Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Similar documents
Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Arc protection relay. Features Three-phase overcurrent function. Application

Earth-fault Relay SPAJ 110 C. Product Guide

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Residual overvoltage relay

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Arc protection relay. Features Three-phase overcurrent function. Application

Feeder Protection Relay REF 610. Product Guide

Synchro-check relay. Application

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Feeder protection relay SPAA 341 C. Product Guide

Relion 611 series. 611 series Type Test Certificate

Feeder protection relay

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

SPA-ZC 302. Profibus-DPV1/SPA Gateway. Product Guide. spa-zc302_rightco300

High impedance protection relay

Communication Gateway COM 610. Product Guide

Motor Protection Relay REM 610. Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

SPAA 341 C Feeder protection relay

Remote I/O RIO600 Product Guide

GRD130 - FEATURES APPLICATION

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Protection Relays PHASE & RESIDUAL OVERCURRENT

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Bus Bar Protection Relay B-PRO 4000

Relion 610 series. Voltage Protection REU610 Product Guide

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

FL MC 2000E (SM40) LC

extending the boundaries of technology evolution of proven technology FEATURES

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Type VRLTC tap changer

RT4B-110V/12A RECTIFIER

AO523 Analog Input Module

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

AI531 Analog Input Module

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

TM241C40U controller M IO transistor NPN

RT7-48V/6kW Specification

Relion 610 series. Feeder Protection REF610 Product Guide

TU531, TU532 Terminal Unit

RT4F-120V/20A-WAC RECTIFIER

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

TM221ME32TK controller M IO transistor PNP Ethernet

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

INGEPAC DA-CU. Control Unit. Data Sheet ZY8932IMA01E 31/03/2016

TM221CE40T controller M IO transistor PNP Ethernet

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

TM221M16TG controller M IO transistor PNP spring

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

TM241C24T controller M IO transistor PNP

TM241CE40T controller M IO transistor PNP Ethernet

RT4F-48V/50A-WAC RECTIFIER

TM221M16R controller M IO relay

Electronic timer CT-ARS.11

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

For Transmission, Distribution and Machinery protection.

AX522 Analog Input/Output Module

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

RT12-240V/2.4kW Rectifier Specification

Electronic timer CT-ERS.21

TM221CE24R controller M IO relay Ethernet

CD522 Encoder, Counter and PWM Module

AX521 Analog Input/Output Module

TM221M32TK controller M IO transistor PNP

PSC-AC. PSC AC-series W 1 to 3 Outputs. AC-DC Power supply. Input Voltage ranges. Single output ratings. 2-3 outputs ratings

TM241CE24T controller M IO transistor PNP Ethernet

TM241CE24U controller M IO transistor NPN Ethernet

TM241CE24T controller M IO transistor PNP Ethernet

MSR 2400R. Rugged Power System for Military and Heavy Duty Applications

Switching relay CT-IRE with 1 c/o (SPDT) contact

RT4F-110V/25A RECTIFIER

Power Products. Station Automation COM600 Product Guide

ABB 520BID01 Binary Input datasheet

Electronic timer CT-AHD.22

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

TM3AI4 module TM3-4 analog inputs

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

Model Number Structure

Technical specifications

Multifunction Transducer MT440

DC522 Digital Input/Output Module

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

SREDU Double Connection Option Card for Lon Star Coupler RER 111

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Binary output and supervision 520CSD01 Data sheet

Voltage Transducer UMT516 / MT516

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

Contact protection relay

Transformer Protection Relay

TF501, TF521 Terminal Bases

TM241C40R controller M IO relay

TM3TI8T module TM3-8 inputs temperature

DC541 Digital Input/Output Module

Transcription:

Directional or Non-Directional Earth-Fault Product Guide

Issued: 17.06.19994 Status: Updated Version: C/16.10.2002 Data subject to change without notice Features Directional or non-directional low-set earthfault current stage with definite-time or inverse definite minimum time (IDMT) characteristic Directional or non-directional high-set earth-fault current stage with definite-time characteristic Deblocking zero-sequence voltage stage with definite-time characteristic The two earth-fault current stages can be configured to operate alternatively as two voltage stages: three-stage voltage monitoring operation possible Intermittent earth-fault protection Circuit-breaker failure protection (CBFP) Disturbance recorder - recording time up to 19 seconds - triggering by a start or a trip signal from any protection stage and/or by a binary input signal - records two analogue channels and seven digital channels - adjustable sampling rate Non-volatile memory for - up to 60 event codes - setting values - disturbance recorder data - recorded data of the five last events with time stamp - number of starts for each stage - alarm indication messages and LEDs showing the status at the moment of power failure Galvanically isolated binary input with a wide input voltage range All settings can be modified with a personal computer HMI with an alphanumeric LCD and manoeuvring buttons IEC 60870-5-103 and SPA bus communication protocols Two normally open power output contacts Two change-over signal output contacts Output contact functions freely configurable for desired operation Optical PC-connector for two-way data communication (front) RS-485 connector (rear) for system communication Continuous self-supervision of electronics and software. At an internal relay fault (IRF), all protection stages and outputs are blocked. User-selectable rated frequency 50/60 Hz User-selectable password protection for the HMI Display of primary current and voltage values as well as phase angle values Multi-language support Application The directional or non-directional earth-fault relay is a secondary relay which is connected to the voltage and current transformers of the object to be protected. The earth-fault current and the zero-sequence voltage unit continuously measure the zerosequence voltage, earth-fault current and phase angle of the object. On detection of a fault, the relay will start, trip the circuit breaker, provide alarms, record fault data, etc., in accordance with the application and the configured relay functions. The voltage unit includes low-set stage U 0 b> and the earth-fault current unit low-set stage I 0 > and high-set stage I 0 >>. The earth-fault stages can be replaced by two additional voltage stages, low-set stage U 0 > and high-set stage U 0 >>. The protection functions are independent of each other and have their own setting groups and data recordings. The voltage and current functions use conventional transformer measurement. An output contact matrix allows start or trip signals from the protection stages to be routed to the desired output contact. Design The relay includes a high-set and low-set earth-fault current unit, a zero-sequence voltage unit and a circuit-breaker failure protection unit. Further, the relay includes an HMI module, a self-supervision system and a disturbance recorder. 3

Directional or non-directional earth-fault current unit The high-set and the low-set stage the directional earth-fault current unit can be configured to be either directional or non-directional. The directional earth-fault stages can be given either a basic angle or a sin(ϕ) or a cos(ϕ) characteristic. The start and the tripping of the directional earth-fault stages with the basic angle characteristic are based on measuring the earth-fault current, I 0, the zero-sequence voltage, U 0, and the phase angle, ϕ, between the voltage and the current. An earth-fault stage will start when the following three criteria are fulfilled at the same time: The earth-fault current, I 0, exceeds the set start value of the low- or high-set earthfault stage. The zero-sequence voltage, U 0, exceeds the set start value of U 0b >, which is the same for both stages in the deblocking mode. The phase angle, ϕ, between the voltage and current falls within the operation sector ϕ b ± ϕ. The basic angle of the network is -90 for isolated neutral networks and 0 for resonant earthed networks, earthed with an arc suppression coil (Petersen coil) with or without a parallel resistor. The operation sector is selectable and can be either ϕ = ±80 or ±88. Both operation sectors can be extended. When an earth-fault stage starts, a start signal will be generated and a start indication shown on the HMI. If the above mentioned criteria remain fulfilled until the set operate time elapses, the stage will deliver a trip signal and a trip indication will be shown on the HMI. The trip indication will remain active although the protection stage is reset. The direction of the fault spot is determined by means of the angle between the voltage and the current. Basic angle ϕ b can be set between -90 and 0. When basic angle ϕ b is 0-, the negative quadrant of the operation sector can be extended with ϕ a. Extended operation sector ϕ a can be set between 0 and 90. The start and the tripping of the directional earth-fault stages with the sin(ϕ) or the cos(ϕ) characteristic are based on measuring the earth-fault current, I 0, the zero-sequence voltage, U 0, and the phase angle, ϕ, between the voltage and the current. The sinus or cosinus value of the phase angle is calculated and multiplied by the earth-fault current to get the directional earth-fault current, I ϕ. An earthfault stage will start when the following three criteria are fulfilled at the same time: The directional earth-fault current, Iϕ, exceeds the set start value of the low- or high-set earth-fault stage. The zero-sequence voltage, U 0, exceeds the set start value of U 0b >, which is the same for both stages in the deblocking mode. The phase angle, ϕ, between the voltage and the current falls within the operation sector, corrected with ϕ c. When an earth-fault stage starts, a start signal will be generated and a start indication shown on the HMI. If the above mentioned criteria remain fulfilled until the set operate time elapses, the stage will deliver a trip signal and a trip indication will be shown on the HMI. The trip indication will remain active although the protection stage is reset. The direction of the fault spot is determined by means of the angle between the voltage and the current. Directional earth-fault characteristic sin(ϕ) corresponds to the earth-fault protection with the basic angle -90 and cos(ϕ) to the earth-fault protection with the basic angle 0. The operation directions, forward or reverse, of the directional earth-fault stages can be selected independently of each other. The directional stages may also be separately configured to be non-directional. The low-set stage I 0 > can also be used for protection against intermittent earth-faults, which may occur in insulated cables used in compensated networks. When the earth-fault current exceeds the set start value of low-set stage I 0 >, the earth-fault unit will start to deliver a start signal after a ~70 ms start time. When the set operate time at definite-time characteristic or the calculated operate time at inverse definite minimum time (IDTM) characteristic elapses, the earth-fault unit will deliver a trip signal. When the earth-fault current exceeds the set start value of high-set stage I 0 >>, the earthfault unit will start to deliver a start signal after a ~60 ms start time. When the set operate time elapses, the earth-fault unit will deliver a trip signal. 4

It is possible to block the start and the tripping of an earth-fault stage by applying an external binary input signal to the relay. The low-set stage of the earth-fault unit can be given either a definite-time or an inverse IDMT characteristic. At IDMT characteristic, six time/current curve groups are available, of which four comply with the IEC 60255 standard: the normal inverse, very inverse, extremely inverse and long time inverse. The two additional IDMT curve groups, referred to as RI and RD, are special curve groups according to ABB praxis. The inverse-time function of stage I 0 > can be set to be inhibited when stage I 0 >> starts. In this case the operate time will be determined by stage I 0 >>. The high-set stage can be set out of operation. This state will be indicated by dashes on the LCD and by 999 when the set start value is read via serial communication. The set start value of stage I 0 >> can be automatically doubled in a start situation, e.g. when the object to be protected is connected to a distribution network. Thus a set start value below the connection inrush current level may be selected for stage I 0 >>. A start situation is defined as a situation where the earth-fault current rises from a value below 12% x I 0 > to a value above 150% x I 0 > in less than 60 ms. The start situation ends when the current falls below 125% x I 0 >. Zero-sequence voltage unit When the zero-sequence voltage exceeds the set start value of low-set stage U 0b >, the voltage unit will start to deliver a start signal after a ~70 ms start time. When the set operate time at definite-time characteristic elapses, the voltage unit will deliver a trip signal. The two current stages, I 0 > and I 0 >>, can be replaced by two additional voltage stages, low-set stage U 0 > and high-set stage U 0 >>, to create a three-stage zero-sequence voltage module. All three voltage stages measure the same voltage but can have separate settings both regarding sensitivity and operate time. The signalling and trip relays can also be selected separately for all three stages. a ~70 ms start time. When the set operate time at definite-time characteristic elapses, the voltage unit will deliver a trip signal. When the zero-sequence voltage exceeds the set start value of high-set stage U 0 >>, the voltage unit will start to deliver a start signal after a ~60 ms start time. When the set operate time elapses, the voltage unit will deliver a trip signal. It is possible to block the start and the tripping of a voltage stage by applying an external binary input signal to the relay. High-set stage U 0 >> can be set out of operation. This state will be indicated by dashes on the LCD and by 999 when the set start value is read via serial communication. Circuit breaker failure protection (CBFP) unit The CBFP unit will generate a trip signal via power output 2 (PO2) if the fault has not been cleared on expiration of the set operate time 0.10 s...1.00 s. Normally, the CBFP unit controls the upstream circuit breaker. It can also be used for tripping via redundant trip circuits of the same circuit breaker. The CBFP unit is activated with a software switch. Disturbance recorder The includes an internal disturbance recorder which records the momentary measured values, or the RMS curves of the measured signals, and seven digital signals: the external binary input signal and the states of the internal protection stages. The disturbance recorder can be set to be triggered by a start or a trip signal from any protection stage and/or by an external binary input signal, and either on the falling or rising triggering edge. The ratio of the pre- and post-triggering of the recording can be set. The recording length varies according to the selected sampling frequency. The RMS curve is recorded by selecting the sampling frequency to be the same as the nominal frequency of the relay. See the table below for details: When the zero-sequence voltage exceeds the set start value of low-set stage U 0 >, the voltage unit will start to deliver a start signal after Nominal frequency Hz Sampling frequency Hz Recording length s 50 800 1.20 50 400 2.40 50 50 19.20 5

Nominal frequency Hz Sampling frequency Hz Recording length s 60 960 1.00 60 480 2.00 60 60 16.00 HMI module The HMI of the is equipped with six push-buttons and an alphanumeric 2 x 16 characters LCD. The push-buttons are used for navigating in the menu structure and for adjusting set values. An HMI password can be set to protect all user-changeable values from being changed by an unauthorised person. The offers you multi-language support. The following languages are available for the HMI menu: English, German, French, Spanish, Italian, Swedish and Finnish. Self-supervision (IRF) The is provided with an extensive self-supervision system which continuously supervises the software and the electronics of the relay. It manages run-time fault situations and informs the user about an existing fault via a LED on the HMI and a text message on the LCD. Communication capabilities The can be connected to a substation automation or monitoring system using either the SPA bus communication protocol or the IEC 60870-5-103 remote communication protocol. Both protocols are supported in the same device. The SPA bus communication protocol is an asynchronous serial communication protocol (1 start bit, 7 data bits + even parity, and 1 stop bit) with a selectable data transfer rate (default 9.6 kbps). It is a master/slave protocol supporting one master device and several slave devices. The SPA bus protocol can be used to transfer data, e.g. measured currents, registered values, events, and relay settings, between the master and the slave device. The supports the IEC 60870-5-103 remote communication protocol in the unbalanced transmission mode with a data transfer rate of 9.6 kbps. The IEC 60870-5-103 protocol is used to transfer mesurand and status data from the slave to the master. Disturbance recorder data, however, cannot be transferred using this protocol. The is provided with two serial communication ports, one on the rear panel and the other on the front panel. The is interfaced with a fibre-optic bus by means of the bus connection module RER 103 via the D9S-type RS-485 connector on the rear panel of the device. The RER 103 enables the use of either the SPA bus or the IEC 60870-5-103 communication protocol. The use of the IEC 60870-5-103 protocol normally requires the fibre-optic star coupler RER 125. The optical PC-connector on the front panel is used to connect the relay to the CAP 501/ 505 setting and configuration tools. The front interface uses the SPA bus protocol. The optical PC-connector galvanically isolates the PC from the relay. Since this connector is standardized for ABB relay products, only one connecting cable (ABB art. No 1MKC- 950001-1) will be required. The can also be connected to the Lon bus using a LON-SPA Gateway. Auxiliary voltage supply The requires a secured auxiliary voltage supply to operate. The internal power supply of the relay forms the voltages required by the relay electronics. The power supply is a galvanically isolated (flyback-type) DC/DC converter. When the auxiliary voltage is connected, the READY indicator LED on the front panel will be on. The primary side of the power supply is protected with a fuse located on the PCB of the relay. The fuse size is 3.15 A (slow). 6

Technical data Table 1: Energizing inputs Rated frequency 50/60 Hz ±5 Hz Current input Rated current, I n 0.2 A 1 A 5 A Thermal withstand capability - continuously 1.5 A 4 A 20 A - for 1 s 20 A 100 A 500 A Dynamic current withstand - half-wave value 50 A 250 A 1250 A Input impedance < 750 mω < 100 mω < 20 mω Voltage input Rated voltage, U n 100/110/115/120 V Thermal withstand capability - continuously 2 x U n - for 10 s 3 x U n Input impedance > 4.7 MΩ Table 2: Measuring range Measured residual voltage (U 0 ) as a percentage of the rated voltage of the energizing input Measured earth-fault current (I 0 ) as a percentage of the rated current of the energizing input Table 3: Binary input Operating range Rated voltage Current drain Power consumption Table 4: Power outputs (PO1 and PO2) Rated voltage Continuous carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control circuit timeconstant L/R < 40 ms, at 48/110/220 V dc Minimum contact load 0...400% x U n 0...800% x I n 18 265 V dc U r = 24/48/60/110/220 V dc ~ 2 25 ma < 0.8 W 250 V ac/dc 5 A 15 A 30 A 5 A/3 A/1 A 100 ma at 24 V ac/dc Table 5: Signal outputs (SO1, SO2) and self-supervision (IRF) output Rated voltage Continuous carry Make and carry for 3.0 s Make and carry for 0.5 s Breaking capacity when the control circuit timeconstant L/R < 40 ms, at 48/110/220 V dc Minimum contact load 250 V ac/dc 5 A 8 A 10 A 1 A/0.25 A/0.15 A 100 ma at 24 V ac/dc Table 6: Data communication Rear interface, connector 2.2 Front interface RS-485 connection for the fibre-optic interface module RER 103 SPA bus or IEC 60870-5-103 protocol 4.8 or 9.6 kbps Optical RS-232 connection for opto-cable 1MKC 950001-1 SPA bus protocol 4.8 or 9.6 kbps 7

Table 7: Auxiliary voltage U aux rated U aux variation power start-up time, typical Burden of auxiliary supply under quiescent/operating condition Ripple in the dc auxiliary voltage Interruption time in the auxiliary dc voltage without resetting the relay Ur =110/120/220/240 V ac Ur =48/60/110/125/220 V dc 80 265 V ac 38 265 V dc 300 ms ~ 4 W/~ 10 W Max 12% of the dc value < 30 ms at 48 V dc < 100 ms at 110 V dc < 500 ms at 220 V dc Table 8: Enclosure class Front side IP 54 (flush-mounted) Rear side, connection terminals IP20 Note! A rear protective cover (accessory part) can be used to protect and shield the rear of the case. Table 9: Dimensions Width Frame 111.4 mm, box 94 mm Height Frame 265.9 mm (6U), box 249.8 mm Depth 235 mm (245.1 mm with a protective rear cover, available as an option) Enclosure size 1/4 (x 19 ) Weight of the relay ~3.0 kg Table 10: Environmental tests Specified service temperature range -10...+55 C Storage temperature tests -40...+70 C according to the IEC 60068-2-48 Dry heat test According to the IEC 60068-2-2 Dry cold test According to the IEC 60068-2-1 Damp heat test, cyclic According to the IEC 60068-2-30 Table 11: Standard tests Insulation tests Dielectric tests According to the IEC 60255-5 Test voltage 2 kv, 50 Hz, 1 min Impulse voltage test According to the IEC 60255-5 Test voltage 5 kv, unipolar impulses, waveform 1.2/50 µs, source energy 0.5 J Insulation resistance measurements According to the IEC 60255-5 Isolation resistance > 100 MΩ, 500 V dc Mechanical tests Vibration tests (sinusoidal) According to the IEC 60255-21-1, class I Shock and bump test According to the IEC 60255-21-2, class I Seismic test According to the IEC 60255-21-3, class 2 Table 12: Electromagnetic compatibility tests EMC immunity test level requirements consider the demands in the generic standard EN 50082-2 1 MHz burst disturbance test, class III According to the IEC 60255-22-1 Common mode 2.5 kv Differential mode 1.0 kv Electrostatic discharge test, class III According to the IEC 61000-4-2 and IEC 60255-22-2 For contact discharge 6 kv For air discharge 8 kv 8

Table 12: Electromagnetic compatibility tests Radio frequency interference tests Conducted, common mode Radiated, amplitude-modulated Radiated, pulse-modulated According to the IEC 61000-4-6 and IEC 60255-22-6 (2000) 10 V (rms), f = 150 khz 80 MHz According to the IEC 61000-4-3 and IEC 60255-22-3 (2000) 10 V/m (rms), f = 80 1000 MHz According to the ENV 50204 and IEC 60255-22-3 (2000) 10 V/m, f = 900 MHz Radiated, test with a portable transmitter According to the IEC 60255-22-3, method C; f =77.2 MHz, P=6 W; f =172.25 MHz, P=5W Fast transient disturbance tests According to the IEC 60255-22-4 and IEC 61000-4-4 Other terminals 4 kv Binary input 2 kv Surge immunity test According to the IEC 61000-4-5 Power supply 4 kv, line to earth 2 kv, line to line I/O ports 2 kv, line to earth 1 kv, line to line Power frequency (50 Hz) magnetic field 100 A/m IEC 61000-4-8 Voltage dips and short interruptions According to the IEC 61000-4-11 30%/10 ms 60%/100 ms >95%/5000 ms Electromagnetic emission tests According to the EN 55011 and EN 50081-2 Conducted, RF-emission EN 55011, class A, IEC 60255-25 (Mains terminal) Radiated RF-emission EN 55011, class A, IEC 60255-25 CE approval Complies with the EMC directive 89/336/EEC and the LV directive 73/23/EEC 9

Connection diagram A L1 L2 L3 0 - N dn - I da PC S1 P1 I O S2 P2 + + Tx RER 103 Rx U aux ~ + 1.1 1 2 3 4 6 * 100V BI IRF 14 2.1 2.1 2.1 1 2 17 18 13 15 ~ SO2 SO1 PO2 PO1 3 4 2.1 2.1 2.1 2.1 10 11 12 7 8 9 5 6 + + + Spa Bus 1MKC950001-1 *REJ527B 418BAA: REJ527B 411BAA: 2 = 5 A 3 = 1 A 5 2 = 1 A 6 3 = 0.2 A SGB1 SGB1 + - IRF Uob> START Blocking of stage Uob> TRIP Io> START Blocking of stage Io> TRIP SGR1 SGR2 SGR3 SGR4 4 4 3 3 2 2 1 1 Optical PC-interface Io>> START SGR5 2 1 7 SGB1 Blocking of stage Io>> TRIP SGR6 4 3 1 SGB1 INDICATIONS CLEARED I/O =Default value 2 SGB1 OUTP. CONT. UNLATCHED AND INDIC. CLEARED 3 SGB1 4 SGB1 MEMORIZED VALUES AND INDIC. CLEARED; OUTPUT CONTACTS UNLATCHED SWITCHGROUP SELECTION ConD527 Fig. 1 Connection diagram of the directional earth-fault relay Ordering TOrder numbers Order number (I 0 inputs 0.2 A/1 A) Order number (I 0 inputs 1 A/5 A) REJ527B 411BAA (Article nr:1mrs091411-baa) REJ527B 418BAA (Article nr:1mrs091418-baa) Accessories Protective cover for rear connectors 1MRS060132 Flush mounting kit 1MRS050209 Semi-flush mounting kit 1MRS050253 Wall mounting kit 1MRS050240 Side-by-side mounting kit 1MRS050241 19 Rack mounting kit 1MRS050257 Optic bus connection module (RER 103) 1MRS090701 Opto-cable 1MKC950001-1 References Configuration, setting and SA system tools The following tool versions are needed to support the new functions and features of Release B: CAP 505 Product Engineering Tools; CAP 505 v. 2.1.1, or later Additional information Technical Reference Manual Installation Manual Operator s Manual CAP 501 Setting Tools; CAP 501 v. 2.1.1, or later LIB 510 Library for MicroSCADA; LIB 510 v. 4.0.3-1, or later SMS 510 Substation Monitoring System; SMS 510 v. 1.0.0-3, or later 1MRS 750616-MUM 1MRS 750526-MUM 1MRS 751055-MUM 10

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation