Instruction Bulletin. Sepam Series 20 & 40 Relays Quick Start Guide

Similar documents
Electrical network protection Sepam series 20 Sepam series 40 Quick start

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Instruction Bulletin Trim and Rail Extension Kit (6-, 12-, and 18-inch) Installation onto an NF Panelboard Class 1670

PM Series Power Meter

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

ACCESS 9340/9360 Meter Input/Output Module

Technical Specificaions. kwh Energy Meter

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

BCM2 Series Branch Circuit Monitors Quick Setup Guide

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

PowerLogic ION7550 / ION7650 Hardware Lockable Meter

Quick Start Guide TS A

PowerLogic High Density Metering System 1-Meter Enclosure

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

Technical Specifications. Dual Source kwh Energy Meter

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

SAVE THESE INSTRUCTIONS

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

Upgrading Legacy Iso-Gard Line Isolation Monitors and Remote Indicators

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp)

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

QUICK START GUIDE Generator Protection Unit GPU 300

Technical Specifications. Multi Function Meter

7KM2112-0BA00-3AA0 SENTRON PAC3200. English. Operating Instructions DANGER CAUTION DANGER. Order-No.: A5E Last update: 18 January 2008

Technical Specifications. Dual Source Energy Meter (EB / DG)

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

Sepam Series 80 Installation, use, commissioning and maintenance

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

Replacing the Power Supply

Siemens Drives & PLCs

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

PowerLogic ION7300 Series

Installation and Operation Manual

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

JUMO Quantum PID100/PID200/PID300

PowerLogic TM Series EM4800 Multi-Circuit Meters. Configuration Guide

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100hp)

SMVector Additional I/O Module Installation and Operation Manual

Hubbell Surge Protective DeviceS

QUICK START GUIDE Paralleling and Protection Unit PPU 300

Redundancy unit CP-A RU

Modicon Premium PLCs TSX CSY 84 / 85 / 164

EnCell Battery Cell Monitor

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

Installation, Operation and Maintenance Manual

SmartBlock I/O Module HE579MIX102 Isolated 6 Relay, 12 DC Inputs, 4 Analog Inputs

SmartBlock I/O Module HE579MIX577/977 Isolated 4/8 Analog Inputs 2/4 Analog Outputs

Square D Clipsal Pascal Automation Controller

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL.

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

XDBKITS5 Bus / DB Terminal Kit (Size 5) Installation Manual DPD00116

5504 Thermocouple Analog Input Module

Conext CL-60 Inverter Firmware Upgrade Process

PV Rapid Shutdown device

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

Documentation Supplement for Marine Smart-UPS SRT5KRMXLIM, SRT6KRMXLIM External Battery Pack SRT192RMBPM

Twido Programmable Controllers Discrete I/O Modules

SUPERVISORY CONTROL AND DATA ACQUISITION SYSTEM (SCADA)

QUICK START GUIDE Paralleling and Protection Unit PPU 300

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

24/48/120 VAC Interface Card Instruction Manual

Section 4 Ground-Fault Protection Devices

Installation Instructions

Profibus DP Expansion Board

Instruction Bulletin. Fiber Optic Switch Packs. SLSPSP101 and SLSPSP102 for use with Luminaires INTRODUCTION CONTENTS OF THE BOX

Quick Start Guide TS 870 ATS

Performance. Simplicity. Sepam, over 20 years of experience of the world leader. Sepam protection relays. For your peace of mind

TeSys IEC Contactors and Overload Relays

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

Galaxy Shore Connection 500 kva. Operation 04/

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

PROTECTION RELAYS: INNOVATIONS FOR THE BENEFIT OF THE USER

M215 (M215-60) Safety

Analog Monitor Installation Manual

Bulletin 1489 Circuit Breakers. Selection Guide

MAN October 2010 PAGE 1 HE-579ACM300 SmartBlock Power and Energy Monitor HE-579ACM300

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

SEM3 - Embedded Micro Metering Module

User Manual. Per Port Monitoring Models

Ground Fault Protection. Instruction Manual

H704-42(H)(E), H704-42/1(H)(E)

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

User Manual. Solar Inverter for Water Pump

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

Multi-Loader. User manual 06/ BBV48778

M A C 3 Wind Speed Alarm & Controller

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

PowerLogic ION7550 RTU option

RM35TF V AC

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

Transcription:

Instruction Bulletin 63230-216-239B1 LaVergne, TN, USA Sepam Series 20 & 40 Relays Quick Start Guide Retain for future use. Introduction Sepam Series 20 Relays Sepam Series 40 Relays Storage Commissioning DANGER HAZARD OF ELECTRIC SHOCK, BURN OR ARC FLASH Turn off power supplying the relay and equipment in which it is installed before working on it. Always use a proprely rated voltage-sensing device to confim that power is off. Replace all devices, doors, and barriers/covers before energizing this equipment. Failure to follow these instructions will result in death or serious injury. Sepam Series 20 and Series 40 protective relays are designed for protection applications on medium-voltage distribution networks. Sepam Series 20 relays are designed for simple applications and include: 10 Logic Inputs Eight Relay Outputs One Communication Port Eight Temperature Sensor Inputs Sepam Series 40 relays are designed for demanding applications and include: 10 Logic Inputs Eight Relay Outputs One Logic Equation Editor One Communication Port 16 Temperature Sensor Inputs Store the Sepam relay in its original packaging in a closed, sheltered location. Check the storage environment annually for the following recommended conditions: Ambient temperature of -13 to +160 F (or -25 to +70 C) Non-condensing humidity 90% Once installed, energize the Sepam relay as quickly as possible, especially in damp locations (condensing humidity 90%). For more information, please refer to: Sepam Series 20 User s Manual - 63203-216-208C1 Sepam Series 40 User s Manual - 63203-216-219B1 1

Sepam Series 20 & 40 Relays 63230-216-239B1 Identification Each Sepam relay comes in a single package that contains the base unit and its connector. Optional accessories, such as modules, the current or voltage input connector, or cables come in separate packages. To identify a Sepam relay, check the two labels on the right side panel of the base unit that describe the firmware and hardware features of the product. Figure 1: Hardware Equipment Label User Machine Interface Model Power Supply Sepam Code Figure 2: Firmware Equipment Label Application Type Operating Language Sepam Code Components A. Optional Input/Output Modules (MES108 or MES114) B. MES108 or MES114 Module Connectors C. MES114 Module Connector D. MES108 or MES114 Module Connectors 1. Base Unit 2. Input Voltage Connector (Series 40 only): Screw-Type Connector (CCA626), or Ring Lug Connector (CCA627) 3. 1/5 A CT Input Current Connector (CCA630), or LPCT Input Current Connector (CCA670), or Voltage Input Connector (CCT640, Series 20 only) 4. Base Unit Connector: Power Supply Output Relay Input CSH30 / 120 / 200 or ACE990 Screw-Type Connector (CCA620), or Ring Lug Connector (CCA622) 5. Remote Inter-Module Link Connection (black) 6. Communication Module Link Connection (green) A B C D 1 2 3 4 5 6 2 2007 Schneider Electric. All Rights Reserved.

63230-216-239B1 Sepam Series 20 & 40 Relays Connections Wiring of Screw Connectors without Fittings Wiring of Screw Connectors with Fittings Wiring of CCA622 Connectors Installation of the Optional MES108 or MES114 Modules The Sepam relay connections are made to the removable, screw-lockable connectors located on the back of the relay. Please note these parameters for screw connectors without fittings: Maximum one wire cross-section of AWG 24 12 (0.2 2.5 mm²) Maximum two wires with cross-section of AWG 24 18 (0.2 1 mm) Stripped wire length: 0.315 0.394 in (8 10 mm) Please note these parameters for screw connectors with fittings: Telemecanique fittings: DZ5-CE015D for 1 wire AWG 16 (1.5 mm²), DZ5-CE025D for 1 wire AWG 12 (2.5 mm²), or Z5-DE010D for 2 wires 2 x AWG 18 (1 mm²) Wire length: 0.323 in (8.2 mm) Stripped wire length: 0.315 in (8 mm) Please note these parameters for CCA622 connectors: Ring lug or spade lug: 1/4 in (6.35 mm) Maximum wire cross-section of AWG 24 12 (0.2 2.5 mm²) Stripped wire length: 0.236 in (6 mm) Torque 6 9 lb-in (0.7 1 Nm) Using a suitable crimping tool, crimp lugs onto wires Insert no more than 2 ring lugs or spade lugs under washers To install the MES114 input/output module, position the MES114 module as pictured in Figure 3 (below) and complete the following steps: 1. Insert the two pins on the bottom of the MES114 module into the corresponding slots 1 on the Sepam base unit. 2. Press the top of the MES114 module against the Sepam base unit NOTE: Confirm the MES114 module is aligned with the connector 2 on the Sepam base unit. 3. Tighten the mounting screw 3. See MES114 Input/Output Module Installation Sheet (63230-216-246) for more information. Figure 3: Installing MES108 or MES114 Modules 2 3 1 2007 Schneider Electric. All Rights Reserved. 3

Sepam Series 20 & 40 Relays 63230-216-239B1 Operation After tripping on a fault (i.e. phase overcurrent): Trip LED is lit I>51 LED is lit The graphic interface (optional advanced UMI) displays: "Phase Fault" message Tripping current Date and time of fault occurrence Pressing the button displays the 16 most recent unacknowledged alarms Pressing the button clears the alarm message Pressing the button resets the protection relay Access to Measurements/Parameters The measurements and parameters can be accessed using the metering, diagnosis, status and protection buttons. They are arranged in a series of screens as shown in the diagram to the left. Energizing of Sepam Menu Choice Measurements Measurements # Values I rms Series 20 Series 40 The data are split up by category into 4 loops, associated with the following 4 buttons: Measurements Measurements Bar Graphs Switchgear Diagnosis Average I General Settings Overcurrent Protection Settings Io Bar Graphs Temperatures 1 to 4 Temperature Sensors NOTE: When you press a button, the system moves on to the next screen in the loop. When a screen includes more than 4 lines, you can navigate the screen using the cursor buttons (, ). Temperatures 5 to 8 Temperature Sensors Protection and Parameter Settings Modes Expert User Machine Interface There are three usage levels: Operator Used to access all the screens in read mode Does not require any passwords Protection Setting Requires the entry of the first password ( ) Allows protection setting ( ) Parameter Setting Requires the entry of the second password ( ) Allows modification of the general settings as well ( ) NOTE: The parameter setting level is used when changing the 4-digit password. An expert user machine interface (UMI) is available to complement the Standard and Advanced UMI. The expert UMI is displayed on a PC equipped with the SFT2841 software (operating a Windows OS version 95 or NT) and connected to the RS 232 link on the front panel of a Sepam relay. 4 2007 Schneider Electric. All Rights Reserved.

63230-216-239B1 Sepam Series 20 & 40 Relays Use of Passwords Each Sepam relay has two 4-digit passwords: To modify protection settings To modify protection settings and all general settings Entry of Passwords Press the button to display the following screen: Figure 4: Password Entry Screen NOTE: The two factory-set passwords are 0000. 1. Press the button to position the cursor on the first digit. 2. Scroll the digits using the cursor buttons (, ) then confirm to go on to the next digit by pressing the button. 3. After entering your password, press the button to position the cursor on the Apply box. Press the button again to confirm. NOTE: When the Sepam relay is in protection setting mode, one key appears at the top of the display. When the Sepam is in parameter setting mode, two keys appear at the top of the display. Figure 5: Parameter Setting Screen Access to the protection setting or parameter setting modes is disabled: By pressing the button Automatically, if no buttons are pressed for more than 5 minutes Modification of Passwords Only the parameter setting qualification level ( ) or the SFT 2841 allows modification of the passwords. Use the general settings screen ( ) to change passwords. Loss of Passwords If you have lost a password and cannot remember it, please contact Schneider Electric Customer Service (1-888-Square-D). 2007 Schneider Electric. All Rights Reserved. 5

Sepam Series 20 & 40 Relays 63230-216-239B1 Entry of Parameter or Setting (e.g. Phase Overcurrent Protection) Follow these steps: 1. Enter password. 2. Access the corresponding screen by pressing the button. 3. Move cursor by pressing the button to reach the desired box (example: curve). 4. Press the button to confirm the selection, then select the type of curve by pressing the or button and confirm by pressing the button. 5. Press the button to reach the Apply option. 6. Press the button to apply the settings. Entry of Numerical Values (e.g. Current Threshold Value) Follow these steps: 1. Position the cursor on the required box using the, buttons and confirm the choice by pressing the button. 2. Select the first digit and set the value (0 9) using the, buttons. 3. Press the button to confirm the choice and go on to the next digit. NOTE: The values are entered with 3 significant digits and a point. The unit (e.g. A or ka) is chosen using the last digit. 4. Press the button to confirm the entry and the key to access the next field. 5. The values entered will be effective after selecting the Apply option at the bottom of the screen and pressing the button. 6 2007 Schneider Electric. All Rights Reserved.

63230-216-239B1 Sepam Series 20 & 40 Relays 2007 Schneider Electric. All Rights Reserved. 7

Sepam Series 20 & 40 Relays 63230-216-239B1 Instruction Bulletin Schneider Electric USA 295 Techpark Drive, Suite 100 LaVergne, TN 37086 USA 1-888-SquareD (1-888-778-2733) www.us.squared.com Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2007 Schneider Electric. All Rights Reserved.