SIPROTEC 5 Application Note. Breaker-and-a-half solutions. SIP5-APN-002, Edition 2.

Similar documents
Extension of BI/BO for busbar protection SIPROTEC 7SS85

SIPROTEC 5 Application Note

SIPROTEC 7SC805. Merging Unit for conventional instrument transformer. Products for digital substations.

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

SIPROTEC 5 Application Note

Products for digital substations SIPROTEC 6MU805. Merging Unit for conventional instrument transformer. Integrated PRP, HSR. siemens.

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

SIPROTEC 5 Protection, automation, and monitoring

Change setting groups via CFC.

SIPROTEC 5 Application Note

Voltage Control of Transformers in Parallel Operation

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

SIPROTEC 5 Application. SIP5-APN-027: Change of switching authority via function keys.

Answers for energy. SIPROTEC 5 the new benchmark for protection, automation, and monitoring of transmission grids

Perfect protection smallest space

SIPROTEC 5 Application Note

Perfect protection smallest space

SICAM AK 3. Flexible automation for all applications. Automation, telecontrol and communication for large data volume.

Product Families and Positioning. Protection Portfolio

SPECIAL CONSIDERATION OF FEEDER PROTECTION FOR BREAKER-AND-A-HALF CONFIGURA- TIONS. G. Steynberg

Lecture 6 Substation Automation Systems

SICAM A8000 Series. Operation, telecontrol, and automation in the smallest spaces. siemens.com/sicam-a8000

Lecture 5 Substation Automation Systems. Course map

SIPROTEC 5 Application Note

Busbar protection REB 670

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

/ sicam SICAM CMIC The smart cube for your distribution network Answers for infrastructure and cities.

Accessories / 7XV5662

Time synchronization via IEE 1588

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note

Auxiliary Units for 7SR23 High Impedance Protection Energy Management

Voltage control of transformers in parallel operation.

Substation Automation Products. Line differential protection RED670 Relion 670 series

Accessories / 7XV5461

Content REF615 Technical Presentation

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

Siprotec 7ST61 / 7ST63

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

PROTECTION, AUTOMATION & CONTROL

Session Five: IEC61850 Based Process Bus Protection Solution for Remote Located Power Transformers

Published by and copyright 2015 Siemens AG Energy Management Freyeslebenstr Erlangen, Germany

Siemens Controls. SIPROTEC 5 Communication Protocols. Preface. Table of Contents. Communication Modules 1 IEC DNP3 3 IEC

Catalog Edition 6 siemens.com/protection

SIPROTEC 4 7SS52 Distributed Numerical Busbar and Breaker Failure Protection

Automation Unit TM 1703 ACP. SICAM 1703 flexible for all applications. Answers for energy.

Configuration and Interoperability Guide for IEC for the SEL-751 Feeder Protection Relay. July 10, 2015

This application note describes configuring automatic bus transfer (ABT) logic with two V57 relays.

Automation System Solutions

Electrical Integration with Smart Communication

Exercise 2. Single Bus Scheme EXERCISE OBJECTIVE DISCUSSION OUTLINE. The single bus scheme DISCUSSION

5SL Miniature Circuit Breakers

SEL Time-Domain Link (TiDL ) Technology

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Substation to substation (ss2ss) GOOSE exchange for critical relay operations

SIPROTEC 4 7SA522 Distance Protection Relay for Transmission Lines

SIPROTEC 4 7SD61 Differential Protection Relay for Two Line Ends

Protective Relays & SCADA Systems

Power Systems Communications Implementation of IEC61850 in a Substation Environment

Relion 630 series. Load Shedding Controller PML630 Product Guide

SIPROTEC 4 6MD66 High-Voltage Bay Control Unit

UPGRADE AND APPLICATION OF AUTOMATION SYSTEM IN T.S. 110/35/10 KV PETROVEC

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Remote communication options include IEC Ethernet communications or Modbus (RS485).

SIGMA. Advanced Generator Protection and Control. Short Form Catalogue

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

Bus Bar Protection Relay B-PRO 4000

Digital Substation Overview of Technology, Industry

Miniature Circuit Breakers for Railway Applications

Application Notes on Generator Protection Schemes

1. Project Description

F650 - More than Feeder Protection & Control. GE Consumer & Industrial Multilin

IEC Interoperability Document for:

Relays for Various Protection Applications / 7SV600

User Manual. AQ-F215 Simulator

Compact Telecontrol System TM 1703 mic. SICAM 1703 flexible for all applications. Answers for energy.

Christian Pinzon, ABB Power Grids The power of one solution for distributed busbar protection What s new in Relion REB500 version 8?

DS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication

IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China

SIPROTEC 5 Devices Protection, Automation and Monitoring

Synchronous switching of distribution sub networks

SIPROTEC 5 New features of V7.5

The complete application guide to specifying a Smart-Gear power distribution solution (PDS) E50001-F710-A123-V1-4A00. Answers for energy.

Hierarchical protection control system of smart substations

AUTOMATED TESTING OF BUSBAR DIFFERENTIAL PROTECTION USING A SYSTEM-BASED APPROACH. Christopher Pritchard, Florian Fink

Designing a new IEC substation architecture

Feeder Protection REF615 Ver Technical Presentation. ABB Oy Distribution Automation. Prashant Ganoo Regional Product Marketing Manager

Experience with a Digital Substation Pilot in North Ame rica

SIPROTEC Compact Overcurrent Protection 7SJ81 for Low-Power CT and VT Applications

Easily configurable HMI system for power automation siemens.com/sicam

7SR23 DAD High Impedance Protection Relay Energy Management

THE MODELING APPROACH OF IEC

Go beyond... IEC Leverage the full potential with leading-edge expertise. Answers for infrastructure and cities.

RelaySimTest. Software for system-based protection testing

////// SUBSTATIONS. DC Switchgear Range. Type MBS (IEEE/ANSI standards)

Transcription:

-and-a-half solutions SIP5-APN-002, Edition 2 www.siemens.com/protection

SIPROTEC 5 Application Note -and-a half solutions SIP5-APN-002, Edition 2 -and-a-half solution Content 1 -and-a-half solutions 3 1.1 Introduction 3 1.2 Properties of a breaker-and-a-half application 3 1.3 Terminology 3 1.4 Requirements for the system solution 3 1.5 Solution concept with SIPROTEC 5 for two feeders 4 1.6 Description of the individual system components 5 1.7 Description of the selected device hardware 6 1.8 SIPROTEC 5 Function Groups for -and-a-half 9 1.9 Protection and (optional) control functions 9 1.10 Summary 10 SIP5-APN-002 2 Edition 2

1 -and-a-half solutions 1.1 Introduction -and-a-half solutions This application describes the requirements for the protection and control of breaker-and-a-half systems and introduces an efficient and innovative solution concept with SIPROTEC 5. 1.2 Properties of a breaker-and-a-half application Each line is delimited by two circuit breakers and the associated current transformers. These currents have to be supersized and processed. Each diameter contains two feeders (two lines or line and transformer). The central circuit breaker is used jointly by both feeders. Only 3 circuit breakers are consequently available for 2 feeders. Hence the designation breaker-and-a-half application. Different voltages have to be selected for synchronizing the switching command depending on the switch position. 1.3 Terminology The following terminology is used in the context of breaker-and-a-half: -and-a-half: Term used for the plant configuration shown in the single line diagram, figure 1. Diameter: Term used to describe the three circuit breakers and associated equipment in the diagram below. A number of such diameters in parallel are applied to the two busbars. Stub Protection: In this application this is a special protection that covers the zone between the breakers and the line isolator when the line isolator is open. Tie-CB: The central circuit breaker, between the two feeders, in the breaker-and-a-half configuration is referred to as the Tie-CB. Leader/Follower: The Leader/Follower logic is associated with the auto re-close function in the breaker-and-a-half configuration. It determines the sequence of re-closing of the two circuit breakers that trip to clear a fault on the OHL. Application Template : Predefined device configuration in DIGSI 5 (e.g DIS overhead line, grounded systems). The application templates contain the basic configurations, required functions groups and function as well as default settings. Function Group: Functional groups (FG) correspond to the primary components (protection object: line; transformer, circuit breaker, disconnector), thereby simplifying the direct reference to the actual system. For example, if the switchgear includes 2 circuit breakers, this is also represented by 2 circuit breaker functional groups a schematic map of the actual system. 1.4 Requirements for the system solution Feeder protection (main protection and backup protection) Circuit-breaker failure protection Edition 2 3 SIP5-APN-002

-and-a-half solutions AR for each circuit breaker of a feeder Controlling the diameter Synchronization of each circuit breaker Sufficient number of inputs and outputs for controlling and detecting the switching elements and signal 1.5 Solution concept with SIPROTEC 5 for two feeders Main protection and backup protection devices for each line 1 central control unit for the entire diameter/bay All devices of a diameter are connected by a so called a diameter bus. Distribution of the functions between the devices using the flexibility of SIPROTEC 5: Control unit: control, synchrocheck Protection devices: protection, tripping, AR, circuit-breaker failure protection Flexible expansion of IOs using the modular quantity structure or connected IO units (diameter bus) Figure 1: Overall concept for protection and control of breaker-and-a-half systems SIP5-APN-002 4 Edition 2

-and-a-half solutions 1.6 Description of the individual system components Diameter bus The diameter bus is implemented in order to ensure the proper data exchange among the devices belonging to the diameter. This provides the following system benefits: fast data exchange between the devices isolated signal exchange (optical fiber) enhanced security compared to wire connections through monitoring of the signal links easy implementation of group indications and additional automation functions (e.g. common start of fault records, coordination of protection functions that run parallel) It is possible to implement communication and function redundancy easy integration of redundant devices and/or additional devices reduced wiring and engineering effort more flexibility for future modifications less space required There is several options for such a diameter bus: 1. Using Protection Data Interfaces (PDI) - Modules USART-xx-yFO 2. Using a dedicated IEC61850 GOOSE Network by adding an ETH-xx-2FO Module, preferably using HSR configuration. Controlling equipment The switching equipment, circuit breakers and disconnector, is operated from a central bay controller. clearly arranged operation owing to representation on the device display The diameter bus provides the central bay controller with all the information that is relevant to assume the control task. (e.g. interlocking) It is possible to activate backup protection functions in the central bay controller if no line backup protection is used. Synchrocheck The synchrocheck is realized centrally in the bay controller for the entire diameter. All voltages are acquired directly and independently by the bay controller and applied to the synchrocheck function depending on the diameter current configuration. enhanced security and reduced wiring effort because no external coupling relays are needed to select the voltage monitoring of all voltage transformers (fuse failure monitor) Line protection The protection scheme can be implemented with a single device. Redundancy can be achieved by using the protection device of one feeder as the backup protection of the other. Line differential protection and distance protection in one device (7SL8). Alternatively, can be also distributed on two devices (7SD8 and 7SA8) integrated stub protection (87Stub) when line disconnectors are open increased sensitivity of the line differential protection through separate transformer acquisition Edition 2 5 SIP5-APN-002

-and-a-half solutions additional stability of the direction determination for the distance protection saturation detection for each transformer 1.7 Description of the selected device hardware The following devices are selected for this solution: 7SL8 Line Differential and Distance Protection (Line 1 Main 1) 7SL8 Line Differential and Distance Protection (Line 2 Main 1) 6MD8 Bay Controller (Control of switching devices of the diameter) 2 x 7SL87 for Line 1 and 2: Product code P1C107747 * 7Sx8 CT VT BI BO PS 201 3 2 IO 202 4 4 8 6 IO 208 4 4 4 11 IO 207 - - 16 8 IO 207 - - 16 8 CB 202 Optional not included Total 47 35 used 32 27 spare: 15 8 Line 1 7Sx8 CT VT BI BO PS 201 3 2 IO 202 4 4 8 6 IO 208 4 4 4 11 IO 207 - - 16 8 IO 207 - - 16 8 CB 202 Optional not included Total 47 35 used: 32 27 spare: 15 8 Line 2 * Diameter Bus with PDI Housing width: 5/6 x 19" Housing type: Flush mounting Binary inputs: 47** Binary outputs: 36 Relays (22 Standard, 14 Fast, 0 High-Speed, 0 Power)** Current transformers: 8 for protection, 0 for measurement and sensitive ground-current detection** Voltage transformers: 8** Modules in 19" row 1: IO202, PS201, IO208, IO207, IO207 SIP5-APN-002 6 Edition 2

-and-a-half solutions Number of LEDs: 32 Display type: Small display Power Supply: DC 60 V-250 V, AC 100 V-230 V Communication: Communications encryption: Normal Integrated Ethernet port: for DIGSI 5 Plug-in module position E: USART-AE-2FO: 2 x optic 1.5 km, 820 nm, ST connector, for serial protocols, e.g. IEC60870-5-103, DNP3.0 etc. and protection interface Plug-in module position F: ETH-BB-2FO: 2 x optic Ethernet, Ethernet 100 Mbit/s, 1300 nm, LC-Duplex connector, 2 km over 50/125 m or 62,5/125 m multimode - fiber Functions: Function points class: Base + 425 function points ** The amount of binary/analog inputs and outputs can be adjusted by adding, reducing, changing the IO Modules. 1 x 6MD86 for Control of switching equipment of the diameter: Product code P1G93301* 6MD8 I U BI BO PS 201 3 2 I/O 202 4 4 8 6 Edition 2 7 SIP5-APN-002

-and-a-half solutions I/O 202 4 4 8 6 I/O 231 - - 24 24 I/O 231 - - 24 24 I/O 231 - - 24 24 PS 203-1 I/O 231 - - 24 24 I/O 230 - - 48 0 CB 202 Optional not included 147 93 used: 47 36 Spare (add. Indications: e.g. MCB trip) 100 57 * Diameter Bus with PDI Housing width: 9/6 x 19" Housing type: Flush mounting Binary inputs: 147** Binary outputs: 93 Relays (75 Standard, 18 Fast, 0 High-Speed, 0 Power)** Current transformers: 0 for protection, 12 for measurement and sensitive ground-current detection** Voltage transformers: 8** * Diameter Bus with PDI ** The amount of binary/analog inputs and outputs can be adjusted by adding, reducing, changing the IO Modules. Modules in 19" row 1: IO202, PS201, IO202, IO201, IO231, IO231 Modules in 19" row 2: PS203, IO231, IO230 Number of LEDs: 64 Key switch: With Display type: Large display Power Supply: DC 60 V-250 V, AC 100 V-230 V Communication: Communications encryption: Normal Integrated Ethernet port: for DIGSI 5 Plug-in module position E: ETH-BA-2EL: 2 x electric Ethernet, RJ45, applicable for DIGSI, IEC61850, DNP, etc. Plug-in module position F: USART-AD-1FO: 1 x optic 1.5 km, 820 nm, ST connector, for serial protocols, e.g. IEC60870-5-103, DNP3.0 etc. and protection interface Functions: Function points class: Base SIP5-APN-002 8 Edition 2

-and-a-half solutions 1.8 SIPROTEC 5 Function Groups for -and-a-half In the SIPROTEC 5 platform was introduced the Function Group concept. A Function group, FG, is the representation of a primary object like a line, circuit breaker, transformer, disconnector, or generic V-I groups, among others. The protection functions are assigned to the corresponding Function Groups where the protection functionality is to operate, providing a clear interface and separation of tasks between the various functions in a complex application. The following example shows the allocation of the required Function Groups and Protection Functions for this application: Distribution of Protection Functions in the corresponding Function Groups: FG Line 7SL87 Line 1 Main 1 A_Q0 Protection Devices B_Q0 FG Line 7SL87 Line 2 Main 1 C_Q0 B_Q0 A_Q0 Control Device 6MD86 B_Q0 C_Q0 Distance Protection x x Line Differential x x Over Current x x Over Voltage x x Auto Reclose x x x x Sync Check x x x Failure x x x x Figure 2: Functional allocation 1.9 Protection and (optional) control functions Several protection functions shall be normally enabled in a diameter in order to cover all possible fault scenarios. The table below shows an example for overhead lines OHL, indicating the type of IED that can be used with information about the applicable Function group and Protection functions, as well as the corresponding if available: Function Distance Protection Differential protection Function Group Line Line Description Protection IED Detailed App Instr. Main and / or back up protection in OHL Main and / or back up protection in OHL 7SA86, 7SA87, 7SL86 SIP5-APN0016 Earth Fault Protection Voltage / frequency Protection Line Back up protection in OHL 7SA86, 7SA87, Line Additional protection in OHL 7SA86, 7SA87, Stub Line Protection to cover the zone 7SA86, 7SA87, SIP5-APN017 Edition 2 9 SIP5-APN-002

-and-a-half solutions protection between circuit breakers and line isolator Busbar protection Busbar Protection to the busbar and zone between CB and Busbar 7SS85 failure protection Circuit Local back-up protection for breaker fail scenarios after a protection trip 7SA86, 7SA87, 7VK86 7VK87 and 6MD8x Auto reclose Incl. leader follower function Circuit Together with the OHL protection provides for reclose of CB after OHL fault clearance 7SA86, 7SA87, 7SL87, 7VK86 7VK87 and 6MD8x SIP5-APN-018 Sync Check Circuit Provides sync check prior to 7SA86, 7SA87, closing of CB (after AR or control command) 7VK86 7VK87 and 6MD8x SIP5-APN-004 Figure 3: Function and function group overview of a diameter 1.10 Summary The solution concept introduced above uses the multiple features of the SIPROTEC 5 series. It is based on a distributed system solution approach whose components are merged to a total solution using highly efficient and reliable communication options. The individual functions can be adjusted flexibly to customer requirements and to the individual device within the overall solution. SIP5-APN-002 10 Edition 2

Published by and copyright 2015: Siemens AG Energy Management Products Humboldtstr. 59 90459 Nuremberg, Germany www.siemens.com/siprotec For more information, please contact your Siemens Partner or our Customer Support Center. Phone: +49 180 524 84 37 Fax: +49 180 524 24 71 (Charges depending on the provider) Email: support.energy@siemens.com Application Note: SIP5-APN-002, Edition 2 Printed on elementary chlorine-free bleached paper. All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. For all products using security features of OpenSSL the following shall apply: This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit (www.openssl.org). This product includes cryptographic software written by Eric Young (eay@cryptsoft.com).