TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Super universal modules

Resistance measuring module

Digital input modules

Power supply module, bus connection module

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

TXM1.8RB. TX-I/O Blinds module

Island bus expansion module

Web interface BACnet/IP

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Extension module for lighting control

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

BACnet/IP Web Interface

Room automation station

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Room unit with PPS2 interface

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Room unit with PPS2 interface

9283P01. Extension module. Integration of existing PT-I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Communication module to connect M-bus devices to POL6xx.xxx controllers.

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP

CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. POWER SUPPLY RELAY OUTPUTS. Power supply. 4.

Automation stations modular series

Room Temperature Controller

Heating Circuit Controller

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

Rotary version, three-position control

TX-I/O Product Range. Features. Description. Document No January 24, 2007

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Airflow Pressure Sensor

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

POL635.XX/XXX POL636.XX/XXX POL638.XX/XXX POL638.70/XXX

Room unit with PPS2 interface

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

ERF910. RF Repeater. Synco living

Non-communicating room controllers

Electromotoric actuators

Air damper actuators

Room unit with PPS2 interface

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018

PXM20-E. Operator unit BACnet auf Ethernet/IP DESIGO PX

PHOENIX CONTACT Features

Interface converter for VAV compact controllers

Semi flush-mounted room temperature controllers with LCD

Fast running actuators for air dampers

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

Universal Controller

Use. Functions. OpenAir TM. Linear version, modulating, AC 24 V

TX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007

SEH62.1. Digital Time Switch

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

Product and functional description

Semi flush-mounted room temperature controllers with LCD

Non-communicating room controllers

Heating Circuit Controller

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Signal Doublers. VariTrans A 20300

Extension module for graphic Web functions for one automation station

Semi Flush-mount Room Temperature Controllers with LCD

Immersion Temperature Sensors

AIAS. Technical description

Product and functional description

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

MINI MCR-SL-PT100-UI-200

QMX3.P30 QMX3.P70 QMX3.P02 QMX3.P34 QMX3.P74 QMX3.P37. Wall-mounted sensors and room operator units for KNX PL-Link, KNX S-mode and KNX LTE-Mode

Extension module for Web functions generic

TM3TI8T module TM3-8 inputs temperature

Handheld Tool for VAV compact and modular controllers

Room controller. For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode)

Rotary actuators for ball valves

PanelView Plus/VersaView CE Terminals and Display Modules

Room automation stations

Status display unit with P-bus connection

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Room Temperature Controllers

Measuring transducers MI4x0 series Programmable transducers for RTD sensors MI450

Temperature controller Ducted systems

Room Temperature Controller

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Automation stations compact model

RM35LM33MW liquid level control relay RM35-L V AC/DC

Electrical Actuators

TM3TI4 module TM3-4 inputs temperature

Compact room automation stations, BACnet/IP, AC 230 V

02/11/2015

Transcription:

8 173 TX-I/O niversal modules TXM1.8 TXM1.8-ML Two fully compatible versions: TXM1.8: 8 inputs/outputs with LED signal / fault indication TXM1.8-ML: As TXM1.8, but with additional local override facility with LCD display (LO/ID to ISO 16 484-2) 8 universal I/O points, individually configurable as Digital input: maintained contact, pulse or counter Analog input: sensor, 0..10 Analog output: 0..10 Compact DIN format, small footprint Separate terminal base and plug-in I/O module for convenient handling Self-establishing bus connection for maximum ease of installation Terminal isolation function for fast commissioning I/O module replaceable in seconds, without rewiring and without affecting the full functioning of the remaining I/O modules All terminals are directly on the I/O modules, allowing direct connection of field devices without additional terminal strips. Simple strategy for operation and display I/O status LED for each I/O point; mode of operation (N/C or N/O) and brightness depend on I/O function LEDs and LCD for fast diagnostics Double-sided labels for identification of all I/O points CM2N8173en_05 11 Jun 2010 Building Technologies

Functions The modules support the following I/O functions: Function Signal type Description Status signal D20 D20R olt-free, interrogation (maintained contact), N/O contact olt-free, interrogation (maintained contact), N/C contact Status pulses D20S olt-free, N/O contact, interrogation (pulse) Counter pulses C olt-free, N/O contact, interrogation (pulse) Counting frequency max. 100 Hz (electronic counter) max. 25 Hz (mechanical counter) oltage, resistance and temperature 10 P1K R2K5 DC voltage Resistance Resistance 0... 10 Pt 1000 ohms and resistance transmitter 2500 Ω R1K Ni1K Pt1K 375 Pt1K 385 T1 NTC10 K NTC100 K LG-Ni 1000 ohms LG-Ni 1000 ohms Pt 1000 (SA) Pt 1000 (Europe) PTC NTC 10 K NTC 100 K Proportional output signals Y10S Proportional control output, DC 0... 10, with storage of control value For a detailed description of these functions, please refer to document CA110561, "TX-I/O functions and operation". Compatibility Support of signal types and functions in different building automation and control systems: see TX-I/O Engineering and installation manual, CM110562 Type summary ASN niversal module TXM1.8 niversal module TXM1.8-ML with LCD display and local override Delivery The terminal base and the electronic plug-in unit are interconnected and delivered in the same box. Accessories The available accessories include address keys, label sheets, and spare transparent label holders. Refer to data sheet CM2N8170. 2/10

Technical and mechanical design For a description of the features common to all TX-I/O modules, please refer to the TX-I/O Engineering and installation manual, document CM110562. Indicators and operator controls 19 21 23 24 25 27 29 31 32 33 Connection terminals (No. 1 screwdriver) with test pickup (for 1.8...2 mm pins) and terminal number Signal designation 12 (5) (6) (7) (8) Override status LEDs (yellow) Address key and module status LED LCD panel (TXM1.8-ML only) (1) (2) (3) (4) (5) (6) (7) (8) I/O point numbers Override button (TXM18-ML only) (1) (2) (3) (4) I/O status LEDs (green) 2 4 6 8 10 12 14 16 8173z10 7 15 I/O status LEDs The I/O status LEDs (green) indicate the status of the inputs and outputs (peripheral devices) They are also used for diagnostics Module status LED Address key The module status LED illuminates the transparent address key The LED (green) shows the module status as a whole (as opposed to the status of the I/O points) It is also used for diagnostics The module operates only with the address key inserted The module address is mechanically encoded in the address key When replacing the I/O module, the address key must be swiveled outward. It remains plugged into in the terminal base. 3/10

Local override and LCD display (TXM1.8-ML only) For a detailed description, please refer to document CM110561, "TX-I/O Functions and operation". Override button Override status LED LCD display Warning Pressing an override button in the middle enables or disables the local override Pressing "+" or " " respectively increases or reduces the output value. Only outputs can be overwritten. Any attempt to overwrite an input results in an error indication. The yellow "Override" LED indicates that local override is active The following information is displayed for each I/O point: Configured signal type Symbolic display of process value Information for diagnostics. All safety-relevant functions must be implemented with external solutions The local override must not be used for safety shutdown operations In compliance with the standard (ISO 16 484-2, Section 3.110), the module executes all local overrides directly, without safety precautions or interlocks. Full responsibility lies with the operator. Module labeling The plug-in I/O module has a removable transparent cover (the label holder) for insertion of a label. 2 1 8172z11 Disposal The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 4/10

Engineering, mounting, installation and commissioning Please refer to the following documents Document TX-I/O functions and operation TX-I/O Engineering and installation manual Replacement of legacy modules Number CM110561 CM110562 CM110563 Mounting Permitted orientation The TX-I/O devices can be installed in any orientation: It is important to provide adequate ventilation so that the admissible ambient temperature (max. 50 C) is not exceeded. Technical data Supply (bus connector on side) Operating voltage DC 22.5... 26 Extra low voltage SEL or PEL in accordance with HD384 Max. power consumption TXM1.8 1.5 W TXM1.8-ML 1.8 W (for the sizing of power supplies, see CM110562) Protection All terminals of the modules Against shortcut and incorrect wiring with AC / DC 24 Bus connector on side No protection! Field devices Insulation resistance The of the connected field devices against mains voltage must comply with the requirements for safety extra-low voltage (SEL) or protection by extra-low voltage (PEL) as per HD 384. Measuring cables Cable material Solid or stranded copper wire Cable cross section See manual CM110562 Permitted cable length max. 300 m AC/DC output oltage AC / DC 12... 24 (field supply) Admissible current per module Max. 4 A (total for all 4 terminals) (, Terminals 7, 15, 24, 32) Fuse T 10A, in power supply module/bus connection module 5/10

Digital inputs / counter inputs Digital inputs are not electrically separated from the system electronics. Mechanical contacts must be volt-free. Electronic switches must comply with SEL / PEL standards. Counter inputs faster than 1 Hz that are routed for more than 10 m in the same trunking as analog inputs must be shielded. Contact sensing voltage Contact sensing current Contact resistance with contacts closed Contact resistance with contacts open DC 21.5...25 1.0 ma (initial current 6 ma) Max. 200Ω Min. 50kΩ Min. closing / opening time [ms] including bouncing Max. bounce time [ms] Max. Counting frequency (symmetric) Maintained contact 60 20 Pulse contact 30 10 Mechanical counter 20 10 25 Hz electronic counter..5..0 100 Hz Analog inputs counter memory Correction of line resistance 0... 4.3 x 10 9 (32 bit counter) 1 Ω (calibrated In module) Signal type Range Resolution Resistance Pt 1000 and P1K 0...2500 Ohm 100 mohm resistance transmitter R2K5 0...2500 Ohm 100 mohm Temp. measurement Pt1K 375-50 180 C 10 mk Pt1K 385 1) -50...400 (600) C 1) 20 mk Ni1K 1) -50 150 (180) C 1) 10 mk R1K (LG-Ni 1000) -50...150 C 10 mk T1 1) -50...130 (150) C 1) 10 mk NTC 10K 1) -40...115 C 1) 10 mk (25 C) NTC 100K 1) -40...125 C 1) 10 mk (25 C) 1) 180 C, 600 C, NTC: only with reduced hum injection oltage measurement 10 2) 0...10 1 m 2) In case of open connection: negative voltage 3.1, 0.05 ma (open circuit detection) Analog outputs Signal type Range Resolution Output voltage Y10S 0 10 1 m Output current max. 1 ma Connection terminals Mechanical design Solid conductors Stranded conductors without connector sleeves Stranded conductors with connector sleeves (DIN 46228/1) Screwdriver Rising cage terminals 1 x 0.5 mm 2 to 4mm 2 or 2 x 0,6 mm to 1.5 mm 2 1 x 0.5 mm 2 to 2.5 mm 2 or 2 x 0,6 mm to 1.5 mm 2 1 x 0.25 mm 2 to 2.5 mm 2 or 2 x 0,6 mm to 1.5 mm 2 Slot-headed screws Screwdriver No. 1 with shaft diameter 4.5 mm 0.6 Nm Max. tightening torque Test pickups (test terminals) For pin diameter 1.8 2.0 mm 6/10

Local override (TXM1.8-ML only) Local override / indication device ISO 16 484-2, Section 3.11 Classification to EN 60730 Housing protection standard Ambient conditions Mode of operation of automatic electrical controls Contamination level Mechanical design Protection standard to EN 65029 Front-plate components in DIN cut-out Terminal base Operation Climatic conditions Temperature Humidity Mechanical conditions Operation Climatic conditions Temperature Humidity Mechanical conditions Type 1 2 Protection class III IP30 IP20 To IEC 60721-3-3 Class 3K5 5... 50 C 5 95 % rh Class 3M2 To IEC 60721-3-2 Class 2K3 25 70 C 5 95 % rh Class 2M2 Standards and directives Product standard Automatic electronic controls for household and similar use Electromagnetic compatibility Immunity (domestic & industrial) Emissions (domestic & industrial) CE conformity EMC Directive EN 60730-1 EN 60730-1 EN 60730-1 2004/108/EC C-tick conformity Emissions AS/NZS 61000-6-3 L approbation L 916, L 864 Environmental compatibility The product environmental declaration CM1E8174 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) ISO 14001 (Environment) ISO 9001 (Quality) SN 36350 (Environmentally compatible products) 2002/95/EC (RoHS directive) Color Terminal base and plug-in I/O module RAL 7035 (light gray) Dimensions Housing to DIN 43 880, see "Dimensions" Weight Without / with packaging TXM1.8 179 / 200 g TXM1.8-ML 202 / 223 g 7/10

Connection diagrams (examples) Digital inputs (1) (2) (3) (4) (5) 2 4 6 8 10 12 14 16 19 21 K1 K2 K3 K4 S5 8174z13 K1 K2 K3 K4 S5 niversal module Status contact (N/O) Status contact (N/C) Pulse contact (N/O) Pulse contact (N/C) Electronic switch Terminal layout STOP Counter inputs TXM1.8, TXM1.8-ML I/O point (1) (2) (3) (4) (5) (6) (7) (8) System neutral ( ) 1) 2 6 10 14 19 23 27 31 Input (+) 4 8 12 16 21 25 29 33 Counter inputs faster than 1 Hz that are routed for more than 10 m in the same trunking as analog inputs must be shielded. Analog inputs (1) (2) 2 4 6 8 M B (3) 10 12 B1 B2 R3 B4 B5 niversal module LG-Ni 1000 temperature sensor Pt 1000 temperature sensor Resistance-type sensor Active sensor with external supply External supply must NOT be earthed (earth loop) Active sensor with AC / DC supply B1 B2 R3 (1) (2) 2 4 6 7 8 B4 B5 8173z14 Terminal layout TXM1.8, TXM1.8-ML I/O point (1) (2) (3) (4) (5) (6) (7) (8) Measuring neutral ( ) 1) 2 6 10 14 19 23 27 31 Input (+) 4 8 12 16 21 25 29 33 AC / DC sensor supply voltage 2 Selected from: 7, 15, 24, 32 2)... 8/10

Analog outputs (1) (2) 2 4 6 Y1 7 Y2 8 (3) 10 12 Y3 8173z15 Y1 Y2 Y3 niversal module Actuator with input DC 0..10 General device with input DC 0..10, supplied by module General device with input DC 0..10, supplied externally External supply must NOT be earthed (earth loop) Terminal layout TXM1.8, TXM1.8-ML I/O point (1) (2) (3) (4) (5) (6) (7) (8) System neutral ( ) 1) 2 6 10 14 19 23 27 31 Output (+) 4 8 12 16 21 25 29 33 AC / DC operating voltage 2) Selected from: 7, 15, 24, 32 2) 1) All measuring / system neutral terminals are interconnected, not in the terminal base but in the plug-in I/O module. When this unit is pulled outward (into the "parking" position) there is no connection. The system neutral of a digital input can be connected to any system neutral terminal With analog inputs and outputs, the measuring / system neutral must always be connected to the terminal associated with that I/O point. 2) All AC/DC 24 supply terminals are interconnected (in the I/O module, not in the terminal base). They are protected in the power supply module / bus connection module. For wiring details refer to the TX-I/O Engineering and installation manual, CM110562. 9/10

Dimensions Dimensions in mm 90 67 45 22 44 70 77.5 7.1 98 108 64 3 8172M01 10/10 2007-2010 Siemens Switzerland Ltd Subject to change