FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

Similar documents
Liebert. AFC from 500 to 1700 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert. EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

Liebert. AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability CERTIFIED HVAC-HYGIENE.

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

SUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems

Liebert AFC from 500 to 1450 kw. The Adiabatic Freecooling Solution with Top-Tier Availability

Liebert. PCW from 25 to 220 kw. Chilled Water Units Optimizing Data Center Efficiency

Liebert. DCL up to 35 kw. Modular Rack Cooling

Liebert. PDX from 15 to 165 kw. Direct Expansion Solution for Small and Medium Data Centers

Liebert. DCL up to 35 kw. Modular Rack Cooling

PEX+ High Efficiency, Low Operating Cost Precision Solution for Data Centers

Liebert. HPC-S Free Cooling Chiller Designed for the Efficient Cooling of Small Data Centers

Liebert HPC. Freecooling Scroll Chillers for the Efficient Cooling of Data Centers

CRITICAL INFRASTRUCTURE ASSESSMENTS

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

Liebert DCW CATALOGUE

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

Liebert. DSE Thermal Management System Free Cooling Economization Without Using Water

Efficiency of Data Center cooling

Rack cooling solutions for high density racks management, from 10 to 75 kw

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Liebert PDX from 15 to 120 kw

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Liebert PDX from 15 to 120 kw

DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

Liebert Economizer Cooling Solutions Reduce Cooling Costs by up to 50% Without Compromising Reliability

Why would you want to use outdoor air for data center cooling?

Welcome Association of Energy Engineers to the Microsoft Technology Center

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Liebert. icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

Precision Cooling Mission Critical Air Handling Units

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Liebert DCW Family Chilled Water-Based High Density Cooling For The Data Center. Precision Cooling For Business-Critical Continuity

IT Air Conditioning Units

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

Liebert DSE Precision Cooling System Industry-best efficiency. Increased capacity. Ensured availability. EFFICIENCY. CAPACITY. AVAILABILITY.

Google s Green Data Centers: Network POP Case Study

VERTIV SERVICE CAPABILITY

Liebert. CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Liebert PDX. The Cooling Solution for Small and Medium Data Centers. Digital Scroll. Part Load. Competent Partner Efficiency

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

Data Center Energy Savings By the numbers

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

MSYS 4480 AC Systems Winter 2015

Ecoflair Air Economizers

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

Liebert PCW. Cool the Cloud

2017 EMEA Data Centre Cooling Solution Product Leadership Award

CASE STUDIES ENERGY EFFICIENT DATA CENTRES

NG DataCenters. Paolo Caturegli Maurizio Davini

Liebert. APM from 30 to 300 kw. The Compact Row Based UPS With FlexPower Technology

CLIMATE. CUSTOMIZED. CyberHandler2 from 30KW to 520 KW. The indirect evaporative free-cooling Air Handling Unit

PROCESS & DATA CENTER COOLING. How and Why To Prepare For What s To Come JOHN MORRIS REGIONAL DIRECTOR OF SALES

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Total Modular Data Centre Solutions

Aquaflair. BREC/F and BCEC/F kw

Retro-Commissioning Report

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER

Case Study: The design of a modern data centre Jeffrey Brindle Technical Director, HP Critical Facilities Services

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Five Best Practices for Increasing Efficiency, Availability and Capacity: The Enterprise Data Center Design Guide

Introducing the Heat Wheel to the Data Center

Indirect Adiabatic and Evaporative Data Center Cooling

Liebert HPC. Data Center Freecooling Chiller with 100% Compressor Back Up

HIGH DENSITY RACK COOLING CHOICES

Indirect Adiabatic and Evaporative Data Centre Cooling

Liebert : The Right Cooling For IT Environments

IEC DATA CENTRE INDIRECT EVAPORATIVE COOLING SYSTEM

Rack & Enclosure Systems

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

VERTIV LIFE SERVICES. Remote Diagnostic and Preventive Monitoring

SmartCabinet Intelligent, Integrated Containment for IT Infrastructure

Scalable, Secure. Jason Rylands

Liebert. PDX and PCW Compact Perimeter Cooling Solutions

Running Your Data Center Under Ideal Temperature Conditions

Switch to Perfection

Saving Water and Operating Costs at NREL s HPC Data Center

SMARTAISLE Intelligent, Integrated Infrastructure for the Data Center

Trading TCO for PUE? A Romonet White Paper: Part I

Planning a Green Datacenter

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

DATA CENTER AIR HANDLING COOLING SOLUTIONS

Munters Data Center Cooling Solutions. Simon Young & Craig MacFadyen Munters Data Centers

2016 COOLING THE EDGE SURVEY. Conducted by Vertiv Publication Date: August 30, 2016

Next Generation Cooling

Data Center Energy and Cost Saving Evaluation

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

Knürr CoolAdd The universal retrofit solution against overheating in server racks. Rack & Enclosure Systems

High Efficient Data Center Cooling

Energy Efficiency Solutions for Your Data Center

Thermal management. Thermal management

Reducing Data Center Cooling Costs through Airflow Containment

New Design Strategies for Energy Saving. Intelligent free-cooling

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Transcription:

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER Applications in Diverse Climates within Europe, Middle East and Africa

Freecooling, Evaporative and Adiabatic Cooling Technologies in Data Center Applications Just a few years ago, the standard working temperature of a data center white space was approximately 22 C. Today, it is quite normal to have data centers running between 24-27 C in front of the servers, as confirmed by the American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE), who expanded its data center operating temperature guidelines. The data center environment is getting hotter and data center management has evolved accordingly to incorporate more power and higher temperatures. Data center designs, in accordance with ASHRAE guidelines, have thus accepted to move to the upper limit of the recommended envelope, and in some cases, even to the allowable ranges (A1-A4), allowing data center managers and manufacturers to be creative with cooling solutions. One of the most efficient solutions that have recently been introduced is adiabatic and evaporative cooling: an ancient technique brought into the 21 st century. 1% 9% 8% 7% 6% 5% 4% 3 3% 25 2 2% Absolute Humidity (g/kg) in the Data Center 15 1 5-1 -5 5 1 15 2 25 3 35 4 45 5 55 Temperature ( C) in the Data Center 24 ASHRAE Recommended 211 ASHRAE Recommended A1 A2 A3 A4 1% Using Freecooling Technology in Europe, Middle East and Africa (EMEA) Figure 1. ASHRAE guidelines The traditional cooling approach considers open aisle architectures with return air temperatures to cooling units between 22-26 C and supply air temperatures to the data center between 1-14 C to be considered standard. With the use of intelligent air distribution management to the servers, data center designers and facility managers can increase chilled water temperatures from the standard 7-12 C, to 2-26 C. As a result of the Vertiv SmartAisle cold aisle containment solution, the servers exact cooling and airflow needs are met, thus investing only necessary kilowatts in targeted cooling. The Vertiv SmartAisle solution increases space efficiency and provides uniform and predictable temperature to all IT equipment, directly controlling cold aisle temperature and humidity. Combined with the right chiller, such as the Liebert HPC freecooling chiller or the Liebert AFC adiabatic freecooling chiller, the benefits are even greater: yhigher capacity at smaller footprint ysignificant energy savings as a result of the freecooling usage for a significant number of hours per year ylow noise operation. In this paper, we will investigate the impact of using freecooling technologies with and without adiabatic and evaporative technologies in major EMEA cities. 2

Introducing Adiabatic and Evaporative Cooling Technologies How Adiabatic and Evaporative Cooling Works By using an ancient process with a heritage that can be traced back to the Roman Empire, adiabatic/evaporative cooling is a process of reducing air temperature as a result of water evaporation in the air. Over 2, years ago, the system was used to lower the temperature in a hot room by spraying water into the air or on the floor, which has a cooling effect on the area as the water evaporates. Today, adiabatic/evaporative cooling uses the principles of the ancient system with the benefit of 21 st century technology within the category of thermal management units. The Benefits of Adiabatic Cooling Applied to Freecooling Chillers The ancient adiabatic cooling principle can be used today to significantly reduce data center energy bills. One of the most interesting possible applications is the enhancement of a freecooling chiller s efficiency, obtained by humidifying ambient air going into the heat rejection coils (both the condensing and freecooling ones). The ambient air is humidified and cooled down, without incurring in any additional energy cost, by passing through wet pads. Air is thus delivered at a lower temperature to the freecooling and the condensing coils, thus achieving respectively a higher freecooling capacity and a more efficient compressor operation. With a chiller operating at full load, the following annual energy savings can be expected when adopting this system: ycompared to a freecooling chiller, a saving of 25-35% Liebert AFC - The First Integrated Adiabatic Freecooling Chiller in the Market As a result of these smart applications, new generation data centers will be able to provide unparalleled benefits in terms of cost saving, reliability and cooling availability. A freecooling chiller with an integrated adiabatic system design in one single unit is, in fact, able to guarantee 1% cooling even in the worst environmental conditions of ambient temperatures peaks. This also holds true in the case of water shortages, where back-up compressors will provide full capacity whenever needed. Another significant advantage of such unit is its ability to retrofit existing thermal management systems or existing chilled water type designs, without the need to re-design the entire cooling infrastructure. It is important to note that the Liebert AFC reaches its peak performance when operated in conjunction with floor mount units such as Liebert PCW and Vertiv SmartAisle containment, thus granting superior freecooling and energy savings. So far, cutting-edge data centers have been preferably located in cold climatic areas, in order to leverage the cold ambient air, thus increasing the use of freecooling and consequently improving annual efficiency. For example, the best mechanical power usage effectiveness (ppue) value that can be achieved by a highly efficient freecooling system in Northern Europe (i.e. a chilled water system in Oslo, working between 2-15 C water temperatures) is in the range of 1.11-1.15. ycompared to a standard air-cooled chiller, a saving of 6-65%. In cases of systems with redundancy and part load conditions, the energy savings can be even higher. The adiabatic freecooling chiller thus offers new levels of efficiency, allowing data center managers to reduce overheads. 3

In warm countries, such as the Mediterranean area, the use of freecooling is traditionally very limited and compressors cover most of the cooling load, in terms of hours per year. For this reason, data center managers conventionally conceived freecooling systems as being less attractive compared to a standard air-cooled chiller system; the latter achieving ppue values of 1.2-1.3. The recent trend, however, has seen freecooling become increasingly convenient, as a result of an increase in chilled water temperatures alongside the increase in data center air temperatures. Figure 2. Adiabatic cooling allows for ppue values as low as 1.1 even in southern EMEA countries. An adiabatic wet pad system is able to decrease the temperature of the air entering the freecooling coils of 5-1 C (depending upon weather conditions), thus allowing freecooling to operate at even higher ambient temperatures. This system, moreover, delivers even greater benefits to the data centers working at partial loads; as a result of a considerable adiabatic freecooling capacity which covers the load almost all year round. The compressors cooling back-up is called on duty only in case of simultaneous peaks both in data center loads and external ambient temperatures: but this happens only for a very limited amount of hours per year. Figure 3. Liebert AFC adiabatic pads 4

If we consider two different European cities, such as London and Madrid, as shown in Figure 4, it is clear that, at full data center load, Liebert AFC can run in hybrid mode (adiabatic freecooling plus backup compressors) at almost 1% of the time. Even more impressive is that even in cities such as Dubai, which register a higher average ambient temperature, the hybrid mode is active for 5% of the time. Hours/Year 5 4 3 2 1 FC + AD FC AD FC+DX AD + DX 81% 19% % -1 1 2 3 4 5 Ambient Temperature ( C) LONDON Hours/Year 3 2 1 FC + AD FC AD FC+DX AD + DX 74% 26% <.5% -1 1 2 3 5 Ambient Temperature ( C) MADRID Hours/Year 5 4 3 2 AD FC + Hybrid 5% DUBAI 1 AD FC AD FC+DX AD + DX 6% 44% 5% 1 2 3 4 5 Ambient Temperature ( C) FC AD FC AD FC DX AD DX FREECOOLING: cooling without compressors ADIABATIC FREECOLING: the adiabatic system extends freecoling operation to higher ambient temperatures HYBRID COOLING: adiabatic freecooling with backup compressor cooling ADIABATIC MECHANICAL COOLING: the adiabatic system increases the efficency of mechanical cooling mode Figure 4. Liebert AFC annual operating modes in London, Madrid, Dubai, 1 MW Tier 4 data center at full load (chillers at 5% load) Adiabatic ON for ambient temperatures >8 C 5

The benefits are significant also when we examine the mechanical power usage effectiveness obtained using our Liebert AFC solution. If we consider a legacy solution, including a standard chilled water floor mount unit and an air-cooled chiller (units with efficiency at standard market levels), the ppue obtained is of 1.21 in London and 1.31 in Dubai. If we consider the same data center requirements, but with Liebert PCW and Liebert AFC (working with designed chilled water temperatures of 26-2 C and a data center air supply of 22 C) the ppue obtained is of 1.6 in London and 1.18 in Dubai, which are both significantly lower values compared to those obtained with the legacy solution. In these units, in fact, the water consumption has a very low impact in terms of costs when compared to the energy savings achieved. This is possible as a result of an optimized design and advanced control logic specifically conceived for this new product. The electronic control predictively calculates the balance between water and energy costs and implements the combination which optimizes operating costs. CITY AIR-COOLED CHILLER STEP 1 FREECOOLING CHILLER STEP 2 FREECOOLING CHILLER STEP 3 ADIABATIC FREECOOLING CHILLER CW 12-7 C CW 15-1 C CW 26-2 C CW 26-2 C London ppue ppue ppue ppue 1.21 1.17 1.9 1.6 Madrid ppue ppue ppue ppue 1.22 1.18 1.12 1.7 Dubai ppue ppue ppue ppue 1.31 1.32 1.24 1.18 Figure 5. ppue values in different cities. These values consider a chilled water system composed of CRACs, pumps and different chiller technologies. 6

The Benefits of Evaporative Cooling Applied to Indirect Evaporative Freecooling Units The Liebert EFC is Vertiv s indirect evaporative freecooling unit which acts as a complementary unit to the Liebert AFC adiabatic freecooling chiller. Both use the adiabatic/evaporative cooling technology, but the former also includes indirect air-to-air heat exchange. The Liebert EFC is capable of reducing air temperatures by leveraging the evaporative cooling principle through the evaporation of pressurized water which cools the surrounding air. The highly efficient evaporative system sprays water inside the unit, as well as onto the heat exchanger to enable cooling even at high ambient air temperatures, without the need for mechanical cooling. The evaporative principle uses air to absorb water that is sprayed at high pressure. Water evaporation thus removes heat from the air and cools the outside air temperature. Outside air consequently transitions from dry bulb temperature to wet bulb temperature (Figure 6 shows the transition from 35 C to 2 C). The use of evaporative cooling allows freecooling operation to be maximized and compressor-related cooling to be reduced to a minimum, thus optimizing operating costs even further. 35 4 45 5 55 1% 9% 8% 7% 6% 5% 4% 3 3% 3 25 2 25 2% 15 2 Absolute Humidity (g/kg) 1 5-5 5 1 15 (35 C DB; 2 C WB) 1% -1-5 5 1 15 2 25 3 35 4 45 5 55 Temperature ( C) Figure 6. The Psychrometric Chart 7

In order to optimize the overall system efficiency, the Liebert EFC unit has been designed to automatically change its operating mode according to the external environment. When the external air is cold enough to allow for freecooling, the unit works in dry operation mode (winter operation mode). Higher ambient temperatures and external humidity determine unit capacity and performance as the evaporative effect is directly associated to the external air capacity in order to absorb water. When the unit operates in environments with a higher temperature and lower relative humidity (summer operating mode), Liebert EFC works in evaporative mode. In climates featuring high levels of humidity, the unit may require the integration of a Direct Expansion (DX) system or the installation of a Chilled Water (CW) coil (DX/CW operation mode). Exhaust External Air Winter DC Hot Return Air DC Supply Air Dry Operation Air-to-Air Heat Exchange Without Spraying Water Externel Air Exhaust External Air Summer DC Hot Return Air DC Supply Air Wet Operation Air-to-Air Heat Exchange Via the Spraying of Water to the External Air Side Externel Air Exhaust External Air Air Optional DC Hot Return Air DC Supply Air DX/CW Integration External Air Is too Hot to Achieve 1% Cooling with Adiabatic, the DX Module Is thus Integrated to Cover the Missing Capacity Externel Air Figure 7. Liebert EFC operating modes 8

While respecting ASHRAE guidelines, the Liebert EFC unit can be installed not only in colder climates, where the unit takes advantage of the dry operating mode, but also in hotter ones (as shown in Figure 8 for Istanbul), where DX operation is reduced to a minimum and used only during extreme temperature peaks that occur throughout the year. This results in a significant reduction in electrical consumption, even at full load (reaching the highest possible savings at partial loads). The cost function, which is the software logic embedded in the control, optimizes running costs (water and electricity), and, according to the external dry bulb and heat load, selects the most convenient working mode (i.e. dry vs. wet). With the same logic, the cost function will also optimize the use of the optional DX mode. ASSUMPTIONS: DATA CENTER 36 C 24 C 1% IT LOAD (N REDUNDANCY OPERATION) Hours per Year 6 55 5 45 4 35 3 25 2 15 1 5-2 -1 1 2 3 4 5 Ambient Air Temperature London 45% dry mode 45% dry or wet mode (cost function) 1% wet mode Hours per Year 6 55 5 45 4 35 3 25 2 15 1 5-2 -1 1 2 3 4 5 Ambient Air Temperature Frankfurt 48% dry mode 36% dry or wet mode (cost function) 16% wet mode Hours per Year 6 55 5 45 4 35 3 25 2 15 1 5-2 -1 1 2 3 4 5 Ambient Air Temperature Istanbul 31% dry mode 33% dry or wet mode (cost function) 34% wet mode 2% wet + DX mode Figure 8. Liebert EFC operating modes in different cities 9

One of Liebert EFC s key differentiators is its state-ofthe-art Vertiv ICOM Control which guarantees water management and energy optimization both at unit and teamwork level. The user-friendly Vertiv ICOM Control collects information from different units key parameters and operating modes (dry, wet and DX/CW) while taking into account water and electricity costs. This allows the control to predictively calculate and implement the combination which optimizes operating costs. Liebert EFC also offers a constant control of data center air via its integrated control logic, ensuring dew point temperature is lower than heat exchanger surface temperature, thus avoiding unnecessary dehumidification which often occurs during extreme winter operation (i.e. temperatures <-2 C). This occurs when the unit s unnecessary internal dehumidification can cause it to exceed ASHRAE recommended minimum humidity levels. The Vertiv SmartAisle control logic, moreover, optimizes internal air volumes and temperatures according to specific server needs and allows Liebert EFC to exactly match the servers airflow needs, ensuring that not even a single watt is wasted in moving or cooling unnecessary air. As a result of these state-of-the-art technologies, both in terms of servers and in thermal management technologies, top efficient data centers today can also be built in warmer climates, thus contributing and leading the way to a significant reduction in global energy consumption. 1

The Thermal Management Product Portfolio With the introduction of the Liebert AFC adiabatic freecooling chiller and the Liebert EFC indirect evaporative cooling unit, Vertiv can offer the solution that better meets any data center need (i.e. maximized availability, reduced total cost of ownership, higher efficiency, lower installation costs, unit modularity or outdoor space limit) independently of the application: ydirect expansion systems: from floor-mount to in the row units able to operate at high return air temperatures suitable for the increased temperatures within which the IT equipment works ychilled water systems: highly efficient chilled water floor mount units and freecooling chillers that maximize freecooling operation all year round yadiabatic chilled water systems: combining adiabatic, freecooling and mechanical cooling technologies in a single unit yindirect evaporative freecooling: indirect air-to-air heat exchange and evaporative cooling technologies in one footprint. DIRECT EXPANSION ADIABATIC CHILLED WATER 1% 9% 8% 7% 6% 5% 4% 3 3% 25 2 2% Absolute Humidity (g/kg) in the Data Center 15 1 5 1% 2 3 4 5 6 7 8 9 1 11 12 13 Temperature ( F) in the Data Center CHILLED WATER EVAPORATIVE Utmost Efficiency at the Data Center System Level with the Vertiv ICOM Control The last remarkable aspect of Vertiv s Thermal Management solutions lie in the innovative Vertiv ICOM Control which exploits the function of a single unit operation as well as multiple units working together (the teamwork mode). This feature is extremely important in order to maximize energy efficiency within a data center environment. In addition to the teamwork mode available in any Thermal Management unit, on Liebert AFC and Liebert EFC, the Vertiv ICOM Control also exploits the management of energy and water by collecting information from the different units key parameters and operating modes while taking into account water and electricity costs. The control predictively calculates and then implements the combination which optimizes operating costs. When considering the entire data center scenario, including indoor and outdoor units, the Vertiv ICOM Control becomes the key driver in terms of delivered efficiency at the data center system level. The software logic, embedded in the control, ensures the perfect coordination of the whole system, thus leading to superior energy savings at the entire data center level. 11

VertivCo.com Vertiv Infrastructure Limited, George Curl Way, Southampton, SO18 2RY, VAT Number: GB188146827 216 Vertiv Co. All rights reserved. Vertiv, the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.