ATEX category II 2 G, Ex zone 1 ATEX category II 1 D, Ex-zone 20 for temperatures up to -25 C SIL2 acc. to IEC 61508 Rectangular, housing DSU35 Plastic, PP-GF30-VO Two outputs for monitoring the position of rotary actuators Mounting on all standard actuators Temperatures up to -40 C DC 2-wire, nom. 8.2 VDC 2 outputs acc. to DIN EN 60947-5-6 (NA- MUR) Type designation Ident no. 1051017 Rated switching distance Sn 4 mm Mounting conditions Non-flush Correction factors St37 = 1; Al = 0.3; stainless steel = 0.7; Ms = 0.4 Repeat accuracy ð 2 % of full scale Temperature drift ð ± 10 % ð ± 20 %, ð -25 C Hysteresis 1 10 % Ambient temperature -40 +70 C For explosion hazardous areas see instruction leaflet Terminal chamber Wiring Diagram Output function 4-wire, NAMUR Valve control Exi (max. 30 V) Switching frequency 0.05 khz Voltage Nom. 8.2 VDC Non-actuated current consumption ï 2.1 ma Actuated current consumption ð 1.2 ma Approval acc. to KEMA 02 ATEX 1090X Functional principle Inductive sensors detect metal objects contactless and wear-free. Dual sensors are especially designed for position detection in rotary actuators. They combine the reliability of non-contact inductive sensors with the flexibility of a modular housing system. Design Dimensions Housing material Active area material Electrical connection Dual sensor for valve monitoring,dsu35 62 x 60 x 35.4 mm Plastic, PP-GF30, Yellow Plastic, PP-GF30, black Terminal chamber Clamping ability ð 2.5 mm 2 Vibration resistance 55 Hz (1 mm) Shock resistance 30 g (11 ms) Protection class IP67 MTTF 2283 years acc. to SN 29500 (Ed. 99) 40 C Packaging unit 1 Switching state Included in delivery 2 LEDs,Yellow/Red 2 cable glands (blue), 1 blanking plug 1 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
2 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Accessories Type code Ident no. Description BTS-DSU35-EB1 6900225 Actuation kit (puck) for dual sensors; end position damped; hole pattern on flange surface 80 x 30 mm and 130 x 30 mm; connection shaft (shaft extension) height 20 mm / Ø max. 30 mm BTS-DSU35-Z01 6900229 Mounting kit dual sensors, for larger rotary actuators: Spacer plate and snap ring max. Ø 65 mm; hole pattern on flange surface 30 x 80 mm (30 x 130 mm); connection shaft (shaft extension) height 30 mm / Ø max. 30 mm BTS-DSU35-Z02 6900230 Mounting kit dual sensors, for larger rotary actuators: Ø disc and snap ring max. 65 mm; hole pattern on flange surface 30 x 80 mm (30 x 130 mm); connection shaft (shaft extension) height 20 (30) mm / Ø max. 40 mm BTS-DSU35-Z03 6900231 Mounting kit dual sensors, for larger rotary actuators: Ø disc and snap ring max.110 mm; hole pattern on flange surface 30 x 130 mm; connection shaft (shaft extension) height 30 mm / Ø max. 70 mm BTS-DSU35-Z07 6900403 Mounting kit dual sensors, for larger rotary actuators: Ø disc and snap ring max.110 mm; hole pattern on flange surface 30 x 130 mm; connection shaft (shaft extension) height 50 mm / Ø max. 75 mm 3 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Accessories Type code Ident no. Description BTS-DSU35-EBE3 6901070 Actuation kit (puck) for dual sensors; end position damped; "open" and "closed" switchpoint adjustable; hole pattern on flange surface 80 x 30 mm and 130 x 30 mm; connection shaft (shaft extension) height 20 / Ø max. 30 mm BTS-DSU35-EU2 6900455 Actuation kit (puck) for dual sensors; end position undamped for clockwise and counter-clockwise drives; hole pattern on flange surface 80 x 30 mm and 130 x 30 mm; connection shaft (shaft stud) height 20 (30) mm / Ø max. 30 mm IMX12-DI01-2S-2T-0/ 24VDC 7580020 Isolating switching amplifier, 2-channel; SIL2 acc. to IEC 61508; Ex-proof version; 2 transistor outputs; input Namur signal; ON/OFF switchable monitoring of wire-break and short-circuit; toggle between NO/NC mode; signal doubling; removable screw terminals; 12.5 mm wide; 24 VDC power supply 4 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com
Operating manual Intended use This device fulfills the directive 2014/34/EC and is suited for use in explosion hazardous areas according to EN 60079-0:2012 + A11 and EN 60079-11:2012. Further it is suited for use in safety-related systems, including SIL2 as per IEC 61508. In order to ensure correct operation to the intended purpose it is required to observe the national regulations and directives. For use in explosion hazardous areas conform to classification II 2 G and II 1 D (Group II, Category 2 G, electrical equipment for gaseous atmospheres and category 1 D, electrical equipment for dust atmospheres). Marking (see device or technical data sheet) É II 2 G and Ex ia IIC T6 Gb and É II 1 D Ex ia IIIC T95 C Da acc. to EN 60079-0, -11 Local admissible ambient temperature ATEX category II 2 G electrical equipment -40 +70 C, category II 1 D -25 +70 C. The corresponding temperature classes are provided in the ATEX type-examination certificate. Installation/Commissioning These devices may only be installed, connected and operated by trained and qualified staff. Qualified staff must have knowledge of protection classes, directives and regulations concerning electrical equipment designed for use in explosion hazardous areas. Please verify that the classification and the marking on the device comply with the actual application conditions. This device is only suited for connection to approved Exi circuits according to EN 60079-0 and EN 60079-11. Please observe the maximum admissible electrical values. After connection to other circuits the sensor may no longer be used in Exi installations. When interconnected to (associated) electrical equipment, it is required to perform the "Proof of intrinsic safety" (EN60079-14). Attention! When used in safety systems, all content of the security manual must be observed. Installation and mounting instructions Avoid static charging of cables and plastic devices. Please only clean the device with a damp cloth. Do not install the device in a dust flow and avoid build-up of dust deposits on the device. If the devices and the cable could be subject to mechanical damage, they must be protected accordingly. They must also be shielded against strong electro-magnetic fields. The pin configuration and the electrical specifications can be taken from the device marking or the technical data sheet. In order to avoid contamination of the device, please remove possible blanking plugs of the cable glands or connectors only shortly before inserting the cable or opening the cable socket. Special conditions for safe operation avoid static charging Service/Maintenance Repairs are not possible. The approval expires if the device is repaired or modified by a person other than the manufacturer. The most important data from the approval are listed. 5 / 5 Hans Turck GmbH & Co.KG ñ D-45472 Mülheim an der Ruhr ñ Witzlebenstraße 7 ñ Tel. 0208 4952-0 ñ Fax 0208 4952-264 ñ more@turck.com ñ www.turck.com