OpenAir Electronic Damper Actuator GDE/GLB Rotary Non-spring Return Document No. 9-67 EA678R a b e d c f a. Actuator b. Position indicator c. Mounting bracket d. Mounting screws e. 4 mm hex key f. Shaft insert for use with /8-inch (8- mm) shafts Product Description Steps for direct-coupled mounting of the OpenAir GDE/GLB Series non-spring return rotary electronic damper actuator. Figure. Parts of the GDE/GLB Rotary Actuator. Instructions WARNING: Do not open the actuator. Product Numbers GDE.U GDE.U/B (4 pk) GDE.P GDE.P/B (4 pk) GDE.Q/B 6-ft cable ( pk) GDE.P GDE6.P GDE6.P GDE6.P/B (4 pk) GDE6.P GDE64.P GDE66.P GLB.P GLB.P GLB6.P GLB6.P GLB6.P GLB64.P GLB66.P NOTE: Place the actuator on the damper shaft so that the front of the actuator is accessible. The label is on the front side.. Determine whether the damper blades will rotate clockwise or counterclockwise to open. See Figure.. If the blades will rotate counterclockwise, slide the manual override switch to manual, and move the adjustment lever to the right. Return the switch to automatic. See Figure 9. Required Tools 4 mm hex wrench 4 mm (5/-inch) drill bit and drill Small flat-blade screwdriver Marker or pencil Estimated Installation Time minutes Warning/Caution Notations WARNING : Personal injury/loss of life may occur if you do not follow a procedure as specified. Equipment damage or loss of data may occur if you do not follow a procedure as specified. To mount a (modulating) GDE/GLB6x, set the Dual In-line Package (DIP) switches to the required positions.. To access the DIP switches, raise the tab on the lower left side of the actuator. See Figure. The factory setting is clockwise (middle switch), with a direct-acting feedback signal (right switch).. Close the tab over the DIP switches. To mount a (-positon) GDE/GLBx for counterclockwise rotation, follow the Counterclockwise Damper Rotation instructions located in the Wiring Diagrams section when wiring the actuator to the controller. Item Number: 9-67, Rev. DA Page of 7
Document No. 9-67 CLOCKWISE TO OPEN "" COUNTER CLOCKWISE TO OPEN. A /8-inch shaft adapter is provided in actuator package.. Hold the shaft insert so that the raised tabs are inserted last when placing the insert into the back of the actuator.. Proceed to Figure 6. When using a 5/8-inch shaft: EA68R only for: GDE6...P GLB6...P MODULATING only for: GDE6...P GLB6...P MODULATING Figure. Setting the Direction of Rotation. NOTE: For DIP switch setting options, see the Technical Instructions EA GDE/GLB- (55-87P5). Mounting and Installation NOTE: The GDE/GLB actuator comes with a factory installed /-inch shaft guide. If shaft size is /-inch, proceed with Figure 6. EAR Figure 5. 5/8 Ø inch shaft.. Remove factory installed /-inch guide. See Figure.. Mount actuator to shaft per Figure 6. When using a /8-inch shaft: Remove factory installed /-inch guide. See Figure. EA999R Figure. Removing /-inch Ø shaft guide for /8-in or 5/8-in shaft. EA5R Figure 6. Mounting Actuator to Damper Shaft. f 4 mm 6- lb-in (7- Nm) Torque 5 b EA679R Mounting GDE/GLB on ~ /8-inch 8... mm shafts 4 Figure 4. /8 Ø inch shaft, see Figure Item f. EA5R Figure 7. Installing the Position Indicator (b). Page of 7
Document No. 9-67 CENTER THE MOUNTING BRACKET IN THE SLOT THESE HOLES FOR USE WITH ACCESSORY KITS ONLY. DO NOT USE IN THE INSTALLATION OF DIRECT-COUPLED APPLICATIONS The auxiliary switch setting shafts rotate with the actuator. NOTE: The scale is valid only when the actuator is in the "" position on clockwise motion. / / 4 mm 5/ in. A B EA786R4 c d Figure 8. Attaching the Mounting Bracket. Manual Override To move the damper blades and lock the position with no power present, do the following:. Slide the red manual override knob toward the back of the actuator. See figure 9.. Make adjustments to the damper position.. Slide the red manual override knob toward the front of the actuator. Once power is restored, the actuator returns to automated control. ADJUSTMENT LEVER d EA66R 8 7 6 5 AUX SWITCH ADJUSTMENT Figure. Auxiliary Switch Setting Dial. Mechanical Range Adjustment EA55R 4 mm EA56R < Figure. Moving the Mechanical Range Stop.. Loosen the stop set screw.. Move it along the track to the desired position, and fasten it in place. PLR AUTO MANUAL Figure 9. Manual Override. Mechanical Range Limitation and Self adapt Feature. To use the entire to V input signal to control the adjusted range, raise the tab located on the lower left-hand side of the actuator and locate the DIP switches. See Figure. Dual Auxiliary Switch Setting For GDE/GLB 6x, GDE/GLB64x and GDE/GLB66x only. Factory setting: A = 5 B = 85 Use a flat-blade screwdriver to adjust the A switch. The long arm of the points to the setting. Manually turn the red ring of the B switch. The narrower tab on the ring points to the setting. See Figure.. Set the self-adapt DIP switch to (ON).. Close the tab over the DIP switches. For example, if you set the locking screw at 7 and turn the self-adapt switch ON, a 5V input signal will drive the damper to 5 (5% of its adjusted range). Page of 7
Document No. 9-67 EA8R Figure. Self-adapt Switch in the On Position. Factory setting (OFF) When turning the self-adaptive feature on, or after software reset with the feature on, the actuator will enter a five-minute calibration cycle as the actuator adjusts to the rotation limits of the system. The software reset happens after power on, or may be caused by electrostatic discharge (ESD) at levels of kv and above. Slope (span) and Offset adjustment For GDE/GLB6x and GDE/GLB64x only Factory setting: Slope (span) ΔU Offset Uo = Use a flat-blade screwdriver to make adjustments. The long arm of the points to the setting. EA6R Ys Uo U V SLOPE, U 4 6 OFFSET, Uo 5 4 Figure. Wiring All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class transformers. Do not use autotransformers. Determine the supply transformer rating by summing total VA of all actuators used. It is recommended that one transformer power no more than actuators. WARNING: Installations requiring Conformance All wiring for CE rated actuators must only be separated extra low voltage (SELV) or protective extra low voltage (PELV) per HD84-4-4. Use safety-isolating transformers (Class III transformer) per EN 6558. They must be rated for % duty cycle. Overcurrent protection for supply lines is maximum A. Wiring Diagrams GDE/GLBx Counterclockwise Damper Rotation of GDE/GLBx If the damper blades turn counterclockwise to open (CCW), reverse the 6 (violet) and 7 (orange) wires at the controller. Do not wire different types of actuators (such as GBB or GIB actuators) in parallel with these models. NOTE: (For GDE/GLB floating control actuator series only) To prolong actuator life, use a controller and/or software that provide a time-out function. This function removes the actuator drive signal after the signal has been on for a predefined time. Page 4 of 7
Document No. 9-67 GDE/GLBx, Continued Each wire has the standard symbol printed on it. See Table. 4 Vac Power Supply Floating Control. 6 7 P P P S S4 Standard Symbol Table. -position Control 4 Vac. Function Terminal Designation Color Supply (SP) G Red 6 Control signal clockwise Y Violet 7 Control signal Y Orange counterclockwise EA8R M NEUT 4 Vac A S S 7 (ORANGE) 6 (VIOLET) (RED) EARTH GROUND ISOLATING CLASS TRANSFORMER FOR 4 Vac POWER : SAFETY ISOLATING TRANSFORMER PER EN 674 B S5 S6 S Switch A Common Q Gray/red S Switch A N.C. Q Gray/blue S Switch A N.O. Q4 Gray/pink S4 Switch B Common Q Black/red S5 Switch B N.C. Q Black/blue S6 Switch B N.O. Q4 Black/pink P Feedback Potentiometer a White/red to % P - P P Feedback Potentiometer b White/blue Common P Feedback Potentiometer c White/pink to % P - P EA65R Vac Figure 4. Floating Control. Each wire has the standard symbol printed on it. See Table. Standard Symbol Table. Modulating Control. Terminal Designation GDE/GLB6x Function 4 Vac Power Supply, Modulating Control Supply (SP) G Red Color 8 M Neutral (SN) G Black 8 to V input signal Y Gray 9 Output for to Vdc position indication U Pink EA9R Factory installed options S Switch A Common Q Black S Switch A N.C. Q Black S Switch A N.O. Q4 Black S4 Switch B Common Q Black S5 Switch B N.C. Q Black S6 Switch B N.O. Q4 Black Figure 5. to Vdc Modulating Control. Page 5 of 7
Document No. 9-67 Retrofit Wiring Modulating Control ( to Vdc) Siemens GDE Series GLB Series Belimo LMB Series NMB Series Honeywell MN755 Series MN75 Series* Johnson M94 Series M99 Series* Function Color Number Color Number Color Number Color Number Supply 4V Red Red Red Red Common Black Black Black Black () to Vdc Input Gray 8 White Brown Gray () to Vdc Feedback Pink 9 Orange 5 Blue 5 Orange 4 NOTE: MN75 Series is not available precabled. Numbers listed associate with terminal positions. M99 Series is not available precabled. Numbers listed associate with terminal positions. Floating Control Siemens GDE Series GLB Series Belimo LMB Series NMB Series Honeywell MN65 Series MN6 Series* Johnson M94 Series M99 Series* Function Color Number Color Number Color Number Color Number Common Red Black Black Black 4V CW Violet 6 Red Red Red 4V CCW Orange 7 White White 4 Orange NOTE: MN6 Series is not available precabled. Numbers listed associate with terminal positions. M99 Series is not available precabled. Numbers listed associate with terminal positions. References EA GDE/GLB- 55-87P5 OpenAir Electronic Damper Actuators GDE/GLB Series Non-spring Return Rotary 4 Vac Modulating Control EA GDE/GLB- 55-88P5 OpenAir Electronic Damper Actuators GDE/GLB Series Non-spring Return Rotary 4 Vac Three-Position Control Page 6 of 7
Document No. 9-67 Dimensions 7/6 () min. 4 inch mm / (.8) / () 5/ () min. /4 inch 6 mm min. 8 inch mm 5-7/6 (7) -7/6 (87) 6-5/8 (68) 7-/6 (8) 5/6 (94) -/8 (6) min. -/8 inch 6 mm 5/ (4) EA5R min. inch 5 mm min. /8 inch mm /6 () EA5R -/4 (7) Figure 6. Dimensions of the OpenAir GDE/GLB Actuator and Mounting Bracket. Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. OpenAir is a trademark of Siemens Schweiz, AG. Product or company names mentioned herein may be the trademarks of their respective owners. Building Technologies Division Deerfield Parkway Buffalo Grove, IL 689 USA + 847-5- Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@siemens.com Document No. 9-67 Printed in the USA Page 7 of 7