Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL

Similar documents
SCADA Controlled LOR/ER - DNP3.0 Communications Protocol - TECHNICAL MANUAL ES-SLOR-1

DNP 3.0 & Modbus SCADA INTERFACE INSTRUCTIONS FOR 205T BASED SYSTEMS

A36D/TPSD DNP 3.0 & Modbus SCADA INTERFACE

DNP Points List and Implementation for the 6802 Vista Control

DNP Points List and Implementation

DNP3 Communication User's manual

S&C M Series Switch Operator. Sophisticated Microprocessor Control of Overhead Distribution Switches

Autodaptive Capacitor Control M 2501B

BITRONICS 878 DIOD Product Description BITRONICS 878 DIOD DISTRIBUTED INPUT/OUTPUT DEVICE

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

Page 1 MRK-D-0011, V2.0 Aeroqual SM50 User Guide

EVO AT SERIES BATTERY CHARGER AT SERIES BATTERY CHARGER COMMUNICATIONS MANUAL. EVO - Microprocessor Controlled Float Battery Charger JA

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

SOFTWARE DOCUMENTATION. DNP3 Configuration / Interoperability Guide for the DATRAN XL4 DNP3 RTU

GE MDS, LLC. NETio Series. Protocol Communications Supplement. March 2013 Part No A01, Rev. C

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

SOFTWARE DOCUMENTATION. DNP3 Configuration / Interoperability Guide for the DATRAN II excel DNP3 RTU

Chapter 6: DNP Introduction. 6.2 Features of the DNP The OSI/ISO model. 6.3 Basic topology

DNP Points List and Implementation for Universal Controls

REL 512 Connectivity With A Harris Westronics RTU Using DNP 3.0

SEM3 - Embedded Micro Metering Module

Mounting and Connections

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

PG&E Points List for Universal Controls

VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System User Guide V1.0. Innovations BTRM200. Battery Test Remote Monitor User Guide

Latching, Sequence and Impulse Relays Application Data

SM100. On-Line Switchgear Condition Monitoring

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

PXM 4/6/8K DNP3 PXM 4/6/8K DNP3 Ethernet Communications User Manual

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

Release 2.11 Standard AXE Primary Firmware is not intended for use on any 8521 Controller not licensed as a RTU.

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide

BRC SERIES 20kW High Voltage Power Supply

DNP3 Device Profile Based on DNP XML Schema version Showing both the Device's Capabilities and its Current Configuration

DNP Points List and Implementation

PLA User. WARNING: read connection information(p5) before connecting PL controllers to the PLA

Instruction Manual for BE-SP3 Circuit. 10/21/07

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

BTRM200 Battery Test Remote Monitor. User Guide

Remote Terminal Unit ER1000 APPLICATION FEATURES

DEEP SEA ELECTRONICS PLC

NTX Series Product Comparison

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

Advantage CT/LTC Protocol Manual

SCADAPack DNP Driver. User and Reference Manual

CS7 Industrial Control Relays

An ISO 9001 Company. KLP POWER SUPPLY

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL. Total System Manager

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

IntelliCAP PLUS Supplement for Landis & Gyr Telegyr 8979 Protocol

FPU-16 A-B PROTOCOL/DATA LOGGER MANUAL

CS8 Industrial Control Relays

PGR-2601 MANUAL DC GROUND-FAULT RELAY

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Specifications N Termination Voltage Range Current Consumption, Max. Type Number Termination. Voltage Range. Sinking Sensor Current

CP30/G30/MC31 Firmware Version 3100 Known Issues

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

CAN bus switch panels mounted either on the dash or the steering wheel allow for vastly simplified wiring and reduced weight.

Technical Note DNP3 & Control Relay Output Block Command

PAC2 Dual Door Access Controller

NovaTech Orion I/O Overview

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

MESP TECHNICAL SPECIFICATION FOR A RECTIFIER UNIT CONTROL & PROTECTION SYSTEM FOR USE IN THE 1500V DC TRACTION SYSTEM

Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

PRELIMINARY. Preliminary Technical Datasheet #TDAX Discrete I/O P/N: AX inputs, 8 relay outputs, SAE J1939 with Electronic Assistant

VPGate Manual PROFIBUS to serial

MODEL: R2K-1 SEN TRONIC AG. R2K Series

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

Mounting the Model 2601

BE1-BPR BREAKER PROTECTION RELAY ADVANTAGES

DNP3 Field Device Profile. for

PM296/RPM096 POWER QUALITY ANALYZERS. Application Note: DNP Setup Using PAS V Report by Exception. BB0127 Rev. A1

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit

satech TSB-14 MAIN FEATURES

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

SCADAPack 350E 357E. Smart Remote Terminal Unit

NX21 USER MANUAL. Telemetry Unit. Version 1.5

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX

MINER-S Station Controller

Innovative Electronics for a changing world MANUAL POE 4+4 GM

Model SFS01-V2 IMPORTANT! MULTI-ATTEMPT AUTOMATIC ENGINE SMART SWITCH

PS-4100 POWER SUPPLY MANUAL

Single Phase Systems-North American PC125/PC420 Series

Scout-S Station Controller

2 NOVATECH. This page is intentionally left blank.

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

DNP3 Device Profile. Device Profile Template. Data Dictionary. Release 2.0. January 30, 2001

PAC1 Door Access Controller

CURRENT PROTECTION RELAY SMPR-1

SCADAPack 530E 535E. remote Programmable Automation Controller

Transcription:

Control Indicator Module (CIM) - DNP3 Communications Protocol - TECHNICAL MANUAL Page 1 of 35

Introduction...4 Basic Operation...5 Front Panel Controls and Indicators...5 Real Time Clock Battery Back Up...7 CIM Address Programming...8 SCADA Communication System...9 DNP3 Protocol...9 CIM DNP3 Points...16 Serial Transmission Details...18 Communications Hardware Requirements...18 Single Trip Coil Mode...19 Configuring the CIM for Single Trip Mode...20 Control Functions in Single Trip Coil Mode...21 Connections in Single Trip Coil Mode...23 Dual Trip Coil Mode...24 Configuring the CIM for Dual Trip Coil Mode...25 Control Functions in Dual Trip Coil Mode...26 Connections in Dual Trip Coil Mode...28 Circuit Switcher or Ganged Single Pole Breakers Mode...29 Configuring the CIM for Circuit Switcher or Ganged Single Pole Breakers Mode...30 Control Functions in Circuit Switcher or Ganged Single Pole Breakers Mode...31 Connections in Circuit Switcher of Ganged Single Pole Breakers Mode...34 Specifications and Tests...35 Operating Voltage...35 TRIP Contact Ratings...35 CLOSE/Reclose Contact Ratings...35 SCADA Interface...35 RS 485...35 External ReClose Output...35 140 V maximum - 1 A maximum...35 Ambient Temperature Rating...35 Surge Withstand Capability...35 EMI/RFI (Radio Frequency Immunity)...35 Dielectric Withstand Voltage...35 Page 2 of 35

Tested Life Under Rated Load...35 Environmental Testing...35 Page 3 of 35

Introduction The Control Indicator Module (CIM) unit is a Breaker Control Switch with expanded functionality. It provides remote/local circuit breaker control (trip/close), remote/local Recloser Relay control, and Breaker Trip Coil monitoring. The CIM contains a serial (DNP3) SCADA interface for remote control and monitoring functions. All controls, indicators and solid state electronic circuitry are contained within a single modular enclosure that can be horizontally or vertically panel mounted within the limits of a standard 19-inch rack system. The CIM does not depend upon software or remote communications or require paging through menus on a screen. The product is operated with simple front panel controls and configured with one four position internal switch. The CIM provides the following benefits: - Security supervisory remote control from operations control center via SCADA. - Confidence providing a local manual operated switch for emergency conditions. - Training minimum training required, present equipment in service with similar functions. - Immediate Control no delay in locating the correct display or proper control sequence. The CIM unit is applicable in any breaker control scheme for either Transmission and/or Distribution substations or switchyards. It provides for manual local or remote automatic control of switchable equipment. The CIM unit is easy to use, requires minimum training, and provides immediate control of equipment in the event of emergencies. The CIM unit replaces three switches and six indicator lights located on a breaker control panel. The CIM contains a breaker control switch, two LED s which indicate the status of the breaker, two LED s which indicate the status of SCADA and Reclose enable, and switches enabling/disabling SCADA and Reclose. Power, control and SCADA connections are at the rear of the CIM. The CIM can be configured in one of three modes: A. Single trip coil mode, in which a breaker with one trip coil is controlled and monitored. B. Dual trip coil in which two separate, isolated trip coils are monitored and controlled. C. Circuit switcher or ganged single pole breakers mode, in which three trip coils are monitored. Page 4 of 35

Basic Operation Front Panel Controls and Indicators Figure 1 CIM Front Panel The Front panel controls and indicators are shown in Figure 1. The front panel controls work identically however the CIM is configured (single trip coil mode, dual trip coil mode, or circuit switcher mode). A. Breaker Control Switch (52CS Switch) The manual switch is directly connected to the output of the CIM. Turning it to the TRIP or CLOSE positions applies voltage to the TRIP outputs of the CIM or to the CLOSE output. This occurs even if the rest of the CIM module was to lose power or malfunction. The switch action is also registered by the CIM microprocessor and used in indicating the source of a TRIP signal. B. Trip Coil Monitor LED When the breaker is in the CLOSE position (as indicated by XA/XB contact inputs to the CIM) the trip coil monitor glows red if the TRIP coils(s) are intact. One, two or three TRIP coils are monitored, depending on the mode the CIM has been configured to. C. Breaker Open LED When the circuit breaker is in the open or TRIP position (as indicated by XA/XB contact inputs to the CIM) the Breaker Open LED will glow green. The source of the TRIP signal that opened the breaker is also indicated: Continuous Green Light Trip Caused by external protective relay. Slow Flashing Green Light Manual Trip from 52CS switch. Fast Flashing Green Light Trip from SCADA. D. ReClose Enable/Disable Switch When this switch is in the Disable position the CIM blocks an external ReClose relay. If this switch is in the Enable position, then ReClose can be remotely Enabled or Disabled. If the switch is in the disable position, then ReClose cannot be remotely enabled. This function will only be operable when the unit is in the CLOSE state. Page 5 of 35

E. ReClose OUT LED The Amber ReClose OUT LED is lit when Reclose is Disabled via the local manual switch. F. SCADA Enable/Disable Switch This toggle switch enables/disables SCADA commands. G. SCADA OUT LED The amber SCADA Enable/Disable LED is lit when SCADA is disabled. Figure 2 Rear Panel of CIM 2 4 6 8 10 12 14 1 3 5 7 9 11 13 Figure 3 Removable Terminal Block Numbering Page 6 of 35

Real Time Clock Battery Back Up The real time clock on the communications board has a battery back up circuit that keeps the clock running even when the main power to the CIM has been removed. This battery is electrically removed from the circuit when the CIM is powered and is electrically connected when the power is removed. This configuration will allow the clock to run for up to 25 years after the power is removed from the CIM. While the clock is always running events are not stored while the main power is removed from the CIM. If it is desired to replace the battery then access to it can be obtained by removing the top cover of the CIM. Located on the right front of the communications board, when looking at the front of the unit, is the battery holder. There is a tab on top that holds the battery in place. Carefully remove the battery by lifting up on the right hand side and sliding the battery out towards the right. To install the new battery simply reverse the process making sure that the positive side of the battery is on top. The replacement battery should be a 3 volt lithium with a part number CR2032 or its replacement. Battery Page 7 of 35

CIM Address Programming Each CIM can have its personal address set or changed in the following manner. Connect a PC with a terminal emulator, such as Hyper Terminal, to the CIM through a RS232 to RS485 converter. Open the CIM and switch the 7th position of the communications daughter board switch to the on position. Apply power to the CIM and note that the red LED on the main board is on. This indicates that the CIM is in the programming mode. You must enter, from the PC keyboard, a five digit number with leading zeros followed by the ENTER key to program the address. To set the address to 539 then type 00539 ENTER What is entered will be echoed back and when the CIM leaves the programming mode after storing the new address in non-volatile memory the red LED will go out and the green LED will begin flashing, indicating that the CIM is running. Don t forget to put the switch back in the off position before putting the cover back on the CIM. Page 8 of 35

SCADA Communication System DNP3 Protocol This section describes the DNP3 communications protocol employed by the CIM, and how to exchange information with the CIM utilizing the DNP3 protocol. The CIM communicates by emulating a subset of the DNP3 communications protocol in the operational software of the CIM programmable controller. The SCADA communication system operates the same for all three modes of operation for the CIM device, i.e., for Single Dual or Circuit Switcher type Breaker trip coil systems. This implementation of the DNP3 protocol will respond to single fragment messages and then only to the first object in the message. This implementation will only generate single fragment responses. A fragment is a maximum of 50 bytes. Each fragment will be returned as one data link layer frame which is a maximum of 65 bytes. Also unsolicited responses and application level retries are not supported. The CIM is referred to as an IED (Intelligent Electronic Device) and will respond to a DNP3 message if there are no detected errors in the message, the address of the CIM matches the address of the destination field in the message, and message requires a reply. See below for a description of valid messages, their actions, and replies. Message Structure The DNP3 message structure is comprised of three sections of the OSI model: the Data Link, Transport, and Application layers. A complete technical discussion of the protocol is available from the DNP users group or from Electroswitch if required. Device Addresses The Device Address Field of the Data Link layer will support addresses from 0 to 65535 with 65535 being the BROADCAST address. All devices will act on the broadcast address so care must be taken in using it. Each CIM can have its personal address set or changed and this address is stored in non-volatile memory. Page 9 of 35

Supported Data Link Layer Functions FUNCTION DESCRIPTION ACTION 0 SEND Confirm expected. Reset of link. Sends confirm and sets FCB bit. 1 SEND Confirm expected. Reset of user process. Not implemented. 2 SEND Confirm expected. Test Function. Not implemented. 3 SEND Confirm expected. User Data Passes data to application layer. 4 SEND No confirm expected Unconfirmed Data Passes data to application layer. Supported Application Layer Functions FUNCTION DNP OBJECT USED 0 CONFIRM. Not implemented. 1 READ. DNP3 Object 60 - Class 0,1,2,3. 2 WRITE. DNP3 Object 50 Set Time/Date. DNP3 Object 80 Clear IIN Restart Bit 3 SELECT. DNP3 Object 12 Trip/Close, Enable/Disable Reclose. 4 OPERATE. DNP3 Object 12 Trip/Close, Enable/Disable Reclose. 129 RESPONSE DNP3 Object 12 Trip/Close, Enable/Disable Reclose. DNP3 Object 1 16 Status points DNP3 Object 2 Event Log Page 10 of 35

CIM Functions CIM FUNCTION DNP MESSAGE Breaker TRIP CONTROL RELAY OUTPUT BLOCK Object 12, Variation 1 Qualifiers: 1 octet index and 8 bit quantity octet quantity index. (17H) CONTROL POINT: 0 Count field: Doesn t matter. ON Time: Doesn t matter. OFF Time: Doesn t matter. Status: Doesn t matter. Control Field = 81 HEX selects Trip pulse on. Note: The hardware fixes the pulse length to what is required to switch the breaker but limits it to 1 second. APPLICATION FUNCTIONS SUPPORTED: SELECT BEFORE OPERATE OPERATE AFTER SELECT RETURNS: Application Response Function with Control Relay Block status. Object 12, Variation: Same as sent Qualifier: Same as sent CONTROL POINT: 0 Status Field indicates: 0. Request accepted. 1. Request not accepted because arm timer timed out. 2. Request not accepted because no previous matching select. 3. Request not accepted because of formatting errors. 4. Control operation not supported for this point. 5. Request not accepted because of hardware problems. (Caused by SCADA being disabled.) Page 11 of 35

CIM FUNCTION DNP MESSAGE Breaker CLOSE CONTROL RELAY OUTPUT BLOCK Object 12, Variation 1 Qualifiers: 1 octet index and 8 bit quantity octet quantity. (17H) CONTROL POINT: 0 Count field: Doesn t matter ON Time: Doesn t matter OFF Time: Doesn t matter Status: Doesn t matter Control Field = 41 HEX selects Close pulse on. Note: The hardware fixes the pulse length to what is required to switch the breaker but limits it to 1 second. APPLICATION FUNCTIONS SUPPORTED: SELECT BEFORE OPERATE OPERATE AFTER SELECT RETURNS: Application Response Function with Control Relay Block Status. Object 12, Variation: Same as sent Qualifier: Same as sent CONTROL POINT: 0 Status Field indicates: 0. Request accepted. 1. Request not accepted because arm timer timed out. 2. Request not accepted because no previous matching select. 3. Request not accepted because of formatting errors. 4. Control operation not supported for this point. 5. Request not accepted because of hardware problems. (Caused by SCADA being disabled.) Page 12 of 35

CIM FUNCTION DNP MESSAGE Reclose Enabled CONTROL RELAY OUTPUT BLOCK Object 12, Variation 1 Qualifiers: 1 octet index and 8 bit quantity octet quantity. (17H) CONTROL POINT: 1 Count field: Doesn t matter ON Time: Doesn t matter OFF Time: Doesn t matter Status: Doesn t matter Control Field = 03 HEX selects reclose latched on and NUL op. APPLICATION FUNCTIONS SUPPORTED: SELECT BEFORE OPERATE OPERATE AFTER SELECT RETURNS: Application Response Function with Control Relay Block status Object 12, Variation: Same as sent Qualifier: Same as sent CONTROL POINT: 1 Status Field indicates: 0. Request accepted. 1. Request not accepted because arm timer timed out. 2. Request not accepted because no previous matching select. 3. Request not accepted because of formatting errors. 4. Control operation not supported for this point. 5. Request not accepted because of hardware problems. (Caused by SCADA being disabled.) Page 13 of 35

CIM FUNCTION DNP MESSAGE Reclose Disabled CONTROL RELAY OUTPUT BLOCK Object 12, Variation 1 Qualifiers: 1 octet index and 8 bit quantity octet quantity. (17H) CONTROL POINT: 1 Count field: Doesn t matter ON Time: Doesn t matter OFF Time: Doesn t matter Status: Doesn t matter Control Field = 04 HEX selects reclose latched off and NUL op. APPLICATION FUNCTIONS SUPPORTED: SELECT BEFORE OPERATE OPERATE AFTER SELECT RETURNS: Application Response Function with Control Relay Block status Object 12, Variation: Same as sent Qualifier: Same as sent CONTROL POINT: 1 Status Field indicates: 0. Request accepted. 1. Request not accepted because arm timer timed out. 2. Request not accepted because no previous matching select. 3. Request not accepted because of formatting errors. 4. Control operation not supported for this point. 5. Request not accepted because of hardware problems. (Caused by SCADA being disabled.) Page 14 of 35

CIM FUNCTION DNP MESSAGE Get CIM Status CLASS 0 Object 60, Variation 1 Qualifiers: All data. (06H ) APPLICATION FUNCTIONS SUPPORTED: READ RETURNS: Application Response Function with CIM STATUS Object 1, Variation 1 Qualifier: No index packed (00H) POINTS: 16. See Point description. Get CIM Event Log, Changed Status CLASS 1,2,3 Object 60, Variation 2, 3, or 4 Qualifiers: All data. (06H ) When data is available then iin class 1 data bit is set. APPLICATION FUNCTIONS SUPPORTED: READ RETURNS: Application Response Function with CIM LOG Object 2, Variation 2 Qualifier: No index packed 8 bit quantity (07H) POINTS: Changed points (5 MAX) if points changed Since last read. If no points changed then an application response is returned with no object. (SEE CLASS 1 POINT meaning below for Event Log Description.) Clear Restart Bit CLASS 80 IIN, Variation 1 Qualifier: No index (0H) APPLICATION FUNCTIONS SUPPORTED: WRITE. RETURNS: Null Response. Set Date and Time CLASS 50 TIME/ DATE, Variation 1 Qualifier: No index, 8 bit quantity (07H) 1 point starting at 0. APPLICATION FUNCTIONS SUPPORTED: WRITE. RETURNS: Null Response. Page 15 of 35

Error Responses: The following error messages are supported in the IIN bytes and are returned as an error response message if a message with the correct destination address is received with no CRC errors and one of the following applies. ERROR RESPONSE IIN2 Bit 0 BAD FUNCTION IIN2 Bit 1 - OBJECT UNKNOWN IIN2 Bit 2 OUT OF RANGE IIN2 Bit 3 BUFFER OVERFLOW IIN2 Bit 4 ALREADY EXEC IIN2 Bit 5 BAD CONFIG IIN1 Bit 1 CLASS 1 DATA DESCRIPTION Application Function not supported. Object not implemented for this function. Control point out of range for this object. Always zero Always zero Always Zero Set when event change data available. The master sends a request and the IED (Intelligent Electronic Device) slave responds with either a normal reply, error reply, or an no reply. CIM DNP3 Points CLASS 0 POLL POINTS POINT MEANING 0 Reclose On (43X output active) 1 Reclose Enabled (Front panel switch enabled and 43X active) 2 Trip Coil OK (Valid only when breaker is CLOSED ) 3 Breaker Tripped 4 Breaker Closed 5 Protective Tripped 6 Manually Tripped 7 SCADA Tripped 8 Manual Reclose Event Stored * 9 Protective Trip Stored * 10 Not Used 11 Close Event Stored * 12 Trip Event Stored * 13 Not Used 14 SCADA Tripped * 15 SCADA Enabled Note: For Class 0 polls if a point is set then meaning is true. * = internal use. Page 16 of 35

CONTROL RELAY BLOCK POINTS POINT MEANING 0 Breaker Trip/Close Control 1 SCADA Reclose Enable/Disable Control CLASS 1 POLL POINTS POINT MEANING 128 Manual Trip Event Point 129 SCADA Trip Event Point 130 Protective Trip Event Point 131 Manual Close Event Point 132 SCADA Close Event Point 133 Manual Reclose Disabled Event Point 134 Manual Reclose Enabled Event Point 135 SCADA Reclose Disabled Event Point 136 SCADA Reclose Enabled Event Point 137 SCADA Disabled Event Point 138 SCADA Enabled Event Point This data is returned in an Object 2 in response to a Class 1,2 or 3 poll and shows the point that changed and when. i.e. if a point 137 is returned with a time stamp of 04/30/00 15:03:45 it means that somebody switched the front panel SCADA disable/enable switch to disable at that time and date. Once a changed event is read it is erased. This data is stored in non-volatile memory so power glitches will not affect it. A maximum of the five most recent changed events will be returned. This feature will allow the master to poll less frequently and still get real time status change data. Page 17 of 35

Serial Transmission Details The transmission baud rate is user-selectable, and can be set at installation and altered during real-time operation if required. The CIM baud rates are 1200, 2400, 4800, and 9600. The factory default baud rate is 9600. Contact factory for other baud rates. These parameters are set with dip switches on the communications daughter board. Also programming of the CIM DNP3 address is accomplished by switching switch 7 on and applying power. 8 7 6 5 4 3 2 1 ON Shown for 9600 Baud (In the table X means Doesn t matter) Sw # 8 7 6 5 4 3 2 1 9600 X OFF X X X OFF OFF OFF 4800 X OFF X X X OFF OFF ON 2400 X OFF X X X OFF ON OFF 1200 X OFF X X X ON OFF OFF Program X ON X X X X X X There is an 8 th switch position that is not used. Communications Hardware Requirements 5 4 3 2 1 9 8 7 6 RS-485 B RS-485 A Figure 4 - Pin Out of RS-485 SCADA Port Page 18 of 35

Single Trip Coil Mode In single trip coil mode a breaker with one trip coil and one close coil is monitored and controlled by the +125 VDC 11 13 52CS/C SCADA CLOSE TB1 1 79 7 XRC SCADA CLOSE NC 52CS/C 43X XRC S2 2 3 4 79 43X 52/CC 52CS/T TCM/1 SCADA TRIP 8 14 10 9 52/T 52A 52B 52A - 125 VDC CIM. Figure 5 below shows the function schematically. Figure 5 Schematic of CIM Used in Single Trip coil Mode Page 19 of 35

Configuring the CIM for Single Trip Mode Setting a DIP switch on the bottom of the main circuit board configures the CIM. This is shown in Figure 6 below. Bottom View of CIM with Cover Removed DIP Switch Rear On Off 1 2 3 4 Front ON OFF Single Trip Coil Figure 6 Configuration of CIM for Single Trip Coil Mode Page 20 of 35

Control Functions in Single Trip Coil Mode TRIP A TRIP is initiated by the CIM when signaled by either the manual switch (52CS/T) or SCADA (if SCADA is enabled). The third source of a TRIP is an external Protective Relay. A Protective Relay TRIP is a direct control signal from the Protective Relay to the Breaker and is not influenced by the control logic of the CIM. The TRIP contacts of the 52CS/T switch are directly connected to the terminal block connections, which go to the breaker TRIP coil, providing redundant fail-safe operation in the event of electronics malfunction. TC1 = 52CS/T + SCADA TRIP Once a TRIP is initiated, the CIM will continue to apply voltage to the TRIP until the 52/A contact from the breaker confirm that the breaker has moved into the proper position or 1 second has elapsed, whichever occurs first. When the 52/A contacts indicate the breaker has changed state the breaker open status point will be set and the green Breaker Open LED will flash to indicate the source of the TRIP signal as follows; Continuous Green Light Trip Caused by external protective relay. Slow Flashing Green Light Manual Trip from 52CS switch. Fast Flashing Green Light Trip from SCADA. TRIP Coil Monitor The CIM unit continuously monitors the Breaker Trip coil while the breaker is in the closed position. While in this position, if the coil has continuity the red TRIP Coil Monitor LED will light and the SCADA trip coil ok status point will be set. A small current is passed through the coil to test for continuity (approximately 1 milliampere). In the event of a coil failure, the TRIP Coil monitor LED will go out and the SCADA trip coil status point will be cleared. CLOSE The CLOSE function is controlled by any one of three input signals, a local manual switch (52CS), a signal from a local Reclose Relay device (79), or from a signal from SCADA (if SCADA is enabled). Page 21 of 35

The local manual switch (52CS/C) is connected directly to the CLOSE contacts of the breaker, thus allowing direct control of the breaker in the event of any loss of control power or electronics within the CIM unit. CLOSE = (SCADA CLOSE + 52CS/C) * SCADA TRIP When the CIM executes a CLOSE command it maintains voltage on the CLOSE output until the breaker 52/B contacts confirm that the breaker has moved into the proper position or for 1 second whichever occurs first. At that point the TRIP Coil Monitor will turn on the red TRIP Coil monitor LED and the SCADA breaker closed points will be set appropriately. ReClose The ReClose function is controlled directly by an external Reclose Relay. The CIM interacts with the Reclose Relay in two ways. First, a set of polarized, normally open contacts from the CIM (removable terminal block, pin 7 positive and pin 8 negative) activates the external reclose relay. The CIM unit controls the power provided to the Reclose Relay with a solid state relay device. As shown in Figure 4, The positive power terminal for the external reclose relay is connected to the positive power rail (+37.2 to 140 Volts DC). The negative power terminal of the external Reclose relay is connected to pin 7 of the CIM removable terminal block. Pin 8 of the CIM removable terminal block is connected to the negative power rail. Second, the CIM provides a Reclose blocking function (43X). A normally open (NO) contact from the external reclose relay is then connected between the CLOSE terminal of the CIM unit (TB1, pin 2), which is connected to the close coil, and the CIM 43X output (TB1, pin 3). This connects the contacts of the external reclose relay in series with the enable/disable switch and an interlocking relay named 43X. The 43X device provide an interlocking function to prevent a pumping action on the Close cycle of the circuit breaker. 43X = (SCADA ENABLE RECLOSE + 52CS/C) * (SCADA DISABLE RECLOSE + 52CS/T) XRC = S1 * 43X Page 22 of 35

If the Reclose function is being performed by a digital protective relay or other IED, then the same logical functions are performed, but it is necessary to take into account the particular scheme employed by the external relay. The following two tables shows connections to two common protective relays. DPU 2000 CIM Connection Relay Connection External Connection TB1-1 + Power Supply for Close TB1-3 + IN +OUT TB1-2 -OUT 52/CC SEL 251, SEL 351 CIM Connection Relay Connection External Connection Removable Block, pin 7 -INX TB1-1 +INX + Power Supply for Close TB1-3 +OUTX TB1-2 -OUTX 52/CC Connections in Single Trip Coil Mode Terminal Block TB-1 (see Figure 2) 1 + 37.2 to 140 Volts DC Power for CIM and Close Function. Required for proper operation. 2 Close Coil. Required for proper operation. External Reclose is Connected between terminals 2 and 3 of TB-1. 3 43X. External Reclose Enable Output. External Reclose is Connected between terminals 2 and 3 of TB-1. 4 - DC Power for CIM and Close Function. Required for proper operation. Removable Terminal Block (see Figure 3) 1 Not used in Single Trip Coil Mode. 2 Not used in Single Trip Coil Mode. 3 Not used in Single Trip Coil Mode. 4 Not used in Single Trip Coil Mode. 5 Not used in Single Trip Coil Mode. 6 Not used in Single Trip Coil Mode. 7 Output to External Reclose Relay. Normally connected to the negative power terminal of the external relay. 8 Output to External Reclose. Normally connected to the negative power rail. 9 XB contact closure input. Monitors breaker position and is required for proper operation. 10 XA contact closure input. Monitors breaker position and is required for proper operation. 11 + DC Power for XA and XB circuits. Required for proper operation. 12 Not Used in Single Trip Coil Mode. 13 + DC Power for TRIP Circuit. Required for proper operation. 14 TRIP Output. Required for proper operation. Page 23 of 35

Dual Trip Coil Mode In Dual Trip Coil mode, shown in Figure 7, the CIM controls and monitors a circuit breaker with two trip coils. +125 VDC 13 11 52CS/C SCADA CLOSE TB1 1 79 7 + XRC SCADA CLOSE NC 52CS/C 43X XRC S2 2 3 4 79 52CS/T SCADA TRIP TCM/1 TCM/2 43X 52/CC - 52CS/T 8 14 12 10 9 52-1/T 52-2/T 52A 52B - 125 VDC 52A 52A Figure 7 Schematic of CIM Used in Dual Trip Coil Mode Page 24 of 35

Configuring the CIM for Dual Trip Coil Mode Setting a DIP switch on the bottom of the main circuit board configures the CIM. This is shown in Figure 7. The third DIP switch controls the sense of the XRC SCADA output, so there are two DIP switch settings for dual trip mode, shown in Figure 8. Bottom View of CIM with Cover Removed DIP Switch Rear On Off 1 2 3 4 Front ON OFF Dual Trip Coil Figure 8 Configuring the CIM in Dual Trip Coil Mode Page 25 of 35

Control Functions in Dual Trip Coil Mode TRIP A TRIP is initiated by the CIM when signaled to do so by either the manual switch (52CS/T) or SCADA (if SCADA is enabled). The third source of a TRIP is an external protective relay. A protective relay TRIP is a direct control signal from the protective relay to the breaker and is not influenced by the control logic of the CIM. The TRIP contacts of the 52CS/T switch are directly connected to the terminal block connections, which go to the breaker TRIP coil, providing redundant fail-safe operation in the event of electronics malfunction. There are two isolated trip coil outputs. TC1 on the Removable Terminal Block, pin 12 and TC2 on pin 14. TC1 = 52CS/T + SCADA TRIP TC2 = 52CS/T + SCADA TRIP Once a TRIP is initiated, the CIM will continue to apply voltage to the TRIP outputs (CIM removable terminal block, pin 12 and pin 14) until the 52/A contact from the breaker confirms that the breaker has moved into the proper position or 1 second, whichever occurs first. When the 52/A contacts indicate the breaker has changed state the green Breaker Open LED will flash to indicate the source of the TRIP signal as follows; Continuous Green Light Trip Caused by external protective relay. Slow Flashing Green Light Manual Trip from 52CS switch. Fast Flashing Green Light Trip from SCADA. CLOSE The CLOSE function is controlled by any one of three input signals, a local manual switch (52CS/C), a signal from a local Reclose Relay device (79), or from a signal from SCADA (if SCADA is enabled). The local manual switch (52CS/C) is connected directly to the CLOSE contacts of the breaker, thus allowing direct control of the breaker in the event of any loss of control power or electronics within the CIM unit. CLOSE = (SCADA CLOSE + 52CS/C) *SCADA TRIP When the CIM executes a CLOSE command it maintains voltage on the CLOSE output until the breaker 52/B contacts confirm that the breaker has moved into the proper position or 15 seconds, whichever occurs first. At that Page 26 of 35

point the TRIP Coil Monitor will turn on the red TRIP Coil monitor LED and the SCADA breaker open and breaker closed status points are set appropriately. TRIP Coil Monitor The CIM unit continuously monitors the Breaker Trip coil while the breaker is in the closed position. While in this position, if the coil has continuity the red TRIP Coil Monitor LED will light and the SCADA trip coil OK status point will be set. A small current is passed through the coil to test for continuity (approximately 1 milliampere). In the event of a coil failure, the TRIP Coil monitor LED will go out and the SCADA trip coil status point will be cleared. If the status point is read when the breaker is tripped then the status point will indicate a bad coil so reading this point should be done when the breaker is closed. ReClose The ReClose function is controlled directly by an external Reclose Relay. The CIM interacts with the Reclose Relay in two ways. First, a set of polarized, normally open contacts from the CIM (removable terminal block, pin 7 positive and pin 8 negative) activates the external reclose relay. The CIM unit controls the power provided to the Reclose Relay with a solid state relay device. As shown in Figure 6, The positive power terminal for the external reclose relay is connected to the positive power rail (+37.2 to 140 Volts DC). The negative power terminal of the external Reclose relay is connected to pin 7 of the CIM removable terminal block. Pin 8 of the CIM removable terminal block is connected to the negative power rail. Second, the CIM provides a Reclose blocking function (43X). A normally open (NO) contact from the external reclose relay is then connected between the CLOSE terminal of the CIM unit (TB1, pin 2), which is connected to the close coil, and the CIM 43X output (TB1, pin 3). This connects the contacts of the external reclose relay in series with the enable/disable switch and an interlocking relay named 43X. The 43X device provide an interlocking function to prevent a pumping action on the Close cycle of the circuit breaker. 43X = (SCADA ENABLE RECLOSE + 52CS/C) * (SCADA DISABLE RECLOSE + 52CS/T) XRC = S2 * 43X If the Reclose function is being performed by a digital protective relay or other IED, then the same logical functions are performed, but it is necessary to take into account the particular scheme emp0lyed by the external relay. The following two tables shows connections to two common protective relays. DPU 2000 CIM Connection Relay Connection External Connection TB1-1 + Power Supply for Close TB1-3 + IN +OUT TB1-2 -OUT 52/CC SEL 251, SEL 351 CIM Connection Relay Connection External Connection Removable Block, pin 7 -INX TB1-1 +INX + Power Supply for Close TB1-3 +OUTX TB1-2 -OUTX 52/CC Page 27 of 35

Connections in Dual Trip Coil Mode Terminal Block TB-1 (see Figure 2) 1 + 37.2 to 140 Volts DC Power for CIM and Close Function. Required for proper operation. 2 Close Coil. Required for proper operation. External Reclose is Connected between terminals 2 and 3 of TB-1. 3 43X. External Reclose Enable Output. External Reclose is Connected between terminals 2 and 3 of TB-1. 4 - DC Power for CIM and Close Function. Required for proper operation. Removable Terminal Block (see Figure 3) 1 Not used in Dual Trip Coil Mode. 2 Not used in Dual Trip Coil Mode. 3 Not used in Dual Trip Coil Mode. 4 Not used in Dual Trip Coil Mode. 5 Not used in Dual Trip Coil Mode. 6 Not used in Dual Trip Coil Mode. 7 Output to External Reclose Relay. Normally connected to the negative power terminal of the external relay. Pin 7 must be more positive than pin 8. 8 Output to External Reclose. Normally connected to the negative power rail. Pin 8 must be negative relative to pin 7. 9 XB contact closure input. Monitors breaker position and is required for proper operation. 10 XA contact closure input. Monitors breaker position and is required for proper operation. 11 + DC Power Trip Coil 2 and XA and XB circuits. Required for proper operation. 12 Trip Coil 2 Output. Required for proper operation 13 + DC Power for TRIP Coil 1. Required for proper operation. 14 TRIP Coil 1 Output. Required for proper operation. Page 28 of 35

Circuit Switcher or Ganged Single Pole Breakers Mode In Circuit Switcher or Ganged Single Pole Breakers mode, which is shown above, the CIM provides one output TRIP signal and monitors three separate TRIP coils. +125 VDC 13 11 1 3 11 52CS/C SCADA CLOSE TB1 1 79 + 7-8 XRC SCADA CLOSE NC 52CS/C 43X 10 XRC S2 2 3 4 79 43X 52/CC 52CS/T SCADA TRIP TCM/2 TCM/A TCM/B TCM/C 52B 14 2 4 6 10 9 52A/T 52B/T 52C/T 52A 52B 52A 52A 52A - 125 VDC Page 29 of 35

Configuring the CIM for Circuit Switcher or Ganged Single Pole Breakers Mode Setting a DIP switch on the bottom of the main circuit board configures the CIM. This is shown in the figure above. Bottom View of CIM with Cover Removed DIP Switch Rear On Off 1 2 3 4 Front ON OFF Triple Trip Coil Page 30 of 35

Control Functions in Circuit Switcher or Ganged Single Pole Breakers Mode TRIP A TRIP is initiated by the CIM when signaled to do so by either the manual switch (52CS/T) or SCADA (if SCADA is enabled). The third source of a TRIP is an external protective relay. A protective relay TRIP is a direct control signal from the protective relay to the breaker and is not influenced by the control logic of the CIM. The TRIP contacts of the 52CS/T switch are directly connected to the terminal block connections, which go to the breaker TRIP coil, providing redundant fail-safe operation in the event of electronics malfunction. In Circuit Switcher mode a single TRIP signal is connected through external diodes to three trip coils. The diodes are necessary in order TRIP coil monitoring to work correctly. TC1 = 52CS/T + SCADA TRIP Once a TRIP is initiated, the CIM will continue to apply voltage to the TRIP` output (CIM removable terminal block, pin 14) until the 52/A contact from the breaker confirms that the breaker has moved into the proper position or 1 second has elapsed, whichever occurs first. When the 52/A contacts indicate the breaker has changed state the green Breaker Open LED will flash to indicate the source of the TRIP signal as follows; Continuous Green Light Trip Caused by external protective relay. Slow Flashing Green Light Manual Trip from 52CS switch. Fast Flashing Green Light Trip from SCADA. TRIP Coil Monitor The CIM unit continuously monitors the Breaker Trip coil while the breaker is in the closed position. While in this position, if the coil has continuity the red TRIP Coil Monitor LED will light and the SCADA trip coil OK status point will be set. A small current is passed through the coil to test for continuity (approximately 1 milliampere). In the event of a coil failure, the TRIP Coil monitor LED will go out and the SCADA trip coil OK status point will be cleared. If the status point is read when the breaker is tripped then the status point will indicate a bad coil so reading this point it should be paired with the breaker status points to accurately ascertain the trip coil condition. Page 31 of 35

CLOSE The CLOSE function is controlled by any one of three input signals, a local manual switch (52CS), a signal from a local Reclose Relay device (79), or from a signal from SCADA (if SCADA is enabled). The local manual switch (52CS/C) is connected directly to the CLOSE contacts of the breaker, thus allowing direct control of the breaker in the event of any loss of control power or electronics within the CIM unit. CLOSE = (SCADA CLOSE + 52CS/T) * SCADA TRIP When the CIM executes a CLOSE command it maintains voltage on the CLOSE output until the breaker 52/B contacts confirm that the breaker has moved into the proper position or 15 seconds, whichever occurs first. At that point the TRIP Coil Monitor will turn on the red TRIP Coil monitor LED and the SCADA breaker open and breaker closed points in the status word are set appropriately. ReClose The ReClose function is controlled directly by an external Reclose Relay. The CIM interacts with the Reclose Relay in two ways. First, a set of polarized, normally open contacts from the CIM (removable terminal block, pin 7 positive and pin 8 negative) activates the external reclose relay. The CIM unit controls the power provided to the Reclose Relay with a solid state relay device. As shown in Figure 8, The positive power terminal for the external reclose relay is connected to the positive power rail (+37.2 to 140 Volts DC). The negative power terminal of the external Reclose relay is connected to pin 7 of the CIM removable terminal block. Pin 8 of the CIM removable terminal block is connected to the negative power rail. Second, the CIM provides a Reclose blocking function (43X). A normally open (NO) contact from the external reclose relay is then connected between the CLOSE terminal of the CIM unit (TB1, pin 2), which is connected to the close coil, and the CIM 43X output (TB1, pin 3). This connects the contacts of the external reclose relay in series with the enable/disable switch and an interlocking relay named 43X. The 43X device provide an interlocking function to prevent a pumping action on the Close cycle of the circuit breaker. 43X = (SCADA ENABLE RECLOSE + 52CS/C) * (SCADA DISABLE RECLOSE + 52CS/T) XRC = S2 * 43X If the ReClose function is being performed by a digital protective relay or other IED, then the same logical functions are performed, but it is necessary to take into account the particular scheme emp0lyed by the external relay. The following two tables shows connections to two common protective relays. Page 32 of 35

DPU 2000 CIM Connection Relay Connection External Connection TB1-1 + Power Supply for Close TB1-3 + IN +OUT TB1-2 -OUT 52/CC SEL 251, SEL 351 CIM Connection Relay Connection External Connection Removable Block, pin 7 -INX TB1-1 +INX + Power Supply for Close TB1-3 +OUTX TB1-2 -OUTX 52/CC Page 33 of 35

Connections in Circuit Switcher of Ganged Single Pole Breakers Mode Terminal Block TB-1 (see Figure 2) 1 + 37.2 to 140 Volts DC Power for CIM and Close Function. Required for proper operation. 2 Close Coil. Required for proper operation. External Reclose is Connected between terminals 2 and 3 of TB-1. 3 43X. External Reclose Enable Output. External ReClose is Connected between terminals 2 and 3 of TB-1. 4 - DC Power for CIM and Close Function. Required for proper operation. Removable Terminal Block (see Figure 3) 1 + DC Power for TRIP Coil Monitor A. Required for proper operation. 2 TRIP Coil Monitor A input. Normally connected to TRIP Coil A. Required for proper operation. 3 + DC Power for TRIP Coil Monitor B. Required for proper operation. 4 TRIP Coil Monitor A input. Normally connected to TRIP Coil B. Required for proper operation 5 + DC Power for TRIP Coil Monitor C. Required for proper operation. 6 TRIP Coil Monitor A input. Normally connected to TRIP Coil C. Required for proper operation 7 Output to External Reclose Relay. Normally connected to negative power terminal of an external relay. 8 Output to External Reclose. Normally connected to the negative power rail. 9 XB contact closure input. Monitors breaker position and is required for proper operation. 10 XA contact closure input. Monitors break position and is required for proper operation. 11 + DC Power for XA and XB circuits. Required for proper operation. 12 Not used in Circuit Switcher mode. 13 + DC Power for TRIP Coil 1. Required for proper operation. 14 TRIP Coil 1 Output. Required for proper operation. Page 34 of 35

Specifications and Tests Operating Voltage TRIP Contact Ratings 38 to 140 V DC @ 100 milli-amps 140 VDC maximum 0 to 0.5 seconds 20 A < 1second 15 A < 1 minute 1 A Continuous 0.5 A CLOSE/Reclose Contact Ratings 140 VDC maximum 0 to 1 second 30 A < 1 minute 3 A Continuous 1.5 A SCADA Interface RS 485 External ReClose Output Ambient Temperature Rating Surge Withstand Capability 140 V maximum - 1 A maximum -20 deg. C to +55 deg. C Per IEEE C37.90.1-2500 V Oscillatory Surge 5000 V Fast Transient EMI/RFI (Radio Frequency Immunity) Per IEEE C37.90.2 Dielectric Withstand Voltage 1500 VDC for 60 seconds Tested Life Under Rated Load 10,000 Operations Environmental Testing 80 C for 120 hours 40C for 96 hours at 90 to 95% RH Page 35 of 35