Transformer core modeling for magnetizing inrush current investigation.

Similar documents
Study on Power Transformer Inrush Current

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD

International Journal of Engineering Trends and Applications (IJETA) Volume 4 Issue 2, Mar-Apr 2017

Limiting Sympathetic Interaction Between Transformers Caused by Inrush Transients

An Inrush Current Elimination Technique for Line-Interactive UPS Systems During Switching-in of an Auxiliary Load While Feeding a Main Load

1278 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006

AN ADVANCED APPROACH TO IDENTIFY INRUSH CURRENT AND HARMONICS USING ARTIFICIAL INTELLIGENCE FOR POWER SYSTEM PROTECTION

Micro physical simulation system of electric power systems

VOLT-SECOND BALANCE METHOD FOR MITIGATION OF INRUSH CURRENT IN SINGLE PHASE TRANSFORMERS

Mitigate Inrush Current of transformer with Prefluxing Technique

PREDETERMINING THE SIZE OF INRUSH CURRENT IN POWER TRANSFORMERS COUPLING USING LABVIEW

Reduction of Inrush current in Three Phase Power Transformers using SSSC Device

Assessment of Inrush Current for Power Transformers by Three-Dimensional Representation

Discrimination of magnetic inrush current from fault current in transformer - A new approach

Voltage Control by Microcontroller to Reduce Transformer Inrush Current

Effective Management of Transformer Inrush during Restoration of a Typical Industrial Power System

Reduction of Switching Surges in Large Industrial Motors Connected by Cables

Main Components of a Static Var Compensator (SVC)

Short-Circuit Calculation Methods

Application of Transmission Line Surge Arresters to Reduce Switching Overvoltages

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

International Journal of Advance Research in Engineering, Science & Technology

Precise Algorithm for Nonlinear Elements in Large-Scale Real-Time Simulator. Olivier TREMBLAY*, Martin FECTEAU, Pascal PRUD HOMME Hydro-Québec CANADA

INRUSH CURRENT REDUCTION IN THREE PHASE POWER TRANSFORMER BY USING PREFLUXING TECHNIQUE

POWER FACTOR CORRECTION USING SVC WITH FUZZY LOGIC CONTROLLER

Circuit Breaker Operation & its load calculations

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

Preventing Transformer Saturation and Inrush Current

HVDC Control and Protection Testing Using the RTDS Simulator

CIRCUIT BREAKER TYPE DISCONNECTOR for OVERVOLTAGE PROTECTOR

Capacitor Switching Contactors

Computer Aided Design and Transient Finite Elements Analysis of Induction Motor

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering

Distribution Static Var Compensators and Static Synchronous Compensators for Suppressing Voltage Fluctuation

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

DEVELOPMENT OF PREVENTIVE MAINTENANCE SYSTEM ARISING IN ADVANCED EDDY CURRENT TESTING USING NETWORK TOMOGRAPHY

Integrating Electromagnetic Transient Simulation with Other Design Tools

A Svc Light Based Technique for Power Quality Improvement for Grid Connected Wind Energy System

Application of Multi-level Multi-domain Modeling to a Clawpole

Evaluation of Transient Overvoltages at Terminations in Low-voltage Installations

Final Report. Mini Project TET Group nr 7 - Project nr 4. Students: Hans Lavoll Halvorson, NTNU

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

CP30F Series Circuit Protector for Improving Safety and Wiring Workability

Smart Power Flow Monitoring and Control

Quantum Chargers Enhanced AC Line Transient Immunity

Let s review the four equations we now call Maxwell s equations. (Gauss s law for magnetism) (Faraday s law)

Transient Stability Improvement of Long Transmission Line System by Using SVC

Midwest Energy, Inc. Distributed Generation Interconnection Expedited & Standard Process Application

AIR COOLED MODULAR RECTIFIER

Re-Dispatching Generation to Increase Power System Security Margin and Support Low Voltage Bus

Evaluation of different solutions of faulted phase earthing technique for an earth fault current limitation

Control System for Electrical Exploding Wire Opening Switch Experimental Equipment

Definition and Application of Magnetic Material Metrics in Modeling and Optimization

Quality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Model Number Structure

PERFORMANCE SPECIFICATION SHEET

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Transformer Inrush Current Minimizer Type: TRIM3 Operation Manual

THE INTEGRATED TESTING SOLUTION

Residential/Commercial/Industrial

Circuit Protection Application Note TBU Electronic Current Limiter GR-1089 Port Type 2 and 4 Ethernet Protection

PERFORMANCE SPECIFICATION SHEET

Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ).

Selective overcurrent protection for large MV installations

Suppressing Transients: A New Approach

Automatic simulation of IED measurements for substation data integration studies

Electromagnetic Compatibility ( EMC )

A Development of Electro-Static Discharge Evaluation Circuit for Varistors and Zener Diodes

US Catalog March Surge protective devices (SPDs) UL range

Benchmark systems for ElectroMagnetic Transient (EMT) and Transient Stability (TS) hybrid simulation

QUALITATIVE MODELING FOR MAGNETIZATION CURVE

F6150. Power System Simulator For Testing Protection Relays and Schemes.

Relays & Sockets. RSC Series. RSC Series Solid State Relays. Part Number Selection Specifications

LED Driver Linear / area dimming. Driver LC 50W mA 54V 0-10V lp EXC UNV EXCITE series SELV

LED Driver Compact dimming

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

LED Driver Compact dimming

LED Driver Linear / area dimming

METAL OXIDE VARISTORS

LED Driver Compact dimming

Solid State Remote Power Controller E /627

Simulation of Series Compensated Transmission Lines Protected with Mov Abdolamir Nekoubin

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output

Commission Testing Methods for Protection Systems

LED Driver Linear / area dimming

Hybrid Optimization Strategy using Response Surface Methodology and Genetic Algorithm for reducing Cogging Torque of SPM

For the State of Washington SMALL GENERATOR INTERCONNECTION REQUEST (Tier 1 [Non-Net Meter], Tier 2, Tier 3) (Application Form)

LED Driver Linear / area fixed output

LED Driver Linear / area fixed output

White Paper Surge Current Characteristics: 570 Hybrid Surge Protective Device

LED Driver Linear / area dimming

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

Prepared by: Yvon Filion eng. TransÉnergie, a division of Hydro-Québec

PERFORMANCE SPECIFICATION SHEET

Micro Grid Architecture for Line Fault Detection and Isolation

Model export to Ansys Electronics Desktop

Implementing an Advanced Simulation Tool for Comprehensive Fault Analysis

LED Driver Linear / area fixed output

Transcription:

Mediterranean Journal of Modeling and Simulation MJMS 1 (214) 77 88 Transformer core modeling for magnetizing inrush current investigation. A.Yahiou a, A. Bayadi b a Department of Electrical Engineering, Setif-I- University, Algeria Abstract The inrush currents generated during an energization of power transformer can reach very high values and may cause many problems in power system. This magnetizing inrush current which occurs at the time of energization of a transformer is due to temporary overfluxing in the transformer core. Its magnitude mainly depends on switching parameters such as the resistance of the primary winding and the point-on-voltage wave (switching angle). This paper describes a system for measuring the inrush current which is composed principally of an acquisition card (EAGLE), and LabVIEW code. The system is also capable of presetting various combinations of switching parameters for the energization of a 2 kva transformer via an electronic card. Moreover, an algorithm for calculating the saturation curve is presented taking the iron core reactive losses into account, thereby producing a nonlinear inductance. This curve is used to simulate the magnetizing inrush current using the ATP-EMTP software. Keywords: Inrush current measurement, transformer, Core nonlinearities, Modelling, ATP-EMTP Simulation. Nomenclature ATP Alternative Transients Program EMTP ElectroMagnetic Transient Program : Flux density. : Resistance. : Magnetizing current. : Apparent losses : rms current. : Peak voltage. : Inductance. : rms voltage. : Number of segments. : Linkage flux. : Real losses. : Residual flux. : Reactive losses. : Break points 1. Introduction Magnetizing inrush current in the transformers results from any abrupt changes of the magnetizing voltage. This current in transformer may be caused by energizing an unloaded transformer. Because the amplitude of inrush current can be as high as a short-circuit current [1], a detailed analysis of the magnetizing inrush current under various conditions is necessary

A.Yahiou et al. / MJMS 1 (214) 77 88 for the concerns of a protective system for the transformers. In this regard, some numerical and analytical methods have been proposed in the literature. Bertagnolli proposes a relatively simple equation based on a sustained exponential decay of the inrush current [2]. The analytical formula proposed by Specht is somewhat more accurate as the decay of the dc component of the flux (BR) is considered only during saturation (B > BS) [3]. Holcomb proposes an improved analytical equation [4]. We find an improved design method for a novel transformer inrush current reduction scheme in [5]. The used scheme energizes each phase of a transformer in sequence and uses a neutral resistor to limit the inrush current. A transformer model for inrush current simulation based on separate magnetic and electric equivalent circuits is discussed in [6]. Some methods have been used to convert the curve to (flux peak current) curve [7, 8]. In this paper, first, a method to calculate the saturation curve is presented taking the iron core reactive losses into account, thereby producing a nonlinear inductance. It is also shown that the method is applicable for modelling nonlinearities of power transformers. Then, the system for measuring the inrush current is described. The system is also capable of presetting two factors affecting the magnetizing inrush current (resistance and the point- on-voltage wave at the instant of energization). Finally a one-phase transformer is simulated in ATP- EMTP software, the simulation results are compared with the experimental results. 2. Flux and inrush current As seen from the Fig. 1 (this figure shows the generation of inrush current in a transformer), exceeding flux from the knee point, results in large magnetizing current that in some circumstances can be ten times of the rated current in a transformer. λ λ Magnetisation curve λ r Flux t l l Magnetising current t Inrush current Figure 1. Flux VS magnetzing current. 3. Iron core modelling Under open circuit test configuration, the equivalent circuit of a power transformer can be reduced to a resistance in parallel with an inductance [9], as shown in Fig. 2. The main nonlinear element in the transformer s model is a ferromagnetic inductance. The inductance is defined by gradient in any point of nonlinear magnetizing curve. The piecewise linearized curve is shown in Fig. 3. For computation, the method requires only ( ) curves and the no-load losses at fundamental frequency. Then, calculates the reactive power using: 78

Linkage flux λ A.Yahiou et al. / MJMS 1 (214) 77 88 (1) Where: : Apparent power of the segment.. i t (t) i r (t) i l (t) v(t) R m L m Figure 2. Transformer model for open circuit test. λ3 λ2 XmN λ1 Xm2 Xm1 Xm2 Xm1 -λ1 Magnetizing current i l XmN -λ2 -λ3 Figure 3. Nonlinear saturation curve. 3.1. Computation of magnetizing curve Let us assume that the reactive no-load losses are available as a function of the applied voltage, as shown in Fig. 4. Figure 4. Characteristic. Because of the symmetry of the characteristic with respect to the origin, it is sufficient to observe quart of the cycle, in other word for an angle (Fig. 5). In general, can be found for each through the nonlinear characteristic, either graphically as indicated by the dotted lines in Fig. 8. This will give us the curve over quart of a cycle, from which the no-load reactive losses are found: 79

A.Yahiou et al. / MJMS 1 (214) 77 88 (2) Let us address the reverse problem, i.e., constructing the reactive losses. For the reactance is equal: from the given no-load (3) The current of the first segment is: (4) For, we must use the reactive power definition of equation (2), with the applied voltage. (5) With is the peak voltage. (6) The points in equation (5) are known using: The only unknown factor in equation (5) is the slope of last segment during the current calculation of the same slope. Equation (5) can be rewritten as follows (simplified form): (7) (8) 8

A.Yahiou et al. / MJMS 1 (214) 77 88 v( ) v 3 v v 2 v 1 X 2 X 3 1 π/2 (c) X 1 l1 l2 l3 l (a) l( ) 1 (a) The current π/2 Figure 5. Calculation of the nonlinear inductance. Curve, (b) Output current, (c) Sinusoidal input voltage signal. is obtained by: (b) The above mentioned procedure stages for calculating the saturation curve are summarized in the following flow chart (Fig. 6). (9) 81

A.Yahiou et al. / MJMS 1 (214) 77 88 Begin Input the values of V eff, I eff and P k. N: size of vector V eff Calculate i l1 And X 1. Determine Q k 1. α j= No If i i Yes Calculate α ij i=2, j=1 Calculate y k c j = No If i j Yes Calculate : c j 8,., X 9. Saturation curve = ( ) End Figure 6. Flow chart to compute. No load losses and rms current at 5 Hz were measured for different voltage levels are shown in Table I. According to Faraday s law and in case of a sinusoidal applied voltage, it can be written [1]. The computed points (including core losses) using our approach are shown in table II. The results obtained using the method described in [11] are included for comparison purposes. The obtained characteristic is shown in Fig. 7. It is noted that there is a superposition up to the point (127.78,.6874) because the transformer has an internal capacitance between the coils and between the winding and the ground. Therefore there is a small current in the magnetizing branch of the equivalent circuit. As can be seen, for the same value of, the current calculated using our approach has a value higher than that calculated by [11], which enables us to predict more exact peak inrush current in the simulation (Fig 13). (1) 82

Linkage Flux (V.s) A.Yahiou et al. / MJMS 1 (214) 77 88 Table 1. Curve point and Corresponding Active Power Losses. (W) (A) (V).25.5 9.9.25.13 31.3 1.28.26 67.2 3.1.42 17.9 6.5.84 152.7 12.217 194.1 17.369 22 19.48 225.6 2.5.435 229.3 Table 2. Calculated Points Of curve. (ma) [11](mA) (V.s) 6.13 6.13.446 13.8743 13.8339.149 23.7278 23.6217.325 45.4 44.9937.4857 127.78 122.7732.6874 431.8758 393.5898.8738 766.898 697.2619.993 838.482 765.6141 1.156 886.2378 89.4472 1.322 1.4 1.2 With Active Losses[11] With Reactive Losses 1.8.6.4.2 2 4 6 8 1 Magnetizing Current (ma) Figure 7. Magnetization (saturation) curve l. 83

4. Measurement setup of inrush current Unloade d 2kVA, 22/25V A.Yahiou et al. / MJMS 1 (214) 77 88 One power transformer (2 kva) has been used for laboratory investigations. This transformer is manufactured by unilab laboratory (Italy). It is unloaded; the high voltage side is connected to voltage supply. The laboratory arrangement with the voltage and current measurement points is shown in Fig. 8. A photo is shown in Fig. 9. The data acquisition system has been used to record voltages and currents at the high voltage side. A total of fifteen analogue input channels with simultaneous sampling are available. The input voltage can be selected among ± 1 V. The graphical user interface in LabVIEW is shown in Fig. 1. -Computer. -LabVIEW software. Switch Control v i Acquisition card Figure 8. Measurement setup scheme. Figure 9. Laboratory setup photo. Figure 1. LabVIEW acquisition interface. Figure 11. LabVIEW acquisition diagram. 5. Measured and simulated inrush current comparison When a transformer is energized under no load or lightly loaded conditions, inrush current may flow in the primary circuit. In order to investigate the effects of some parameters of transformer or network on the inrush current, a single-phase transformer (2 kva, 22/25 V, 9.1/8 A) is selected. The equivalent circuit can be shown in Fig. 12 where,,, and are equivalent resistance, leakage inductance of transformer, core losses resistance, magnetizing inductance and source resistance respectively. Table III presents the parameters obtained according to standards short and open circuit tests. This circuit is simulated using ATP-EMTP software. The BCTRAN module and external nonlinear inductance type 93 representing the saturation curve have been used in this simulation. 84

Inrush Current (A) A.Yahiou et al. / MJMS 1 (214) 77 88 Figure 12. Simulation model of transformer. Table 3. Transformer parameters. Parameter Value 3.48 8.7 2847.1 5.1. Simulation by Using the both Saturation Curves Fig. 13 shows the peak of the measured and simulated inrush current; in the simulation one introduces the both curves in the magnetizing branch, obtained by the method based on the active losses [11], and the method presented in this paper. 4 35 3 25 2 15 Measurement. Simulation Using the calculated Curve According to [11]. Simulation Using the Calculated Curve According to présented Method. 4 35 Zoom 1 5 3.6.65-5.55.75.95.115.13 Time (s) Figure 13. Inrush current comparison. As shown in above figure; it is clear that the peak of the inrush current obtained with using the calculated curve by taking the iron core reactive losses into account, near to the measured peak. So we have a good prediction of the peak Inrush current in the following application. 5.2. Effects of source resistance (R S ) In this case, the switching angle (θ) is considered (primary voltage is V). The effects of series resistance have been considered by increasing. The effect of source resistance on the amplitude of inrush current is presented in Fig. 14. 85

Voltage/1 (V), Current (A) Voltage/1 (V), Current (A) Voltage/1 (V), Current (A) A.Yahiou et al. / MJMS 1 (214) 77 88 37.5 3 5 3 2 5 2 1 5 1 5 Simulated Inrush Current Measured Inrush Current Primary Voltage/1 Supply Voltage/1 3 2 5 2 1 5 1 5 Simulatd Inrush Current Measured Inrush Current Primary Voltage/1 Supply Voltage/1-5.6.9.12 Time (s),6,9,12 Time (s) a). b). 2 5 2 17.5 1 5-5 Simulated Inrush Current Measured Inrush Current Primary Voltage/1 Supply Voltage/1 1 5.6.9.12 Time (s) c) Figure 14. Measured and simulated inrush current for different values of R S. As can be seen from Fig 13, increasing source resistance will decrease the amplitude of inrush current. Moreover, it causes faster decay in the amplitude of inrush current. Therefore, it can be said that transformers located closer to the generating plants display higher amount of inrush currents lasting much longer than transformer installed electrically away from generator. 5.3. Effect of the switching angle (Point- On-Voltage) -5 In this section, the effect of the closing moment of circuit breaker or the point on the voltage wave where the circuit breaker is closed has been investigated. In this case the series resistance is ignored. The first result was already presented in Fig. 14 a. Fig. 15 presents the first measured and simulated five peaks of inrush current when the applied voltage is equal to 195 V and then to 182 V (i.e. for closing times t =,492s and t =,51s respectively). It is noted that the highest inrush current amplitude took place when the value of the primary voltage of the transformer is equal to zero. Moreover, the increase in the angle on the voltage wave makes decrease of its amplitude. The energization of the power transformers with a random circuit breaker closing can generate very important amplitude of inrush current. So, it is necessary to control the circuit breaker to choose the optimal moment as a function of the network voltage which allows opening or closing the circuit breaker. 86

Voltage/1 (V), Current (A) Voltage/1 (V), Current (A) A.Yahiou et al. / MJMS 1 (214) 77 88 3 2 5 (.492, 195) 2 17.5 1 5 Measured Inrush Current Primary Voltage/1 Supply Voltage/1 Simulated Inrush Current 3 2 5 2 1 6.5 (.51, 182) Measured Inrush Current Primary Voltage/1 Supply Voltage/1 Simulated Inrush Current 1 1 5 5-5 (a) t=,492s (b) t =,51s Figure 15. Measured and simulated inrush current for different Point- On-Voltage. 6. Conclusion In This paper a system for measuring the inrush current which is composed mainly of an acquisition card and LabVIEW code is described. The system is capable of presetting various combinations of switching parameters for the energization of a 2 kva transformer via an electronic card. Moreover, an algorithm for calculating the saturation curve is presented taking the iron core reactive losses into account, thereby producing a nonlinear inductance. This curve is used to simulate the magnetizing inrush current using the ATP-EMTP software. The results show that increasing switching angle (the point on the voltage wave) or source resistance will decrease the amplitude of inrush current. Therefore, the transformers located closer to the generating plants display higher amount of inrush currents lasting much longer than transformer installed electrically away from generator. Moreover, it can be concluded that, for reducing inrush current, an appropriate switching angle by considering residual flux, must be taken into account. 7. References.6.9.12 Time (s).6.9.12 Time (s) [1] Steurer M., Fröhlich K, "The Impact of Inrush Currents on the Mechanical Stress of High Voltage Power Transformer Coils", IEEE Trans. on Power Delivery, Vol.17, No.1, Jan 22, pp. 155-16. [2] G. Bertagnolli, Short-Circuit Duty of Power Transformers, Second Revised Edition. ABB, 1996 [3] T. R. Specht, "Transformer magnetizing inrush current ", AIEE Trans, Vol. 7, 1951, pp. 323-328 [4] J. F. Holcomb, "Distribution transformer magnetizing inrush current", Transactions of the American Institute of Electrical Engineers, Part III (Power Apparatus and Systems), Vol. 8, No. 57, Dec. 1961, pp. 697-72 [5] Sami G. Abdulsalam, and Wilsun X " Analytical Study of Transformer Inrush Current Transients and Its Applications ", IPST 5 - International Conference on Power Systems Transients, Montreal, Canada June 19-23, 25, No. 14 [6] N. Chiesa, B. A. Mork, and H. K. Høidalen, " Transformer Model for Inrush Current Calculations: Simulations, Measurements and Sensitivity Analysis", IEEE Trans on Power Delivery, Vol. 25, No. 4, Oct 21, pp. 2599-268 -5 87

A.Yahiou et al. / MJMS 1 (214) 77 88 [7] A. Tokic, I. Uglesic, et F. Jakl, " An algorithm for calculations of low frequency transformer transients", IPST 3 - International Conference on Power Systems Transients,, New Orleans, Louisiana, USA, Sep. 23 No. 9a-2 [8] W.Wiechowski, B.Bak-Jensen, C. Leth Bak, J. Lykkegaard " Harmonic Domain Modelling of Transformer Core Nonlinearities Using the DIgSILENT PowerFactory Software",Electrical Power Quality and Utilisation, Journal, Vol. XIV, No. 1, 28 [9] Joydeep Mitra "Advanced transformer modelling for transients simulation" Department of Electrical and Computer Engineering, North Dakota state University, Fargo, North Dakota 5815, July 21, 23 [1] Arrillaga J., Watson N.R.: "Power System Harmonics". John Willey & Sons, London, 23, p. 62 64 [11] Neves L.A.N., Dommel H.W.: "On Modelling Iron Core Nonlinearities". IEEE Trans on Power Systems, Vol. 8, No. 2, May 1993, pp. 417 425 88