Operating instructions Pressure sensor. PE30xx / / 2010

Similar documents
Operating instructions Pressure sensor. PN70xx / / 2010

Operating instructions Pressure sensor. PN70xx / / 2012

Operating instructions Pressure sensor. PN50xx / / 2010

Operating instructions Combined pressure sensor. PN22xx / / 2010

Operating instructions Control monitor for temperature sensors TR /00 04/2011

Operating instructions Electronic temperature sensor TN /00 04/2011

Operating instructions Electronic pressure sensor. PF295x /00 07/2016

Operating instructions Electronic pressure sensor. PI109x / / 2010

Operating instructions Pressure sensor. PN78xx / / 2010

Pressure switch RE B/ Type HEDE10.../1/ Operating instructions

Operating instructions Electronic pressure sensor PI22xx PI23xx

Operating instructions Electronic pressure sensor PI28xx

Operating instructions Electronic pressure sensor PN7xxx

Operating instructions Electronic pressure sensor. PN72xx PN73xx PN76xx / / 2016

Operating instructions Electronic digital pressure sensor EPS25-XXXX-1001

Operating instructions Electronic pressure sensor. PI22xx PI23xx / / 2013

Operating instructions Electronic pressure sensor. PM205x /01 09/2011

Operating instructions Electronic pressure sensor. PN2xxx / / 2015

Operating instructions Electronic pressure sensor. PN22xx PN26xx / / 2015

Operating instructions Programming and display unit PP / / 2010

Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx SB0524

Operating instructions Optical distance sensor O1D / / 2008

Operating instructions Optical distance sensor O1D / / 2012

Operating instructions Control monitor for temperature sensors TR7439

Operating instructions Electronic temperature sensor TN7511

Instruction manual. Electronic pressure gauge (EPG) IM-TE91K033-EN5. Original manual

Installation Instructions Temperature transmitter TAA /00 06/2011

Operating instructions Encoder PerformanceLine. RxP5xx /00 04/2018

Operating instructions Electronic level sensor LK81xx

Operating instructions Flow sensors SAxx04 SAxx14

Operating instructions Photoelectric distance sensor OGD592 OGD593

Operating instructions Electronic level sensor LK10xx LK70xx

Operating instructions Vortex flow meter. SVxxx / / 2015

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Operating instructions Memory plug E /02 11/2011

Operating instructions Optical distance sensor. O5D15x / / 2014

Manual pressure sensors DW35311x DW36311x

Pressure switch type DG 51 E

Operating instructions. Standstill monitor A / / 2011

SM9000. Made in Germany

SM9000. Magnetic-inductive flow meter. Made in Germany

Operating instructions. Speed monitor D / / 2014

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Operating instructions. Switching amplifier DN0210 DN / / 2015

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Operating instructions. ProcessLine analogue module AC / / 2012

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Operating instructions IO-Link INLINE DISPLAY 1.44" E30430

JUMO MIDAS C08. OEM Pressure Transmitter Basic. Applications. Brief description. Special features. Customer benefits

Installation instructions Inclination sensor EC2019 EC / / 2013

Operating instructions Binary level sensor LMC / / 2014

Operating instructions Optical distance sensor. OID25x / / 2014

Operating instructions Optical distance sensor. OID25x / / 2015

Operating instructions RFID evaluation unit DTE / / 2016

JUMO MIDAS C08. OEM Pressure Transmitter Basic. Applications. Brief description. Special features. Customer benefits

Operating instructions Evaluation system for flow sensors VS / / 2013

Operating instructions. Monitor FD / / 2013

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Original operating instructions Fail-safe inductive sensor GG711S

Original operating instructions Fail-safe inductive sensor GI712S

Operating instructions Optical distance sensor. OID20x / / 2014

XXA18P1AM12 Ultrasonic sensor cyl. 90 deg M18 - Sn=1m - analog 4-20mA - SYNC - connector M12

Operating instructions Diagnostic electronics for vibration sensors VSE002 / VXE002 / VXE003 VYE001 / VYE002 / VYE003 / VYE /01 05/2015

Operating instructions. Monitor FS-2 / FS-2N / / 2013

Operating instructions ClassicLine module AC5203 / AC5205 AC5208 / AC5211 AC5213 / AC5214 AC5215 / AC5233 AC /00 02/2015

Operating instructions Monitor FD-2 DR2005 DR / / 2007

Fusion of electronic pressure sensor and analogue display.

Installation instructions Diagnostic electronics for vibration sensors VSE / / 2007

PN7. Communication. Features. Device variant. Copyright 2015, Builder: , Time: 04:31:57

Operating instructions. Monitor FR-1 / FR-1N / / 2013

Operating instructions Optical distance sensor. OID20x / / 2015

Rotary Measuring Technology Absolute singleturn encoder shaft version

AO561 Analog Output Module

TF501, TF521 Terminal Bases

XMLR400M1P25 Pressure sensors XMLR 400bar - G 1/4-24VDC ma - PNP - M12

DI572 Digital Input Module

Communication. Features. Device variant. Copyright 2015, Builder: , Time: 09:23:27

Technical data. General specifications. factory setting: 125 ms Memory Non-volatile memory Write cycles Indicators/operating means

Quick reference guide 3D sensor O3D3xx

DS 201P. Electronic Pressure Switch. Pressure Port With Flush Welded Stainless Steel Diaphragm. accuracy according to IEC 60770: 0.

Communication. Features. Device variant. Copyright 2016, Builder: , Time: 04:59:44

Electronic pressure switch with display Model PSD-4

TSE. Functional Description. Order Code TSE HA /2010. Electrical Pressure Switch N D. p max up to 400 bar (5801 PSI)

Miniaturised pressure sensor Model M-10, standard version Model M-11, version with flush diaphragm

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2

AI561 Analog Input Module

Communication. Features. Device variant. Copyright 2017, Builder: , Time: 01:29:48

Installation instructions RF-identification system with integrated AS-i slave DTSLF / / 2010

Datasheet DE DB_EN_DE44_LCD Rev. ST4-C 07/17. Digital 2-channel differential pressure switch/transmitter with colour-change LCD * *

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Operating and installation instructions Differential pressure monitor

DI561 Digital Input Module

Proximity sensors SME-8M, for T-slot Technical data Magnetic reed

Fusion of electronic pressure sensor and analogue display.

XUK8TAKSMM12 photo-electric sensor - XUK - diffuse - Sn 5m 1Q auto PNP/NPN

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Rotary Measuring Technology

Dimensions. Model Number. Electrical connection emitter. Features. Electrical connection receiver. Product information. Pinout OBE12M-R100-S2EP-IO-V31

DX561 Digital Input/Output Module

DCT 531. Industrial Pressure Transmitter with RS485 Modbus RTU. Stainless Steel Sensor

Transcription:

Operating instructions Pressure sensor PE30xx UK 704884 / 00 08 / 2010

Contents 1 Preliminary note3 1. ymbols used 3 2 afety instructions 3 3 Functions and features 4 4 Function 5 4.1 Processing of the measured signals 5 4.2 witching function 5 4.3 Analogue function 6 5 Installation 6 6 Electrical connection6 7 Operating and display elements 7 8 enu8 8.1 enu structure 8 8.2 Explanation of the menu 9 9 Parameter setting 10 9.1 Parameter setting general 10 9.2 Configuring the display (optional) 12 9.3 Configuration of output 1 12 9.3.1 etting the output function 12 9.3.2 etting the switching limits 12 9.4 Configuration of output 2 12 9.5 User settings (optional) 12 9.5.1 etting the delay time for OUT1 12 9.5.2 etting the damping for OUT1 13 9.6 ervice functions 13 9.6.1 Reading the min./max. values for the system pressure 13 10 Operation 13 10.1 Read the set parameter values 13 10.2 Fault indication 13 11 cale drawing 14 12 Technical data 14 12.1 etting ranges 16 13 Factory setting 17 2

1 Preliminary note 1. ymbols used Instruction > Reaction, result [ ] Designation of buttons, switches or indications Cross-reference Important note Non-compliance can result in malfunctions or interference. UK 2 afety instructions Read this document before installing the unit. Ensure that the product is suitable for your application without any restrictions. Non-adherence to the operating instructions or technical data can lead to personal injury and/or damage to property. In all applications check compliance of the product materials ( chapter 12 Technical data) with the media to be measured. Use in gases at pressures > 25 bar only after contacting the manufacturer ifm For units with culus approval and the scope of validity culus: The device shall be supplied from an isolating transformer having a secondary Listed fuse rated as noted in the following table. Overcurrent protection Control-circuit wire size aximum protective device rating AWG (mm 2 ) Ampere 26 (0.13) 1 24 (0.20) 2 22 (0.32) 3 20 (0.52) 5 18 (0.82) 7 16 (1.3) 10 The ensor shall be connected only by using any R/C (CYJV2) cord, having suitable ratings. 3

3 Functions and features The unit monitors the system pressure of machines and installations. Applications Type of pressure: relative pressure Order no. easuring range Permissible overload pressure Bursting pressure bar PI bar PI bar PI PE3000 0...400 0...5 800 600 8 700 1 000 14 500 PE3001 0...250 0...3 625 400 5 800 850 12 300 PE3002 0...100 0...1 450 300 4 350 650 9 400 PE3003 0...25 0...363 150 2 175 350 5 075 PE3004-1...10-14.5...145 75 1 087 150 2 175 PE3006 0...2.5 0...36.3 20 290 50 725 PE3009-1...1-14.5...14.5 20 290 50 725 PE3029-1...0-14.5...0 10 145 30 450 Pa = bar 10 / kpa = bar 100 Analogue measuring range for PE3004 = 0...10 bar. tatic and dynamic overpressures exceeding the indicated overload pressure are to be avoided by taking appropriate measures. The indicated bursting pressure must not be exceeded. Even if the bursting pressure is exceeded only for a short time, the unit can be destroyed. NOTE: Risk of injury! For gaseous media the application is limited to max. 25 bar. Cannot be used for oils. High-pressure units (400 bar) are supplied with an integrated damping device to comply with the regulations for UL approval and to avoid any risk of injury in case of bursting when bursting pressure is exceeded. When the damping device is removed the damping device can become unusable. When the damping device is removed the unit can no longer be used under UL conditions, If you have any questions, please contact ifm electronic s sales specialists. 4

4 Function 4.1 Processing of the measured signals The unit shows the current system pressure on its display. It generates 2 output signals according to the parameter setting. OUT1 OUT2 switching signal for pressure limit values analogue signal 4..20 ma / 0..10 V 4.2 witching function OUT1 changes its switching state if it is above or below the set switching limits UK (P1, rp1). The following switching functions can be selected: Hysteresis function / normally open: [OU1] = [Hno] ( fig. 1). Hysteresis function / normally closed: [OU1] = [Hnc] ( fig. 1). First the set point (P1) is set, then the reset point (rp1) at the requested distance. Window function / normally open: [OU1] = [Fno] ( fig. 2). Window function / normally closed: [OU1] = [Fnc] ( fig. 2). The width of the window can be set by means of the distance between P1 and rp1. P1 = maximum value, rp1 = minimum value. P 1 P FE 2 P rp HY P rp 1 0 1 0 t Hno Hnc 1 0 1 0 t Fno Fnc P = system pressure; HY = hysteresis; FE = window 5

4.3 Analogue function The analogue output can be configured. [OU2] defines whether the measuring range is provided as 4..20 ma ([OU2] = [I]), or 0..10 V ([OU2] = [U]). Analogue measuring range for PE3004 = 0...10 bar. 5 Installation Before mounting and removing the sensor, make sure that no pressure is applied to the system. Insert the unit in a G¼ process connection. Tighten firmly. 6 Electrical connection The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to. Voltage supply to EN50178, ELV, PELV. Disconnect power. Connect the unit as follows: 2 3 1 4 2: OUT2 4: OUT1 1 2 4 3 BN WH BK BU L+ L Pin 1 Ub+ Pin 3 Ub- Pin 4 (OUT1) switching output for pressure monitoring Pin 2 (OUT2) analogue output for system pressure Core colours of ifm sockets: 1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black). 6

7 Operating and display elements 1 2 3 4 5 6 7 8 9 ode/enter et 10 11 UK 1 to 8: Indicator LEDs --LED 1 to LED 4 = system pressure in unit of measurement as indicated on the label. --LED 4 not used for units with 3 adjustable units of measurement. --LEDs 5 to 7 not used. --LED 8 = switching state of the output. 9: Alphanumeric display, 4 digits --Indication of the current system pressure. --Indication of the parameters and parameter values. 10: et pushbutton --etting of the parameter values (scrolling by holding pressed, incremental by pressing briefly). 11: ode/enter pushbutton --election of the parameters and acknowledgement of the parameter values. 7

8 enu 8.1 enu structure RUN 8

8.2 Explanation of the menu P1/rP1 aximum / minimum value for system pressure, at which output 1 changes its switching status. OU1 OU2 Output function for OUT1: witching signal for the limit values: hysteresis function [H..] or window function [F..], normally open [. no] or normally closed [. nc] each. Output function for OUT2: Analogue signal for the current system pressure: 4...20 ma [I] or 0...10 V [U]. EF Extended functions / Opening menu level 2. UK Uni HI LO d1 dr1 dap di tandard unit of measurement for the system pressure. aximum value memory for the system pressure. inimum value memory for the system pressure (only PE3004, PE3009 and PE3029). witch-on delay for für OUT1. Reset delay für OUT1. Damping for OUT1. Update rate and orientation of the display. 9

9 Parameter setting During the parameter setting process the unit remains in the operating mode. It continues its monitoring function with the existing parameters until parameter setting has been terminated. 9.1 Parameter setting general Each parameter setting requires 3 steps: 1 electing parameter Press [ode/enter] until the requested parameter is displayed. ode/enter et 2 etting the parameter value Press [et] and keep the buton pressed. > > Current setting value of the parameter ode/enter et bit flashes for 5 s. > > After 5 s: etting value is changed: incremental by pressing briefly or scrolling by holding pressed. The numerical values are incremented continuously. If the value is to be reduced: Let the display move to the maximum setting value. Then the cycle starts again at the minimum setting value. 3 Acknowledge parameter value Press [ode/enter] briefly. > > The parameter is displayed again. The new setting value is stored. ode/enter et et more parameters: tart again with step 1. Finishing parameter setting: Press [ode/enter] several times until the current measured value is displayed or wait for 15 s. > > The unit returns to the operating mode. 10

Changing from menu level 1 to menu level 2: [Press [ode/enter] until [EF] is displayed. If the submenu is protected with an access code, [Cod1] flashes in the display. Press [et] and hold it pressed until the valid code no. is shown. Then briefly press [ode/enter]. Delivery by ifm electronic: no access restriction. Press [et] briefly. > > The first parameter of the submenu is displayed (here: [Uni]). ode/enter et ode/enter et UK Locking / unlocking The unit can be locked electronically to prevent unintentional wrong settings. Ensure that the unit is in the normal operating mode. ode/enter et Press [ode/enter] + [et] for 10 s. > > [Loc] is displayed. During operation [Loc] is displayed briefly when you try to change parameter values. For unlocking: Press [ode/enter] + [et] for 10 s. ode/enter et > > [uloc] is displayed. On delivery: Unlocked. Timeout: If no button is pressed for 15 s while the parameters are being set, the unit returns to the operating mode with unchanged values. 10 s 10 s 11

9.2 Configuring the display (optional) elect [Uni] and set the unit of measurement: [bar], [mbar], [Pa], [kpa], [PI], for PE3009 and PE3029 in addition [inhg]. elect [di] and set update rate and orientation of the display: --[d1]: Update of the measured value every 50 ms. --[d2]: Update of the measured value every 200 ms. --[d3]: Update of the measured value every 600 ms. --[rd1], [rd2], [rd3]: Display like d1, d2, d3; rotated by 180. --[OFF]: The display is deactivated in the operating mode. 9.3 Configuration of output 1 9.3.1 etting the output function elect [OU1] and set the switching function: --[Hno] = hysteresis function / normally open, --[Hnc] = hysteresis function / normally closed, --[Fno] = window function / normally open, --[Fnc] = window function / normally closed. 9.3.2 etting the switching limits elect [P1] and set the value at which the output switches. elect [rp1] and set the value at which the output switches back. rp1 is always lower than P1. The unit only accepts values which are lower than P1. 9.4 Configuration of output 2 elect [OU2 ] and set the analogue function: --[I] = current signal proportional to the pressure 4 20 ma, --[U] = voltage signal proportional to the pressure 0..10 V. 9.5 User settings (optional) 9.5.1 etting the delay time for OUT1 [d1] = switch-on delay, [dr1] = switch-off delay. elect [d1] or [dr1] set value between 0.1 und 50 s (at 0.0 the delay time is not active). 12

9.5.2 etting the damping for OUT1 elect [dap], set value. dap-value = response time between pressure change and change of the switching status in milliseconds (ms). The following values can be set. They define the switching frequency (f) of the output: dap 3 6 10 17 30 60 125 250 500 f [Hz] 170 80 50 30 16 8 4 2 1 9.6 ervice functions 9.6.1 Reading the min./max. values for the system pressure elect [HI] or [LO], press [et] briefly. [HI] = maximum value, [LO] = minimum value. Delete memory: elect [HI] or [LO]. Press [et] until [----] is displayed. Press [ode/enter] briefly. [LO] is available only for PE3004, PE3009 and PE3029. UK 10 Operation After power on of the supply voltage the unit is in the Run mode (= normal operation). It carries out its measurement and evaluation functions and generates output signals according to the set parameters. Operation indication chapter 7 Operating and display elements. 10.1 Read the set parameter values Press [ode/enter] briefly until the requested paramerter is displayed. Press [et] briefly. > > The unit indicates the corresponding parameter value for 15 s. After another 15 s the unit returns to the Run mode. 10.2 Fault indication [OL] overload pressure (measuring range exceeded) [UL] underpressure range (measuring range below the minimum value) [C1] short circuit in OUT1; the output is switched off as long as the short circuit exists [Err] (flashing) internal fault The faults C1 and Err are indicated even if the display is deactivated. 13

11 cale drawing 2 3 34 48 1 91,5 94,1 1) 12 x1 57,3 59,6 1) 21,5 27 1,3 30 G 13,5 16,5 1) 1/ 4 Dimensions are in millimeters 1) = dimensions for PE3000 1: display 2: LED s 3: programming button 12 Technical data Operating voltage [V]... 18...36 DC 1) Current rating [ma]... 250 Current consumption [ma]... < 50 Reverse polarity and overload protected... up to 40 V hort-circuit protected; Watchdog Voltage drop [V]... < 2 Power-on delay time [s]... 0.3 witching frequency [Hz]... max.170 Analogue output... 4...20 ma / 0...10 V ax. load current output [Ω]... 500 in. load with voltage output [Ω]... 2000 Response time analog output [ms]...< 3 14

Accuracy / deviations (in % of the span) - Accuracy of switch point... < ± 0.5 - Characteristics deviation... < ± 0.25 (BFL) / < ± 0.5 (L) - Hysteresis... < 0.25 - Repeatability (with temperature fluctuations < 10K)... < ± 0.1 - Long-time stability (in% of the span per year)... < ± 0.05 - Temperature coefficients (TEPCO) in the compensated temperature range 0... +80 C (in% of the span per 10 K) - greatest TEPCO of the zero point / of the span... < ± 0.2 / < ± 0.2 aterials (wetted parts) - PE3000, PE3001, PE3002... V4A (1.4404); Keramik; EPD - PE3003...PE3009, PE3029. stainless steel (31612); ceramics (99.9 % Al2 O3); EPD Housing material...stainless steel (30415); stainless steel (31612); PC (akrolon); PBT (Pocan); PEI; FP (Viton); PTFE 2) Protection... IP 67 III Insulation resistance [Ω]... > 100 (500 V DC) hock resistance [g]... 50 (DIN / IEC 68-2-27, 11ms) Vibration resistance [g]... 20 (DIN / IEC 68-2-6, 10-2000 Hz) witching cycles min.... 100 million) Operating temperature [ C]... -20...80 (UB < 32 V) / -20...60 (UB > 32 V) edium temperature [ C]... -25... +80 torage temperature[ C] -40... +100 EC EN 61000-4-2 ED:...4 / 8 KV EN 61000-4-3 HF radiated:... 10 V/m EN 61000-4-4 Burst:...2 KV EN 61000-4-5 urge:...0.5 / 1 KV EN 61000-4-6 HF conducted:... 10 V 1) to EN50178, ELV, PELV 2) in addition PTFE for PE3003...PE3009, PE3029 BFL = Best Fit traight Line / L = Limit Value etting UK 15

12.1 etting ranges P1 rp1 ΔP min max min max PE3029 PE3009 PE3006 PE3004 PE3003 PE3002 PE3001 PE3000 ΔP = increment 16 bar 4 400 2 398 2 PI 60 5790 30 5760 30 Pa 0.4 40.0 0.2 39.8 0.2 bar 2 250 1 249 1 PI 40 3620 20 3600 20 Pa 0.2 25.0 0.1 24.9 0.1 bar 1.0 100.0 0.5 99.5 0.5 PI 20 1450 10 1440 10 Pa 0.10 10.00 0.05 9.95 0.05 bar 0.2 25.0 0.1 24.9 0.1 PI 4 362 2 360 2 Pa 0.02 2.50 0.01 2.49 0.01 bar -0.90 10.00-0.95 9.95 0.05 PI -12 145-13 144 1 Pa -0.090 1.000-0.095 0.995 0.005 bar 0.02 2.50 0.01 2.49 0.01 PI 0.4 36.2 0.2 36.0 0.2 kpa 2 250 1 249 1 mbar -970 1000-980 990 10 PI -14.0 14.4-14.2 14.2 0.2 kpa -97.0 100.0-98.0 99.0 1.0 inhg -28.8 29.4-29.1 29.1 0.3 mbar -990 0-995 -5 5 PI -14.3 0.0-14.4-0.1 0.1 kpa -99.0 0.0-99.5-0.5 0.5 inhg -29.2 0.0-29.3-0.2 0.1

13 Factory setting P1 rp1 OU1 OU2 Factory setting 25% VR* 23% VR* Hno d1 0.0 dr1 0.0 dap 6 di Uni I d2 bar / mbar User setting * = the indicated percentage of the final value of the measuring range (VR) of the corresponding sensor in bar / mbar is set. UK ore information at www.ifm.com 17