FIELDVUE DVC6200 and DVC6200f Digital Valve Controller Management of Change Guide

Similar documents
Fisher FIELDVUE DVC6200 HW2 Management of Change Guide

DVC2000 Series FIELDVUE Digital Valve Controllers

Fisher FIELDVUE DVC2000 Digital Valve

Fisher FIELDVUE DVC2000 Digital Valve

Type i2p-100 Electro-Pneumatic Transducer

Fisher i2p-100 Electro-Pneumatic Transducer

Proximity Positioner. ICoT. Valve Monitoring and Control Products WESTLOCK

FIELDVUE Instrumentation

FIELDVUE DVC2000 Series Digital Valve Controllers

CHRONOS IDP INTEllIGENT DIGITAl POSITIONER FOR CONTROl VAlVES

Valtek Logix Series Digital Positioner

Fisher i2p-100 Electro-Pneumatic Transducer

FIELDVUE DVC5000f Series Digital Valve Controllers for FOUNDATION fieldbus

Fisher FIELDVUE DVC6000f Digital Valve Controllers (Supported)

VVP10-H HART VALVE POSITIONER. Great Performance, Compact, Robust in Severe Conditions* HART 7 Communication Protocol. Electronic Coil Technology

Fisher 657 and 667 Size 30i - 76i Diaphragm Actuators

FIELDVUE Digital Valve Controllers. Tri-Loop Signal Converter Operation with FIELDVUE Digital Valve Controllers

Fisher FIELDVUE DVC2000 Digital Valve

HART Field Device Specification Fisher FIELDVUE DVC2000 Digital Valve

Fisher i2p-100 Electro-Pneumatic Transducer

Fisher FIELDVUE DVC6200f Digital Valve Controller for FOUNDATION Fieldbus

Installing ValveLink Software. ValveLink Solo ValveLink SNAP ON ValveLink DTM ValveLink PLUG IN for PRM. Installation Guide D102800X012

HART Field Device Specification Fisher FIELDVUE DVC6000 and DVC6200 HW1 Digital Valve Controllers

SVI II ESD. SIL3 Partial Stroke Test Device October 2007 BW5000-ESD. The only SIL3 Smart ESD device that is live during and after a shutdown.

HART Field Device Specification Fisher FIELDVUE DVC6200 SIS Digital Valve

Series 3730 Electropneumatic Positioner Type

Fisher FIELDVUE DVC6200p Digital Valve

SRD991 Intelligent Positioner with HART, FoxCom, PROFIBUS-PA, FOUNDATION Fieldbus H1 or Without Communication

Data Sheet T 8394 EN. Series 3725 Type 3725 Electropneumatic Positioner

Series 3730 Type Electropneumatic Positioner

Project Execution Best Practices

3200IQ Digital Positioner

TECHNICAL BULLETIN. Logix 3200IQ Digital Positioner. Experience In Motion FCD LGENTB /11

Series 3731 Electropneumatic Ex d Positioner Type with FOUNDATION TM Fieldbus communication

Rosemount Transmitter Diagnostics Reduce Maintenance Costs

Type 330SA High-Performance Electric Actuator

A Guide to Management of Change -

HART Field Device Specification Fisher FIELDVUE DVC5000 Digital Valve Controllers

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs

AMS ValveLink Software Quick-Start Guide

Safety manual for Fisher FIELDVUE DVC6200 SIS Digital Valve Controller, Position Monitor, and LCP200 Local Control Panel

The TVC Positioner is designed to provide precise position control of rotary or linear hydraulic or pneumatic actuated valve systems.

II ESD. SIL3 Partial Stroke Test Device. The only SIL3 Smart ESD device that is live during and after a shutdown.

LineGuard Specification Sheet Issued 8/24/10 VA Revision 0. Valve Automation

Supplement to Fisher FIELDVUE DVC6000 SIS Series Digital Valve Controllers for Safety Instrumented System (SIS) Solutions Instruction Manual

Digital EPIC D460/D470 For Rotary, Linear and Standard Applications Operating Manual

TECHNICAL BULLETIN. Logix 500si Series Digital Positioner. Experience In Motion FCD LGENTB /05

TECHNICAL BULLETIN. Logix 500si Series Digital Positioner. Experience In Motion FCD LGENTB /13

Baumann Little Scotty Bronze Control Valve

WIRELESS REMOTE ASSET MONITORING & CONTROL

LTM IntelliGage Series Magnetostrictive Level Transmitters

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 NPT

Performance!Nxt Release

PROFIBUS-PA Positioner Type 3785

Series 3731 TROVIS SAFE Electropneumatic Ex d Positioner

Dual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed.

Operating Instructions EB 8388 EN. Series 373x Positioners. EXPERT + Valve Diagnostics

Digital EPIC Control Transmitters Weatherproof, Intrinsically Safe - ATEX/IEC

Installing ValveLink DTM Software

Data Sheet T 8493 EN. Series 3793 TROVIS 3793 Electropneumatic Positioner with HART communication

Series 3793 TROVIS SAFE 3793 Electropneumatic Positioner with HART communication

IHP24. Intelligent Hydraulic Positioner D HP- PL

Digital Positioner 8049

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

2-IQ Series Smart Valve Positioners

NDIR Infrared Gas Analyzer

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010

Series 3731 Type Electropneumatic Ex d Positioner with FOUNDATION TM fieldbus communication

MTL8000-2/x Series Modular I/O

Instrumentation for Process Analytics

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

Powers TM Controls RL 243 MP Multi-Purpose Relay

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

VEGA SOFTWARE AND DISPLAY INSTRUMENTS

Series 3731 Type Electropneumatic Ex d Positioner with HART communication

Electric Actuators Type 5824 (without fail-safe action) Type 5825 (with fail-safe action)

Submersible Liquid Level Transmitter Series: PT-500

Description: IRB-540 Robot with 6-axis Flexi-Wrist Manipulator, S4P Controller, Conveyor Tracking, and Analog Paint Regulation (APR)

QUICKSTART GUIDE. Infrared Gas Analyzer. Teledyne Analytical Instruments

Fisher FIELDVUE DVC6200p Digital Valve Controller Device Setup and Accessing Communication and Calibration using Siemens SIMATIC Manager/PDM

Level-Lance Model 5400A

TopWorx 4310 Wireless Position Monitor

D3 Digital Positioner. PMV D3 Digital Positioner Product Information. A Flowserve Company

Instruction Manual EW2002-AP 06/10 Rev D. Putting You In Control SVI II AP. Digital Positioner With Remote Position Sensor

AS-interface Network Card

Advanced Fieldbus Diagnostics, Without Fieldbus

Installation and operating instructions

SX90 Process Controller

Do not open when energized or when an explosive atmosphere is present. Electrostatic hazard, clean only with damp cloth.

LED indicators for normal/fault operating conditions, setup mode, loss of analog signal, and solid-state motor control output.

JT400 Multivariable Transmitter

Oil & Gas. Control Control. every move. Pressure Temperature Level Flow

Explosion Proof I/P Transducer

Trusted Strategic Partners in Process Automation. Alliance Member

Hytork XL Pneumatic Actuator

TPE 1464 Series Pressure Transducer

Foundation Fieldbus 5400-IS ICoT Positioner

BLISS ANAND. BA-Series Magnetostrictive Level Transmitter

Tracy Dye, CPAC Rome, March 21 24, Miniature Sample Handling and Analytical Techniques Workshop NeSSI Generation 2

FieldLink process networking

Transcription:

Fisher FIELDVUE DVC6200 and DVC6200f Digital Valve Controller Management of Change Guide 2011 Fisher Controls International LLC. All rights reserved. MY30 (H:)

TABLE OF CONTENTS Background... 3 Management of Change... 3 Common Management of Change (MOC) Checklist Question and Answer... 3 FIELDVUE DVC6000 and DVC6200 Instrument Comparison... 4 DVC6000 to DVC6200 Instrument Transition Design Comparison... 8 1. Electrical - No Change to IS Entity Parameters (Figures 6-9)... 8 2. Position Control Capability... 10 3. Diagnostics Capabilities - No Change (Table 3)... 10 4. Operating Ambient Temperature Limits - No Change... 11 5. Steady-State Air Consumption - No Change... 11 6. Maximum Output Capacity - No Change... 11 7. Connections - No Change... 11 8. Available Configurations... 11 Conclusion... 11 2

Background The Fisher FIELDVUE DVC6000 series of digital valve controllers have proven to be the most reliable digital valve controllers produced. Today, the introduction of the DVC6200 and DVC6200f marks a step change in the technology, which will further improve the reliability of these instruments in the harshest environments. This step change in technology was made possible by utilizing the proven modular technology of the one million and counting existing DVC6000 units in the field today. The design philosophy of the DVC6200 and DVC6200f allows the user the flexibility to transition from legacy FIELDVUE products to the current DVC6200, avoiding lengthy management of change approval documents. This document will highlight the design of the DVC6200 and DVC6200f, which incorporates linkage-less, non-contact feedback technology into an intrinsically safe and explosion-proof package. This feedback technology has been field-proven in the DVC2000 since 2004 in high vibration and corrosive environments. Over 73,000 FIELDVUE DVC2000 instruments have been installed with no failures of this feedback technology. Management of Change Management of change (MOC) is a procedure used to proactively manage changes that have the potential to result in safety or process impacts. Evaluating new techniques for improving MOC approval procedures can have an impact on plant efficiency. Historically, upgrading obsolete products or replacing existing process control equipment has been delayed or abandoned due to the extensive paper work involved in completing a complex MOC approval sheet. Displayed in the following sections are design comparisons between the current DVC6200 and legacy DVC6000 products. These comparisons demonstrate how the design of Fisher technologies allows users to efficiently transition to new, more reliable FIELDVUE products. Common Management of Change Checklist Question and Answer Q1. Does the proposed modification cause any changes to P&ID s? A1. Only the instrument name changes from DVC6000 to DVC6200. Q2. Does the proposed modification change process chemistry, technology or operating and control philosophies? A2. No. Q3. Have the operating and design limits of the proposed modification changed? A3. No. Q4. Have the codes and standards to which the new equipment has been designed changed? A4. No. Q5. Does the proposed modification change the Hazardous Electrical Area classification? A5. No. Q6. Does the proposed modification change existing or create new demands for battery back-up or other power supply redundancy or reliability? A6. No. Q7. Does the proposed modification introduce new equipment that needs to be operated and, has a new operations list been stated? A7. Yes. The DVC6200 and DVC6200f are operated the same as the DVC6000 and DVC600f. 3

Q8. Does the proposed modification introduce new equipment items that require spare parts, training manuals, maintenance procedures or training to teach the maintenance department how to maintain them? A8. Yes. The standard components that maintenance may be required on are the same between the old and new equipment, except for the differing feedback technology. The mounting methodology also varies between the old and new technology. Q9. Does the proposed modification change the spares for existing pieces of equipment? A9. No. Q10. Does the proposed modification introduce new equipment items that require periodic predictive maintenance? A10. No. The new equipment items that may require periodic maintenance are the same as the old equipment items, except for the position feedback element. The new position feedback element (magnet / hall effect sensor) requires no maintenance where the old feedback element was a potentiometer that required periodic evaluation to confirm no mechanical issues were present. FIELDVUE DVC6000 and DVC6200 Instrument Comparison The DV6200 with HART communication uses the same internal components, electronics and covers as the DVC6000. This is detailed below in Table 1. The DVC6000 uses a potentiometer to obtain position feedback, whereas the DVC6200 position feedback utilizes a Hall effect sensor and magnetic array. This is the same technology as used in the DVC2000. The DVC2000 was the first Fisher product released by Emerson that used a Hall effect sensor and a magnet array to measure valve travel. The Hall effect sensor is located in the DVC6200 housing between two pole pieces that are used to sense the magnet flux field of a magnetic array. The magnet array is mounted to the valve stem. As the valve stem moves, the magnet array also moves (relative to the sensor). The magnet array is composed of a series of magnets of different strengths, so the sensor can measure the changing magnetic field. Since there are no touching parts, this feedback is completely non-contact and does not rely on linkages. Table 1: FIELDVUE DVC6000 and DVC6200 Instrument Component Comparison DVC6000 or DVC6000f DVC6200 and DVC6000 DVC6200f and DVC6000f Component I/P No change No change Relay No change No change Printed Wiring Board No change New Term Box No change No change Cover No change No change Mod Base No change No change Back Housing New New Mounting New New Position Feedback DVC2000 Technology DVC2000 Technology Firmware No change New 4

Table 2: FIELDVUE DVC6000 Remote Mount and DVC6200 Remote Mount Component Comparison Description DVC6200 vs. DVC6000 Remote Mount HART DVC6200f vs. DVC6000f Remote Mount Base Unit DVC6205 vs. DVC6005 DVC6205f vs. DVC6005f I/P No Change No Change Relay No Change No Change Printed Wiring Board No Change New Loop Term Box No Change No Change Field Termination Term Box New New Cover No Change No Change Module Base No Change No Change Back Housing No Change No Change Firmware No Change New Remote Travel Feedback Unit New New Position Feedback DVC2000 Technology DVC2000 Technology Wiring between the remote and base unit Needs to be housed in flexible or rigid metal conduit. 5

FIELDVUE DVC6000 FIELDVUE DVC6200 Figure 1: DVC6000 and DVC6200 Instrument Assembly Comparison The DVC6200 and DVC6200f will utilize a new back housing and mounting as is illustrated in Figures 2 and 3 shown on the subsequent pages. The potentiometer of the DVC6000 is removed from the back plane and replaced with a Hall effect sensor that is potted into the new DVC6200 housing design. The terminal box moves to the left of the instrument in the DVC6200 (when viewed from front); this allows for a tighter fit with small actuators and integral mount actuators like the Fisher GX actuator. The fieldbus version of the new 6200f features a new printed wiring board and firmware required to transition to a universal Emerson microprocessor platform. This microprocessor is designed by Emerson and is manufactured exclusively for the various Emerson divisions. All Emerson divisions having fieldbus devices use this processor; this provides consistent behavior and functionality among all Emerson divisions. This product change will include the following improvements to the DVC6200f instrument: Back-up LAS - Every fieldbus segment has a link active scheduler (LAS). There is also a designated device that will act as the backup LAS if the primary LAS were to become unavailable. The DVC6200f has the ability to act as the back-up LAS. Faster block execution - Faster block execution allows the user to schedule a faster macro cycle (better control) and an increased number of loops per segment (reduced wiring). 6

Potentiometer Terminal box Feedback array Hall effect sensor Terminal box Figure 2: DVC6000 Instrument Housing Detail Figure 3: DVC6200 Instrument Housing Detail DVC6005 Base Unit DVC6205 Base Unit DVC6015 or 25 or 35 (Dependent on Actuator Style) Remote Travel Feedback Unit DVC6215 Remote Travel Feedback Unit Figure 4: DVC6000 Remote Mount Figure 5: DVC6200 Remote Mount 7

DVC6000 to DVC6200 Instrument Transition Design Comparison 1. Electrical - No change to IS entity parameters (Figures 6 9). Figure 6: DVC6200 Instrument FM Schematic 8

Figure 7: DVC6200 Instrument FM Approvals Nameplate Figure 8: FM Schematic for DVC6010, DVC6020, and DVC6030 Instruments 9

Figure 9: FM Nameplates for DVC6010, DVC6020, and DVC6030 Instruments The DVC6200 Remote Mount does not have any third party hazardous area approvals yet. 2. Position control capability a. Accuracy = ± 0.55% of output span b. Hysteresis = ± 0.325% of output span c. Deadband = < 0.125% of output span 3. Diagnostic capabilities - No change (Table 3) Table 3: FIELDVUE DVC6200 and DVC6200f Instrument Diagnostic Level Capabilities Capability Diagnostic Level AC HC or FD AD PD Auto Calibration x x x x Custom Characterization x x x x Burst Communication x x x Alerts x x x Step Response, Drive x x Signal Test and Dynamic Error Band, Valve Signature Performance Tuner x x Travel Control - x x Pressure Fallback Performance Diagnostics x Note: AC = Auto calibration (HART instruments only) HC = HART communications (HART instruments only) FD = Fieldbus diagnostics (fieldbus instruments only) AD = Advanced diagnostics (HART and fieldbus instruments) PD = Performance diagnostics (HART and fieldbus instruments) 10

4. Operating ambient temperature limits - No change a. -40 º to 85 º C (-40 º to 185 º F) b. -52 º to 85 º C (-62 º to 185 º F) for instruments utilizing the extreme temperature option (fluorosilicone elastomers) c. -52 to 125 º C (-62 to 257F) for remote mount feedback unit 5. Steady-state air consumption - No change a. At 1.4 bar (20 psig) supply pressure: less than 0.38 normal m3/hr (14 scfh) b. At 5.5 bar (80 psig) supply pressure: less than 1.3 normal m3/hr (49 scfh) 6. Maximum output capacity - No change a. At 1.4 bar (20 psig) supply pressure: 10.0 normal m3/hr (375 scfh) b. At 5.5 bar (80 psig) supply pressure: 29.5 normal m3/hr (1100 scfh) 7. Connections - No change a. Supply pressure: 1/4 NPT internal and integral pad for mounting 67CFR regulator b. Output pressure: 1/4 NPT internal c. Tubing: 3/8-inch recommended d. Vent (pipe-away): 3/8 NPT internal e. Electrical: 1/2 NPT internal conduit connection 8. Available configurations a. Available configurations change from (three configurations) DVC6000 instrument to (one configuration) DVC6200 instrument, reducing user inventory i. DVC6000 valve-mounted instrument: 1. DVC6010 instrument: Sliding stem applications 2. DVC6020 instrument: Rotary applications and long stroke sliding stem applications. 3. DVC6030 instrument: Quarter-turn rotary applications ii. DVC6200 valve-mounted instrument: 1. DVC6200: Sliding stem, rotary, quarter-turn rotary applications b. Available configurations change from (three configurations) DVC6000 remote mount instrument to (one configuration) DVC6200 remote mount instrument, reducing user inventory i. DVC6000 remote travel feedback sensor: 1. DVC6015 instrument: Sliding stem applications 2. DVC6025 instrument: Rotary applications and long stroke sliding stem applications. 3. DVC6035 instrument: Quarter-turn rotary applications ii. DVC6200 remote travel feedback sensor: 1. DVC6215: Sliding stem, rotary, quarter-turn rotary applications Conclusion The FIELDVUE DVC6000 series of digital valve controllers have proven to be the most reliable digital valve controllers ever produced. The design philosophy of the DVC6200 and DVC6200f instruments allows the user the flexibility to transition from legacy FIELDVUE products to the current DVC6200 instrument, avoiding lengthy MOC approval documents. Please refer to the Fisher FIELDVUE DVC6200 Digital Valve Controller Product Bulletin and Instruction Manual for complete features. 11