NEW ERA METER. Installation & Operation Guide NE METER

Similar documents
ALTAI C1N SUPER WIFI CPE INSTALLATION GUIDE. Version 1.0 Date: September, Altai Technologies Ltd. All rights reserved

+Cam Quick Start Guide

Wa r n i n g-wa r n i n g-wa r n i n g

CBV383Z2 Cable Modem Quick Installation Guide

WiFi-Repeater User Manual. Quick Installation Guide(Q.I.G.) REV.1.2

Quick Start Guide.

SERIES 4600 Ethernet Visual-Pager Display INSTALLATION and SPECIFICATION GUIDE. Manual No. D Revision Date: 08/2016 Control: 1.

LED FOLDING WORKLIGHT TM

WiFi Inspection Camera Instruction Manual

NIMBUS a personal dashboard for your digital life

Quick Installation Guide

Zodiac WX QUICK START GUIDE

N331 Wireless Mini Optical Mouse User s Guide

Bluetooth Enabled Access Control MODEL BG-FE. Operating Instructions

Touch Panel Dimmer MH-P511. Introduction

PACKAGE CONTENTS SPECIFICATIONS

EN Series / EXN. Telephone Entry & Access Control System. Quick Start Guide (EN-2A4) ( EXN )

LAMP Tunable Wireless Lamp

fit-pc3i Owner s Manual

DDW36A Advanced Wireless Gateway - Safety and Installation Product Insert. Federal Communications Commission (FCC) Interference Statement

Lantronix Wi-Fi Module Configuration Guide

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

InnoMedia ipbx-400. Quick Install Guide.

Quick Installation Guide

1101 Universal Transmitter

SOHO Access TM Module. User Guide. SAM-SW5U: 5-port 10/100 Ethernet Switch

midibox 2 user manual

Owner s Instruction Manual

3.5 inch Hard Drive Enclosure. Model #: HDE350U. User s Manual

3.5 inch Hard Drive Enclosure. User s Manual

P OCKET POWER 6000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT

ZigBee Server USER GUIDE

AudioCast Receiver Owners Manual

USB-A to Serial Cable

W IRELESS8000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT

Installing the Enphase Envoy-S Metered

ZIPATILE. Quick Start Guide v.1.1

P OCKET POWER 9000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT

Lyric C1 Wi-Fi Security Camera

EoC MDU Wi-Fi Voice Endpoint User s Guide

Indoor Mini Dome. Hardware Manual D91, D92, E91, E92. Ver. 2013/06/14

SubCast Transmitter/Receiver Subwoofer Kit

FCC Regulatory Information

8 WiFi Digital Photo Frame with Touchscreen LCD Display Instructional Manual

LITE TUNES #V

Hypercable injecteur HPOE - Industrial IEEE 802.3at Gigabit PoE Injector. User Manual. v.1.0 Jun Mail :

3G Cell Modem Upgrade

WiFi IP Camera User s Guide

Wireless Sensors and Ethernet Gateway Manual

MobilePro Users Guide Page 1 of 35. MobilePro HPC. User's Guide. Notices Proprietary Notice and Liability Disclaimer Table of Contents

User Manual. Smart Dimmer Switch. Part 1: General Specification Main Features... 2

Introduction. Package Contents. System Requirements

AudioCast Transmitter Owners Manual

Satellite INSTALLATION GUIDE

Quick Start Guide. Powerline Wireless Extender GPLWE150 PART NO. Q1337.

MINI-MAX WIRELESS. RECEIVER WIRING WHITE...to...TERMINAL #1

4MP WI-FI PAN TILT CAMERA QUICK START GUIDE ENGLISH

HomePlug Ethernet Bridge

fiber optic gateway control box

Industrial RFID Reader

Safety and Maintenance You can use your Tablet PC under a wide range of environmental conditions. However, to ensure long use and continued high

Contents 1. Introduction Hardware Operation Software Operation Technical Data 5. IAdea Limited Warranty 6

INSTALLATION INSTRUCTIONS

InnoMedia ESBC B. Quick Install Guide. 1

SMART SWITCH. User s Manual. This product is to be used with the MySmartBlinds automation kit.

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA

User Manual. Daffodil. 2.4GHz Wireless Mouse Souris Sans Fil 2.4GHz 2.4GHz Wireless Maus Mouse senza fili da 2.4 GHz Ratón Inalámbrica 2.

INSTRUCTION MANUAL. Model 600C Radio Remote Control Handset

Enclosure TS-530 User Manual

HUBBCOM GSC3000/GSC4000 Flush-Mount Smart Controller Quick Installation Guide

Wireless Inspection Camera and LCD Display Instruction Manual

LPWWS Smart Wi-Fi Wall Station

PACKAGE CONTENTS SPECIFICATIONS PRODUCT DIAGRAM

W Remote Control 1

Cube Camera with Fixed Lens Hardware Manual D11, D12. Ver. 2013/05/17

SySTIUM TECHNOLOGIES. Assembly Guide. Model 133i

PWRguard PLUS Spring City Drive Waukesha, WI

Hardware Installation 1. Install two AA batteries in the mouse. Pairing Process in Vista and Windows XP SP2

COBALT C INSTALLATION GUIDE RFID CONTROLLER ESCORT MEMORY SYSTEMS. High Frequency Passive Radio Frequency Identification Controller

User Guide of AU-4612

WMC Remote Control and Receiver RRC-127 User Manual

FCC/CE Certification Information

Home Security Camera icamera-1000

UW Purchase Specification Section

ZIPATILE. Quick Start Guide v.1.3

Cardax Prox Plus Mifare Reader

Charging Pad / Charging Stand

KeyRF. KeyRF PC Remote Control (Version 2.2N) Copyright L3 Systems, Inc. Redmond, WA

USB Port Hub HO

USER MANUAL FOR MF0200 GATEWAY BOX VERSION 2.0

Blackwire C610 Blackwire C620

TABLE OF CONTENTS Folding the Jacket Case into a Stand... 2 FCC Information... 3 Location of Parts and Controls... 4 Charging the Keyboard...

Documentation on all Paxton products can be found on our web site -

MP3 Speaker USER GUIDE

Installation Instructions

*520886* IntelliTouch Pool & Spa Control System MobileTouch Wireless Controller. User s and Installation Guide. P/N Rev A

Toucan Surveillance Kit Camera & Smart Socket. User s Manual Model: TSK100KU

USER GUIDE. Element Wireless Smart Plug Model: E1C-NB6

Smartphone Docking Station with Speaker and Bed Shaker

Installation instructions RF-identification system with integrated AS-i slave DTSLF / / 2010

Transcription:

NEW ERA METER Installation & Operation Guide NE METER Autoranging Power Supply Installation Diagnostics Per Phase Voltage & Current kwh, Demand and TOU 0.2% Accuracy -40 C to +85 C Watertight Enclosure Optional WI-FI, Ethernet or 485 Communication WARNING To reduce the risk of electric shock, always disconnect the appropriate circuit from the power distribution system before servicing or installing any NEW ERA METER metering product. Global Power Products 225 Arnold Road Lawrenceville, Georgia 30044 Phone: (770)736-8232 FAX: (770) 736-8231

INTRODUCTION NEW ERA METER Watt-hour, Demand and Time of Use Meter Installation and Operation Instructions Use these instructions to assemble the NEW ERA METER. Read all instructions before you begin the installation. The NEW ERA METER is designed for a variety of metering configurations. It can be used as a stand-alone NEW ERA METER, part of an automated dial-up system or a stand-alone device. All information required to install a stand-alone NEW ERA METER is given in these Installation Instructions and on the diagram inside the meter enclosure. If this meter is to be used with an automated system using WIFI, Ethernet or 485 interface, refer to the NEW ERA METER Installation Manual for additional installation instructions. CONTENTS The NEW ERA METER is shipped from the factory in a kit containing all the hardware needed to assemble the Energy Meter. Each box contains: Description Quantity Energy Meter electronics installed in a Flush Mount enclosure 1 Current Transformers (quantity depends on service type) 3 (3P 4W Wye) Hardware Kit containing: Grounding screw with grounding washer Wire meter seal Plug-on terminal blocks: 4-position block for voltage (TB1) 6-position block for current transformer inputs (TB2) Optional 5-position block for modem or Pulse Output METER MODELS NE-5000 Energy Only (Wh) NE-5100 Energy & Demand (Wh & kwh) NE-5200 Energy, Demand & Time of Use (Wh, kwh, TOU) NE-5300 Energy, Demand, TOU & kva or kvar (Wh, kwh, TOU, kva or kvar) INSTALLATION This section gives instructions for assembling and installing the NEW ERA METER as a stand-alone unit. The NEW ERA METER should be installed only by a qualified electrician. These instructions are not intended to control the interface between this product and the facility wiring. Compliance with NEC and local codes in the final applications should be verified by the local inspection authorities. If equipment is used in a manner not specified by Global Power Products, the protection provided by equipment may be impaired. 2

NOTE: The NEW ERA METER is equipped with one hole in the bottom of the box to accommodate 3/4 conduit. If connecting from the bottom is inconvenient, remove the electronics and drill holes in only in the lower half of the box. The upper portion of the box is used to accommodate the circuit boards. - Select a mounting location at a minimum of 18 off of the floor. Step 1 Mount enclosure by the three mounting tabs found on the back of the enclosure using mounting hardware appropriate for the mounting surface. If needed, drill a hole in lower half of enclosure approximately 2 inches up from the bottom, only after removing the electronics. Figure 1, NEW ERA METER Enclosure Step 2 Connect conduit to load center (or switchgear) and to enclosure. Dot faces the line side Refer to Figure 2 for steps 3 through 5 Step 3 Install Current Transformers. Current Transformers can be used on the incoming lines or on individual breakers. The dot on the Current Transformer always faces the line or supply side of the service. Typical connections for a 3 Phase 4 Wire load center Figure 2 3

Step 4 Make Voltage, neutral, and grounding taps. a) Make sure service is disconnected before make any connections b) Using in-line fuses, tap each of the phases according to all applicable electric codes. c) Secure one end of a grounding lead to earth ground in the breaker panel or meter board. d) Attach a lead to the neutral terminal in the breaker panel or meter panel. e) Run voltage taps along with a secured neutral and ground tap through the conduit to the meter. Step 5 Referring to the wiring diagram on the inside of the meter cover, terminate CT, voltage, ground, and neutral leads. See Figure 3 for a 3 Phase 4 Wire Wye or 4 Wire Delta service and Figure 4 for a 3 Phase 3 Wire Service. a) Attach ground lead to the lower left grounding point on the circuit board using the enclosed grounding washer and screw. b) Now you are ready to install the terminal blocks. The terminal blocks (TB1 and TB2) found in the hardware kit should be installed on the lower section of the of the board. The four terminal voltage connection block (TB1) goes on the lower left side of the board. The six-terminal current transformer connection block (TB2) goes on the lower right side of the board. c) Using the wiring diagram found on the inside of the meter cover, make the appropriate voltage and current lead connections. Refer to Figure 3 for a wiring diagram for a 3-Phase 4-Wire Wye or Delta service and Figure 4 for a 3-Phase 3-Wire Delta service. d) Align each terminal block with the pins and header on the circuit board and gently push the terminal block into place. Figure 3 Wiring Diagram for 3-Phase 4-Wire Wye or Delta Service 4

Figure 4 Wiring Diagram for a 3-Phase 3-Wire Delta, Single Phase 3 Wire & Network Service CAUTION Do not mix the phases of the voltage and current leads. For example, Phase A voltage tap should match phase A Current Transformer leads. Incorrect metering will result, as well as an error being displayed if the leads are improperly connected. Step 6 Close cover and Seal: a) Install the two captive screws in the right hand side of the enclosure cover. b) Install the wire seal in the cover latch. c) Remove any protective covering on the face of the meter. Location of Stainless Steal Lid Screws Tamper Seal Location Code Numbers Test Mode Annunciator Alternate Mode Annunciator Phase Annunciator Watt Disk Emulator Maximum Demand Annunciator Energy Annuciator Hour Annuciator 5

Installation Diagnostics Upon power-up the NEW ERA METER series meters operates in the Normal display mode. The display continuously scrolls through the Normal display sequence, displaying each selected quantity, annunciator, and any other programmed parameter. The meter will operate in Normal Mode until power is disconnected, the Alternate display sequence is initiated, the Test Mode is accessed or the Toolbox Mode is accessed. Test Mode can be accessed using a small magnet (30 gauss) near the reed switch. The reed switch is located in the one o clock position just above the nameplate. TESTING There are several ways to test a NEW ERA METER. The following table lists different testing methods and the equipment required. Testing Method Location Requirements Infrared Test LED Located on face of meter Optical Pick-up, Standard & Comparator Pulse Initiator Outputs Meter must have KYZ Outputs Standard & Comparator Disk Emulation Annunciator LCD Display No Additional Equipment Most field accuracy tests will utilize the Disk Emulator on the bottom of the LCD Display, therefore this method will be described in detail. The NEW ERA METER is equipped with a bi-directional Liquid Crystal Display (LCD) watt-hour disk emulation annunciator. The disk emulation annunciator consists of four segments located in the lower left portion of the display. The NEW ERA METER uses internal multipliers to compensate for current transformers larger than 200 Amps. If your meter is equipped with Time Of Use, Extended Functions or Demand Threshold Outputs, a data sheet of the parameters displayed will be included for all three modes of operation. MODES OF OPERATION NORMAL MODE An NEW ERA METER operates in two modes a NORMAL mode and a TEST mode. The meter powers-up and runs in the NORMAL mode. This is indicated when the TEST indicator is not on, as in the figure below; When the arrow in the lower left corner increments to the right, it indicates the meter is accumulating properly. And the center letters indicates the meter parameters are being displayed. In this case Total kwh is displayed. 6

TEST MODE The individual NEW ERA METER in a can be put in a diagnostic TEST mode by placing a magnet to the right of the display. The meter will sequentially display the voltage, the current and the instantaneous Power for each phase. If a communication module it attached, such as the RS485, the meter will display the programmed ID number, Com ID, and Baud Rate. In addition, the meter will also display Serial Number, Current Transformer Size, Power Outage Monitoring, and Demand Reset Monitoring. Test Mode Tool Placement location. The NEW ERA METER will go into a test mode when a magnet is placed on the surface of the meter. Error Mode If the individual NEW ERA METER detects an error in the wiring ERROR will be displayed in the lower left corner of the LCD. 7

UNITS OF ELECTRICITY MEASUREMENT Units x1,000 x1,000,000 Current Ampere (A) ka - Potential difference Volt (V or E) kv - Real power Watt (W) kw MW Energy Watt-hour (Wh) kwh MWh Reactive power VAR (volt-ampere reactive) kvar MVAR Apparent power Volt-ampere (VA) kva MVA Normal Mode: These only show if the Y are enabled Model Type NE-5000 NE-5100 NE-5200 NE-5300 kwh kw kwh, kw and Time of Use kwh, kw,time of Use, KVAh,kVA,kVArh,kVAr Opitional: Power Factor Carbon Footprint Pulse Input A Pulse Input B Date Time Test Mode: Voltage Phase A Current Angle Phase A Current Phase A Active Power Phase A Voltage Phase B Current Angle Phase B Current Phase B Active Power Phase B Voltage Phase C Current Angle Phase C Current Phase C Serial Number CT Size Comm ID Baud Rate Power Outage Count Demand Reset Count 8

COMMUNICATIONS (Optional Feature) RS485: RS485 communications will be provided on an option board located inside the meter s enclosure capable of supporting up to 250 metering points. This multi-drop network will have a running distance of up to 5000 feet. Ethernet: Ethernet communications will be provided on an option board located inside the meter s enclosure capable of supporting up to 1000 metering points using a standard RJ45 cable and CAT 5 wiring. Wi-Fi: If each meter is equipped with Wi-Fi, the meter shall have the ability to be polled through internet, email, and PC Applications using Wi-Fi module that connects to local wireless network or LAN. Requirements for this connection included: SSID Service Set Identifier name of the wireless network Password Security Type (WPA, WPA2, WPE) *Each of these requirements must be specified by the customer and are preprogrammed to each meter before leaving the manufacturing facility. 9

WARRANTY All products manufactured by North American Power Products are guaranteed against defects in material and workmanship for a period of one year from the date of shipment. In the unlikely event a meter needs calibrated or a customer wants to verify the calibration, a service technician can verify the calibration in the field or the meter can be returned to the factory for recalibration. In either case a calibration fee may be charged. All guarantees are limited to repair or replacement of the defective product. All products returned to the factory for repair must be accompanied by a Return Authorization number and it will be inspected to determine the cause of the failure. Metering equipment determined to have been subjected to an improper installation, neglect or misuse will be repaired or replaced at a standard rate, pending customer approval. FCC PART 15, CLASS A The NEW ERA METER has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection from harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area may cause harmful interference, in which case you will be required to correct the interference at your own expense. Any modifications or changes to the equipment, not expressly approved by the party responsible for compliance, could void your authority to operate the equipment. FCC PART 15, CLASS B The NEW ERA METER has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a residential environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, you are encouraged to try to correct the interference by one or more of the following measures: Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. Consult the dealer or an experienced radio/tv technician for help. Any modifications or changes to the equipment, not expressly approved by the party responsible for compliance, could void your authority to operate the equipment. INSTALLATION SIGN OFF: (this must be completed for warranty verification) CT SIZE VOLTAGE SERVICE Electrician Signature: Date: 10