soft starter parameter value Set Service 10 Write single soft starter parameter value Only available on ASTAT XL soft starters. the soft starter User Manual. For parameter details, see 8 DET-817

Specifications CONFORM AN CE TESTED 10 Specifications Enclosure Dimensions... 40 mm (W) x 166 mm (H) x 90 mm (D) Weight... 250 g Protection... IP20 Mounting Spring-action plastic mounting clips (x 2) Connections Soft starter... 6-way pin assembly Network... 5-way male and unpluggable female connector (supplied) Maximum cable size... 2.5 mm 2 Contacts... Gold flash Settings Node address (MAC ID) Setting... Rotary switches Range... 0 to 63 (63, factory default) Data rate Setting... Rotary switch Options... 125 kb, 250 kb, 500 kb (125 kb, factory default) Power Consumption steady state... 19 ma at 25 VDC... 31 ma at 11 VDC in-rush (at 24 VDC)... 1.8 A maximum for 2 ms Galvanically isolated Certification CE... IEC 60947-4-2 C... IEC 60947-4-2 ODVA... DET-817 9

Specifications È710-16185-00ARËÍ 10 DET-817