3GV M Modbus RTU Register Map

Similar documents
Optidrive VTC Modbus RTU Register Map

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

E2 Modbus RTU Register Map

Optidrive Applications Support Library

Optidrive Applications Support Library

Optidrive Plus 3 GV. Advanced User Guide. Vertical Market Solution : Industrial Washing Machines. Revision 1.00

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 1.10

OPTIDRIVE PLUS 3 GV 3 rd Generation Vector Control AC Variable Speed Drive kW

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Issue 06

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 2.00

1. PRODUCT OVERVIEW GENERAL INFORMATION STANDARDS & EMC ELECTRICAL RATINGS MECHANICAL INSTALLATION...

lnvertek Drives.com ct,ve ELECTRICAL SUPPLIERS LTD

The RS-485 user manual for B800 series communication

Firmware Manual - EC Series Drives

PowerXL DG1 Firmware Release Note

VFA7/VFP7 Parameter List (Ver315)

Compact 2. User Guide (Preliminary) Installation and Operating Instructions. AC Variable Speed Drive kW (1.

AirCare General Purpose ModBus Interface ACM1001. OptiDrive Modbus Module Product Specification. For assistance call

Powerful Performance Advanced motor control

Powerful Performance Advanced motor control

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

QUICK REFERENCE GUIDE

PowerFlex 40 Sample Specification

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

AC Variable Speed Drive. Powerful Performance. Advanced motor control. 0.75kW 250kW / 1HP 350HP V Single & 3 Phase Input

Modbus Protocol. for VASCO, VASCO Solar and MIDA devices. manmodbus_eng_00

Quick Start Guide For GVX9000 AF Drives

Powered to Perform. Everyday Reliability. Exceptional Value. Expertise and Support

OptiDrive Advanced Technical Manual

OPTIDRIVE. look no wires... just total control

STOCK DRIVES CATALOGUE

Section 16. Drives AF-650GP General Purpose Drive. Standard Specifications. Environmental Conditions. Logic Controller (LC) Sequencer

Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM) radio-frequency equipment (EMC)

1. Introduction About the Vacon 5X drive Identifying the drive by model number Drive model numbers...7

Quick Start Guide Cutler-Hammer SVX9000 Drives from Eaton Corporation CONTENT STEP 1 Keypad Operation Overview STEP 2 Standard Wiring Diagrams and

vacon se2 user's manual

1.1.1 Software Version Introduction About this Manual References 2

Contents. Index 35. VLT HVAC Drive Metasys N2

ModBus Communication protocol. The ModBus protocol is an industrial communications and distributed control system

Step 1: Choose the Appropriate CPU Step 2: Make the Connections

User manual. MODBUS-RTU SV-iC5

Installation and Operating Instructions

Specification Number: Product Name: FRENIC-Mega AC Drives for General Purpose Applications (½ - 150Hp at 230V and ½ Hp at 460V)

SAFETY PRECAUTIONS. Throughout this manual we use the following two illustrations to make you aware of safety considerations:

GV3000/SE AC Drive Quick Reference Version 6.06

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

MC Series Drives. Flexible, simple, rugged, robust!

QD:CT Plus & QD:VT Installation and Operating Instructions

HV310 Simplified Drive. 0.5HP-15HP (0.4kW-11kW) 200V-240V / 380V-480V

Frequency Inverters WJ200 Series Compact Inverter

Built-in Board Option DEV001Z. Function Manual

Reliance GV3000 Drive Registers

Pump Data Sheet - Patterson HVAC Pumps Company: Intermountain Hydron Name: Cache County Mountain Crest Date: 09/24/2018

OPTIDRIVE PLUS 3 GV 3 rd Generation Vector Control AC Variable Speed Drive kW

SENSORLESS VECTOR CONTROL

A66SM Installation and Programming Manual

SORDS ELECTRIC ~ MA7200. Sensorless Vector AC Inverter.

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

PART 1: GENERAL PART 2: PRODUCT. Phone: Fax: Web: -

Parameters MICROMASTER 420

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

A66N2 Installation and Programming Manual

FLÄKTGROUP OFFERS A WIDE RANGE OF PER- MANENT MAGNET MOTORS (PM) AND FREQUENCY CONVERTERS FOR PLUG FANS. POWER RANGE IS FROM 0,8 KW TO 15 KW.

Drive Electronics \ Drive Automation \ System integration \ Services MOVITRAC LTE-B. Catalog. Edition 02/ / EN

VLT 2800 DRIVE SPECIFICATIONS

SMD SERIES INVERTER MODBUS CONTROL OPERATION MANUAL. Document: SLmod-e2

The benefits are ease of set-up, more data available for the user from the drive, fast control, and state of the art technology.

ETM MD100 Drive System 1/2HP (370W) User Manual. Table of Contents. Drive Features

JKSSS COMMUNICATION HARDWARE LINK & SOFTWARE PROTOCOL (VER. C)

Version Action Author Date

Installation and Commissioning Instructions AC drive VersiDrive i... /E

N700E Inverter RS485 Interface Instruction Manual

Chapter. Modbus. In This Chapter...

MM200 Motor Management System Communications Guide

Frequency Inverters. WJ200 Series. Compact Inverter. WJ200 Series

Tongta Inverter TDS-F8

Status line The top line of the LCD display shows the basic status information of the drive.

PowerFlex 400 AC Drive Guide Specification

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Altivar 21 Programming and Operation Guide

User Manual. PROFIBUS-DP Option Board for SV-iS5 Series. LG Industrial Systems

GE Power Management. MMII Intelligent MCC Controller

Easy To Use OEMS Take Note

Power Xpert C445 Motor Management Relay Cheat Sheets

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

HVAC Products. Introducing the SED2 Variable Frequency Drives

GPD 506 / Modbus RTU Technical Manual

Q9 ASD LOW VOLTAGE DRIVE

Motor Controllers AC Variable Frequency Drives Type Variflex 3 RVLF Advance

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

1. Introduction. 2. Installation MODBUS INTERFACE

18805 Adams Ct., #110 ~ Morgan Hill, CA 95037, USA ~ ~ ~

Parameter Reference Guide. KBG2 Series. RFC-A Mode

MOTOR STARTERS & VARIABLE SPEED DRIVES Variable speed drives

AF-60 LP TM Micro Drive. Programming Guide

Safety Instruction. This symbol indicates the possibility of injury or damage to property.

User Guide. IP20 & IP66 (NEMA 4X) AC Variable Speed Drive kW V

Unidrive M200, M201 (Frame 1 to 4) Quick Start Guide

Transcription:

Application Note AN-ODP- 38 3GV M Modbus RTU Register Map Author: Ning Xu, Invertek Drives Ltd Revision: 2.21 15 June 2007 General This document details the Modbus RTU memory mapping implemented in Optidrive 3GV-M drives, detailing which addresses are used to read and write data to / from Optidrive pluses in a Modbus RTU network. Note that Optidrive 3GV does not support Modbus RTU as standard, unless Modbus support is specifically requested when ordering the drive and is referred to as 3GV-M. It is also possible to upgrade V2.0 drives to support Modbus. Contact Invertek for more details should this be required. The following parameters should be set correctly when using Modbus : P1-12 (set to 4 for Modbus support) ** P2-26 (communication baud rate) P2-27 (drive address) ** For drive software version V2.20 or later, if P1-12 = 0, 1, 2 or 3, the drive can still be monitored and parameters can be modified via Modbus, but control of the drive is not possible unless P1-12 = 4. See User Guide for more information on these parameter settings The Fieldbus Gateways (Profibus, DeviceNet) also use the Modbus interface. In this case, the baud rate must be set to 57kbps. For more information regarding the fieldbus gateway, please contact Invertek Drives Ltd, or visit our web site: www.invertek.co.uk Invertek Drives Ltd reserves the right to make any change to this document without notice. Specification The following table highlights the specification for the Modbus RTU implementation in Optidrive 3GV-M Protocol Error check Baud rate Data format Physical signal User interface Modbus RTU CRC 9600bps, 19200bps, 38400bps, 57600bps, 115200bps (default) 1 start bit, 8 data bits, 1 stop bits, no parity. RS 485 (2-wire) RJ11 (see user guide for more information) Page 1 of 9 15/06/2007

Memory Map Table 1: Control and status registers Register Upper byte Lower Byte Command Type 1* Command 03,06 R/W 2* Speed reference 03,06 R/W 3* Torque reference 03,06 R/W 4* Acc ramp time Dec ramp time 03,06 R/W 5 Reserved 03 R 6* Error code Drive status 03 R 7* Motor speed 03 R 8* Motor current 03 R 9* Motor torque 03 R 10 Motor power 03 R 11 Digital input status 03 R 12** Rating ID 03 R 13** Power rating 03 R 14** Voltage rating 03 R 15** Software version 03 R * Registers are available in standard fieldbus gateway configuration ** Registers are only available with drive firmware revision V2.21 or later Register Description Read and write register Register 1: Drive command 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Reserved 2nd CMD Bit1, 0: Drive command setup: 00-stop, 01-start, 10-reset Bit 2: 2 nd deceleration ramp select flag Register 2: speed reference setup This register holds the speed reference value with one decimal place (200 = 20.0Hz). The maximum speed reference value is limited by P1-01. Register 3: torque reference setup This register holds the torque reference with one decimal place (450 = 45.0%). The data range is from 0 (0%) to 2000 (200.0%) This torque reference is only active when P4-06=3 and drive is in vector control mode. Register 4: Acc/Dec ramp setup This register specifies the drive acceleration and deceleration ramp time. High byte gives Accel ramp time in second: 25 = 25s, maximum 255. Low byte gives Dec ramp time in second: 66 = 66s, maximum 255. Note that if Accel ramp equals to zero, the register value will be ignored. Page 2 of 9 15/06/2007

Read only register Register 6: Drive status and error code High byte gives drive error code. (Valid when drive tripped, see appendix for details) Low byte gives drive status (0: drive stopped, 1: drive running, 2: drive tipped) Register 7: Motor speed information This register gives motor speed information. The data is in Hz and with one decimal place ( i.e. 234 = 23.4Hz) Register 8: Motor current This register gives motor current information. The data is in Amp with one decimal place (i.e. 87 = 8.7A) Reigster 9: Motor torque This register gives motor output torque information. It is a percentage value as 100.0% equals to motor rated torque. The data value includes one decimal place. Register 10: Motor power This register gives motor power information, the data includes two decimal place. The data unit depends on drive type. (i.e.124 = 1.24 KW/HP) Register 11: Digital input status The value in this register represents the drive terminal digital input status (Digital input 1 to 4). Lowest bit indicates digital input 1 status. Register 12: Rating ID This register gives the following information: Drive size, drive type, Power units and Power value decimal places Register value (16 bits HEX format): X X X X h Power units: Drive type: 0: KW 1: HP 0: 3GV 1: VTC 2: 3GV-M Power decimal places: 0: No decimal places 1: One decimal places 2: Two decimal places Drive size: 1: Size 1 2: Size 2 3: Size 3 4: Size 4 5: Size 5 6: Size 6 Page 3 of 9 15/06/2007

Note: Power decimal places is used for register 13 (Power rating). For example, if we have value x1x0h in register 12 and value 15 in register 13, this gives the drive power as 1.5KW. If we have value x0x0h in register 12 and same value 15 in register 13, this gives drive power as 15KW. Or if we have x1x1h in register 12 and 5 in register 13, then the drive power rating is 0.5HP. If we have x0x1h in register 12 and 5 in register 13, this gives drive power rating as 5HP. Register 13: Power rating Combined with the value in register 12, this gives the drive power rating information Register 14: Voltage level This register gives the rated input voltage for the drive. i.e. 230 : 230V 400: 400V 460: 460V Register 15: Software version This register contains the drive software version info. Value includes two decimal places. i.e. 220 means version 2.20 Table 2: Monitor value registers (Read only register with command 03) Adr Description Data format 21 Bipolar analog input value One decimal place 156=15.6% 22 2 nd analog input value One decimal place 156=15.6% 23 Speed control reference 156=156% 24* Digital speed reference Internal value 25 Motor torque reference 2000=200.0% 26 User PID reference One decimal place 156=15.6% 27 User PID feedback One decimal place 156=15.6% 28 User PID error input One decimal place 156=15.6% 29 User PID P term output One decimal place 156=15.6% 30 User PID I term output One decimal place 156=15.6% 31 User PID D term output One decimal place 156=15.6% 32 User PID Output One decimal place 156=15.6% 33 Motor output torque 1000 = 100.0% 34 Magnetizing current One decimal place 156=15.6A 35 Rotor current One decimal place 156=15.6A 36 Field strength One decimal place 156=15.6% 37 Size 1: Two decimal place 156=1.56ohm Stator resistance Other: Three decimal place 156=0.156ohm 38 Stator inductance Four decimal place 156=0.0156h 39 Rotor resistance Size 1: Two decimal place 156=1.56ohm Other: Three decimal place 156=0.156ohm 40 DC bus voltage 256 = 256V 41 Drive temperature 23 = 23 0 C 42 Supply voltage L1 230 = 230V 43 Supply voltage L2 230 = 230V 44 Supply voltage L3 230 = 230V 45* Estimated rotor speed Internal value 46 Kwh meter One decimal place 156=15.6Kwh 47 Mwh meter 156=156Mwh Page 4 of 9 15/06/2007

Table 3: Parameter registers (Support command 03 and 06) Adr Description Data range Data format 129* Max speed limit 0 to 7200 Internal value 130* Min speed limit 0 to 7200 Internal value 131 Accel ramp time 0 to 30000 One decimal place 300=30.0s 132 Decel ramp time 0 to 30000 One decimal place 300=30.0s 133 Stop mode select 0 to 2 0: Ramp to stop 1: Coast to stop 2: Ramp to stop 134 Energy save 0,1 0: Disable 1: Enable 135 Motor rated voltage 20 to 250 (Low) 20 to 500 (High) 136 Motor rated current Drive dependent One decimal place 300=30.0A 137 Motor rated frequency 25 to 2000 Data unit in Hz 138* Motor rated speed 0 to 60000 Data unit in RPM 139 Preset speed 1 -P1-01 to P1-01 Internal value 140 Control mode 0 to 4 0: Terminal 1: Keypad forward only 2: Keypad forward and reverse 3: PID control mode (N/A) 4: Modbus control mode 141 Trip log Last four trips (See Appendix for details ) 142 Access code 0 to 30000 143 Digital inputs function 0 to 21 See user guide for function details 144* Preset speed 2 -P1-01 to P1-01 Internal value 145* Preset speed 3 -P1-01 to P1-01 Internal value 146* Preset speed 4 -P1-01 to P1-01 Internal value 147* Preset speed 5 -P1-01 to P1-01 Internal value 148* Preset speed 6 -P1-01 to P1-01 Internal value 149* Preset speed 7 -P1-01 to P1-01 Internal value 150* Preset speed 8 -P1-01 to P1-01 Internal value 151* Skip frequency 1 -P1-01 to P1-01 Internal value 152* Skip freq band 1 P1-02 to P1-01 Internal value 153 Analog output function 0 to 10 See user guide for function details Digital output ctrl limit (h) 0 to 100 Located in lower byte 154 Digital output ctrl limit (L) 0 to high limit Located in higher byte 155 Relay output function 0 to 6 See user guide for function details Relay control limit (h) 0 to 100 Located in lower byte 156 Relay control limit (L) 0 to high limit Located in higher byte 157 Relay output mode 0 to 1 0: Normally open 1: Normally closed 158 Zero speed holding time 0 to 60s 600 = 60.0s 159 Start mode select 0 to 6 0: Edgr-r 1: Auto_0 2 6: Auto_1 to Auto_5 160 Reserved 0 Read as zero 161 Keypad restart mode 0 to 3 See user guide for details Page 5 of 9 15/06/2007

Adr Description Data range Data format 162 Enable standby 0 to 60 Data unit in second (s) 163 Display scaling factor 0 to 30000 Three decimal place 300=0.3.00 164 Display scaling source 0 to 1 0: 2 nd analog input 1: Drive speed 165 Brake circuit enable 0 to 3 See user guide for function details 166 Effective switching freq. 0 to 4 and it is 0 = 4KHz, 1 = 8KHz, 2 = 16KHz drive dependent 3 = 24KHz, 4 = 32KHz 167 2 nd Decel ramp time (s) 0 to 30000 One decimal place 300=30.0s 168 Modbus baudrate 0 to 4 0 = 9600bps 1 = 19200bps 2 = 38400bps 3 = 57600bps 4 = 115200bps 169 Drive comms address 1 to 63 170 Master/Slave mode 0 to 1 This is for Optibus application only, not for Modbus. 171 Speed scaling factor 0 to 5000 One decimal place 300=30.0% 172 Bipolar an input format 0 to 3 0: 0..24V 1: 0..10V 2: -10..10V 3: -24V..24V 173 Bipolar an input scaling 0 to 5000 One decimal place 300=30.0% 174 Bipolar an input offset -5000 to 5000 One decimal place 300=30.0% 175 2 nd an input format 0 to 3 0: 0/24V Digital 1: 0..10V 2: 4..20mA 3: 0..20mA 176 2 nd an input scaling 0 to 5000 One decimal place 300=30.0% 177 Ditial speed reference scaling control 0 to 3 See user guide for function details 178 Analog output format 0 or 3 0: 0..10V 1: 4..20mA 2: 10..0V 3: 20..4mA 179 Extended access code 0 to 9999 180 Parameter lock 0 or 1 0: Unlock 1: Locked 181 Drive run time Read only Read value as hours 182 Drive power rating Read only Power with 2 decimal place 183 Reserved Read only Read as zero 184 Reserved Read only Read as zero 185 Reserved Read only Read as zero 186 Reserved Read only Read as zero 187 Reserved Read only Read as zero 188 Reserved Read only Read as zero 189 Reserved Read only Read as zero 190 Reserved Read only Read as zero 191 Reserved Read only Read as zero 192 Reserved Read only Read as zero 193 Reserved Read only Read as zero 194 Reserved Read only Read as zero Page 6 of 9 15/06/2007

Adr Description Data range Data format 195 Reserved Read only Read as zero 196 Reserved Read only Read as zero 197 Reserved Read only Read as zero 198 Reserved Read only Read as zero 199 Control mode 0, 1, 2 0: Vector speed control 1: Vector torque control 2: V/F speed control 200 Motor parameter auto-tune 0 or 1 201 Speed controller P-gain 0 to 4096 202 Speed controller integral time constant 0.001 to 0.100s 1 = 0.001s 203 Motor power factor 0.50 to 0.99 78 = 0.78 204 Torque reference select 0 to 3 0: digital preset value 1: Bipolar analog input 2: 2 nd analog input 3: Modbus reference 205 Maximum torque limit/ref 0 to 200% 100= 100% 206 Minimum torque limit 0 to 150.0% 100 = 10.0% 207 V/F characteristic adjustment frequency 0 to P1-09 500 = 50.0Hz 208 V/F characteristic adjustment voltage 0 to P1-07 100 = 100V * Explanation for internal value: For some speed related parameters, the drive uses an internal value instead of the actual speed in Hz in order to increase the resolution. For these speed related parameters, the internal value instead of the display value must be used in order to set the parameter correctly. Speed Internal = Speed in Hz * Factor When P1-09 <= 100Hz, Factor = 60. ie 30.5Hz -> 1830 When P1-09 <= 200Hz, Factor = 30. ie 30.5Hz -> 915 When P1-09 > 200Hz, Factor = 15. ie 250Hz -> 3750 Page 7 of 9 15/06/2007

Table 4: Advanced parameter registers (Support command 03 and 06) Adr Description Data range Data format 209 Motor stator resistance Drive dependent Size 1: Two decimal place 156=1.56ohm Others: Three decimal place 156=0.156ohm 210 Motor rotor resistance Drive dependent Size 1: Two decimal place 156=1.56ohm Others: Three decimal place 156=0.156ohm 211 Motor stator inductance Drive dependent Four decimal place 156=0.0156h 212 Motor magnetizing current Drive dependent One decimal place 156 = 15.6A 213 Leakage coefficient 0.025 to 0.250 Three decimal place 100 = 0.100 214 Speed filter time constant 0.001s to 0.100s Three decimal place 100 = 0.100 215 Quick RS measurement 1: Enable 0: Disable Default value: 1 216 Motor parameter adaptation 1: Enable 0: Disable Default value: 1 217 Over voltage current control limit 0 100% 218 Regeneration current control limit 0 200% 219 Minimum PWM plulse 0..625 Minimum pluse = value * 33.3ns 220 V/F magnetising delay 0 2000ms 221 Reserved Read only Read as zero 222 Thermal fold back control 1: Enable 0: Disable Default value: 0 223 Auto-restart delay time 1 60s Default value: 20 224 Relay control speed hyteresis value 0%...25.0% One decimal place 156 = 15.6% 225 Hoist function boost speed 0%...10.0% One decimal place 156 = 15.6% 226 Boost speed holding time 0.1s 5.0s One decimal place 15 = 1.5s 227 Speed dead band zone 0%...20.0% One decimal place 156 = 15.6% 228 Modbus comms loss time 0: Trip disable 1 60s 229 Droop control speed 0%...25.0% One decimal place 156 = 15.6% Note: Registers in the above table are only available with drive software version 2.21 or later. Please refer to advance user guide for more information of the corresponding parameter in this table. Page 8 of 9 15/06/2007

Appendix Drive error code information: 0x00 0x01 0x02 0x03 0x04 0x05 0x06 0x07 0x08 0x09 0x0A 0x0B 0x0C 0x0D 0x0E 0x0F 0x10 0x11 No trip Brake circuit over current (short circuit) Over current External trip DC bus over voltage trip DC bus under voltage trip Over temperature trip Under temperature trip Spin start fault Parameter defaut I*t trip (Over load trip) Phase imbalance trip Brake resister over load Power stage trip Communication link loss trip Phase loss trip Thermistor fault Auto-tune fault Dataflow example: Modbus RTU Read data from register 6: Request: [01] [03] [00] [05] [00] [01] [94] [0B] (Drive Addr) (Command) (Reg start addr) (No. of Registers) (Checksum) Reply: [01] [03] [02] [00] [00] [B8] [44] (Drive Addr) (Command) (No of data bytes) (Data) (Checksum) Note that the actual start address of register 6 is 5. --- End --- Page 9 of 9 15/06/2007