CDC 51 1 F000 1 7 6 5 8 Characteristics Single-function impulse-off timer One device includes 10 time ranges, from 0.05 s to 00 h, for the adjustment of the pulse time c/o contacts nd c/o contact can be selected as instantaneous contact (front-face sliding switch) olt-free (dry) control contact Starting the time delay is possible: - via an external control contact or - via the supply voltage LEDs for status indication Width.5 mm CT-AWS 1 10 selectable time ranges, from 0.05 s to 00 h Potentiometer with direct reading scale for the fine adjustment of the pulse time Sliding switch to set the nd c/o contact as an instantaneous contact U/T: green LED - Supply voltage (LED flashes during timing) 5 R1: red LED - Output relay 1 energized 6 R: red LED - Output relay energized 7 Circuit diagram 8 Marker label Approvals a culus b GL e GOST f CCC Marks g CE c C-Tick Order data Type Supply voltage Order code CT-AWS, -8 AC/DC, 110-0 AC 1SR 0 1 R000 Order data (Accessories) Description Order code Adapter for screw mounting on panel 1SR 0 09 R0100 Sealable cover 1SR 0 005 R0100 Marker label 1SR 66 017 R0100 Application The CT-S range timers are designed for use in industrial applications. They operate over a universal range of supply voltages and a large time delay range, within compact dimensions. The easy-to-set front-face potentiometers, with direct reading scales, provide accurate time delay adjustment. Operating mode The CT-AWS with 1 c/o contact offers 10 time ranges, from 0.05 s to 00 h for the adjustment of the pulse time. The time delay range is rotary switch selectable on the front of the unit. The fine adjustment of the time delay is made via an internal potentiometer, with a direct reading scale, on the front of the unit. Timing is displayed by a flashing green LED labelled U/T. 1
Function diagram E Impulse-OFF (Trailing edge interval) This function requires continuous supply voltage at terminals A1/B1/B-A. Opening control contact -, energizes the output relays immediately and timing begins. The green LED flashes during timing. When the selected pulse time is complete, the flashing green LED turns steady and the output relays de-energize. Closing control contact -, before the time delay is complete, de-energizes the output relays and the time delay is reset. If the front-face sliding switch is set to the Inst. position, the nd c/o contact energizes immediately upon application of the supply voltage. A1/B1/B-A - 15-18, 5-8 15-16, 5-6 1-1- green LED t CDC 5 05 F005 t = adjusted pulse time t s = storage time t = t 1 + t Connection diagram E CT-AWS A1 B1 15 B1 5 1 5 A1 15 1 B A 16 18 6 8 8 6 B 18 16 A CDC 5 115 F0005 ersion: 1SR 0 1 R000 A1-A Supply: 110-0 AC B1-A Supply: AC/DC B-A Supply: -8 AC/DC - Control contact to start timing 15-16/18 1. c/o contact 5-6/8. c/o contact 1--/. c/o contact as instantaneous contact
Wiring notes Connection diagram for proximity switch ( wire) with 0 AC supply L1 L+ A1 0 / AC / DC CDC 5 79 F005 N A Proximity switch L- Connection diagram for proximity switch ( wire) with DC supply L+ B1 CDC 5 80 F005 A Proximity switch L- Connection diagram for control contacts L1/L+ A1 X1 A X1 start timing X1 pause timing / time storage CDC 5 78 F005 N/L-
Technical Data Input circuits Supply voltage A1-A 110-0 AC B1-A AC/DC B-A -8 AC/DC Power consumption 110-0 AC approx..5-1 A AC/DC approx. 0.5 A/W -8 AC/DC approx. 1.8 A/W Supply voltage tolerance -15...+10 % Supply voltage frequency AC/DC ersion DC or 50/60 Hz AC ersion 50/60 Hz Control contact connections volt-free (dry) - start timing external Minimum control pulse length 0 ms Non-load voltage at the control contacts 10-0 DC (no galvanic separation to supply circuit) Max. current in the control circuit 1 ma Max. cable length to the control inputs 50 m Duty time 100 % Timing circuit Time ranges 0.05 s - 00 h 1) 0.05-1 s ) 0.15- s ) 0.5-10 s ) 1.5-0 s 5) 5-100 s 6) 15-00 s 7) 1.5-0 min 8) 15-00 min 9) 1.5-0 h 10) 15-00 h Recovery time < 50 ms Repeat accuracy (constant parameters) < 0. % Timing error within the supply voltage tolerance range < 0.008 % / % d U Timing error within operating temperature range < 0.07 % / C Indication of operational states Supply voltage / timer 1st / nd output relay energized green LED steady / flashing while timing red LED / red LED Output circuits 15-16/18, 5(1)-6()/8() Number of contacts Relays, c/o contacts, nd c/o contact selectable as instantaneous contact Contact material AgCdO Related voltage acc. to DE 0110, IEC 6097-1 50 Maximum switching voltage 50 AC, 50 DC Rated switching current acc. to IEC 6097-5-1 AC-1 (resistive) 0 A AC-15 (inductive) 0 A DC-1 (resistive) A DC-1 (inductive) A Maximum lifetime mechanical 0 x 10 6 switching cycles electrical (AC-1, 0, A) 0.1 x 10 6 switching cycles Short circuit proof, max. fuse rating n/c 10 A fast, operating class gl n/o 10 A fast, operating class gl General data Enclosure width.5 mm length 78.0 mm depth 100.0 mm Wire size fine-strand with wire end ferrule x 0.75 -.5 mm (18-1 AWG) fine-strand without wire end ferrule rigid x 0.5 - mm (0-1 AWG) Weight approx. 150 g (5. oz) Mounting position any Degree of protection enclosure / terminals IP50 / IP0
Temperature operating -0...+60 C storage -0...+85 C Mounting DIN rail (EN 500) Standards Product standard IEC 6181-1, EN 6181-1 EMC Directive 89/6/EEC Electromagnetic compatibility IEC 61000-6-, EN 61000-6- ESD acc. to IEC 61000--, EN 61000-- level 6 k / 8 k HF radiation resistance acc. to IEC 61000--, EN 61000-- level 10 /m Burst acc. to IEC 61000--, EN 61000-- level k / 5 khz Surge acc. to IEC 1000--5, EN 61000--5 level k L-L HF line emission acc. to IEC 1000--6, EN 61000--6 level 10 Low oltage Directive 7//EEC Operational reliability acc. to IEC 68--6 g Mechanical resistance acc. to IEC 68--6 6 g Approvals / marks Approvals Marks culus, GL, GOST and CCC CE and C-Tick Isolation data Rated insulation voltage between supply circuit, acc. to DE 0110, IEC 6097-1 supply up to 0 : 00 control circuit and output circuit supply up to 0 : 500 Rated impulse withstand voltage between all isolated circuits acc. to DE 0110, IEC 66 k / 1.-50 µs Test voltage between all isolated circuits.5 k, 50 Hz, 1 min. Pollution category acc. to DE 0110, IEC 66, IEC 55-5 III/C Overvoltage category acc. to DE 0110, IEC 66, IEC 55-5 III/C Environmental testing acc. to IEC 68--0 h cycle time, 55 C, 9 % rel., 96 h Load limit curves AC load (resistive) 00 00 100 80 60 50 0 0 0 CDC 5 19 F005 10 0.1 0. 0.5 1 6 10 I A DC load (resistive) 00 00 100 80 60 50 0 0 0 CDC 5 19 F005 10 0.1 0. 0.5 1 6 10 I A Derating factor F for inductive AC load 1.0 0.9 0.8 F 0.7 0.6 0.5 CDC 5 19 F005 0.1 0. 0. 0. 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ 5
Contact lifetime /switching cycles N N 10 5 9 8 5 10 1 5 6 7 8 I A CDC 5 191 F005 0 50 Hz 1 AC 60 cycles/h Dimensional drawings Dimensions in mm 109,5.1,5.886 10.0 78.07 CDC 5 188 F0005 100.9 Dimensional drawings (Accessories),5.177 6,5.6 11,5.5 CDC 5 187 F0005 10.9,5.886 60.6 Adapter for screw mounting on panel.70,5.886 7.75,5.18 68,5 CDC 5 185 F0005 front-to-back size 107 Sealable cover A11 0.787 8.15 CDC 5 186 F0005 Marker label 6
Druckschrift-Nummer. CDC 111 05 D001 Printed in the Federal Republik of Germany (08/05) ABB STOTZ-KONTAKT GmbH Eppelheimer Straße 8 691 Heidelberg, Deutschland Postfach 10 16 80 69006 Heidelberg, Deutschland Internet http://www.abb.com/lowvoltage -> Control Products -> Electronic Relays E-Mail epr-support@stotzkontakt.de