MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

Similar documents
JERGUSON MTII4300. Installation, Operation, & Maintenance Instructions IOM M per CDC

Magnetostrictive Liquid-Level Sensors with Temposonics Technology. M-Series Model MR3/4 MLG Transmitter with Analog Output.

NightStar. Installation, Operation, & Maintenance Instructions M /04/2016

BLISS ANAND. BA-Series Magnetostrictive Level Transmitter

TPE 1464 Series Pressure Transducer

955 ebrik INSTALLATION MANUAL. Series ebrik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS LINEAR DISPLACEMENT TRANSDUCERS

CDD Carbon Dioxide Transmitter

Level-Lance Model 5400A

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual

Do not open when energized or when an explosive atmosphere is present. Electrostatic hazard, clean only with damp cloth.

BTL6-A_10-M -A1-S115. Data Sheet. english

CDD4 Duct Carbon Dioxide Transmitter

Digital EPIC D460/D470 For Rotary, Linear and Standard Applications Operating Manual

Analyzer/Controller. ph/orp HART. Model 54e ph/orp ESSENTIAL INSTRUCTIONS WARNINGS RISK OF ELECTRICAL SHOCK

Scanner 2000 microefm QuickStart. Installing the Scanner Remote Mount. Direct Mount NUFLO. Part No , Rev. A

Series ULT Ultrasonic Level Transmitter

PanelView Plus/VersaView CE Terminals and Display Modules

Smart Wireless THUM Adapter

KOBOLD TDA Series Digital Temperature Transmitter

955S BRIK. Series 955S Brik. Smart BRIK LDT ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS. Linear Displacement Transducer

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Explosion-Proof Gauge Pressure Transmitter

Family of Water Cut Analyzers

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS

4110 HART Level Encoder

Tempco Instruction Manual

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

LCD Meter for Model 3051 Pressure Transmitters English Rev. AA

Installation Sensing distance Connection Output configuration Operation mode NO Operation mode NC

CONTROL MICROSYSTEMS Analog Input Module. Hardware Manual

SFY Functional Safety Frequency-to-DC Transmitter with Display

KOBOLD PDA Series Digital Pressure Transmitter

Smart Wireless THUM Adapter

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

INSTALLATION INSTRUCTIONS

Transducers & Transmitters HART USERS MANUAL. GP:50 New York LTD Long Road Grand Island, NY USA

CDD4 Series Room CO2 Transmitter Installation Instructions

EPWR Series. RoHS. Product Description. Available Products. Installation Instructions 01

Scanner 2000 Steam Mass Flow Transmitter

16-Channel Digital Input Termination Card 24Vdc

Advanced Test Equipment Rentals ATEC (2832)

This network (Figure 5) has a Panel-Version Facilitator, Operator Terminal, five controllers, and a repeater.

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

SENC 150 REFERENCE MANUAL

DXp-10 and DXp-15 Weight Transmitter

RK-A CONTACTLESS MAGNETOSTRICTIVE LINEAR POSITION TRANSDUCER

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

This Datasheet for the IC660BBA104. Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs

Thread length (overall length) material

Differential Liquid/Gas Pressure Transmitter

Installation and Operating Instructions

Multi-Point Gas Detection and Control System

CONTROL MICROSYSTEMS Thermocouple Analog Input Module. Hardware Manual

Inductive Proximity Sensor

Sensors Division. Level Plus Direct Digital Access (DDA) Tank Gauge. Operation Guide and Installation Manual. P/N Revision D

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBA026. Block 24/48Vdc Analog Current Source 6 Inputs.

PD301 - PD306 Head Mount SMART TEMPERATURE TRANSMITTERS

Series 957SSI Brik. Linear Displacement Transducer. Installation Manual. 957SSI Brik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE...

High Voltage DC Meter

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

Isolated Current Output 5B39 FEATURES APPLICATIONS PRODUCT OVERVIEW

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1

INSTRUCTION MANUAL MODEL RTI-EC RESISTANCE TEMPERATURE INDICATOR TABLE OF CONTENTS 1. GENERAL DESCRIPTION PAGE 1

T E M P O S O N I C S I I I INSTALLATION

dual-line 6-dIGIt process MeteR

Safety. 1. Installation 1.1 CR:Services 1.2 Driver Card Installation 1.3 Sensor Types 1.4 Sensor Wiring

Analog Voltage Combination Module

Carbon Monoxide Sensor - ModBus

HIGH-VOLTAGE DC METER

IPM650 Intelligent Panel-Mount Display

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

User's Manual: Series 250T Potentiometer/Slidewire Input, Two-Wire Transmitters

Multi-Point Gas Detection and Control System

EF-S1 SERIES. Continuously check invisible static electricity in lines. Constantly check static in lines!

E4PA-N. Application Examples. Features. Ultrasonic Displacement Sensor. Now, more advanced with a new mutual interference prevention function.

FLEX Ex Spring Clamp Terminal Base

LTM IntelliGage Series Magnetostrictive Level Transmitters

MODEL 8000MP LEVEL SENSOR

16-Channel Digital Input Termination Card 24Vdc

Quick Start Guide MC-III TM Flow Analyzer

KOBOLD Compact Electronics

CII: Current Input, Isolated

MasterFlux 48V Cascade BLDC Motor Controller Product Specification 030F0137

Item E2CD-C1C3A E2CD-C1R5C3A E2CD-X2R5C3A E2CD-X5C3A 12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.

Level Plus. Magnetostrictive Liquid-Level Sensors with Temposonics Technology

Installation & Operation Guide

Safety. 2. Configuration - Operation 2.1 RTD Selection 2.2 Driver Test Header. 3. Diagnostics 3.1 ph Input 3.2 Temperature Input

Liquid-Level Sensors. M-Series Digital. Liquid Level Transmitter. Operation and Installation Manual I

Multi-Point Gas Detection and Control System

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

Power Over Fiber USER GUIDE. SYSTEM INSTALLATION INFORMATION Description. The leader in rugged fiber optic technology. RLH Industries, Inc.

Flow Meters. Model B Flow Monitor. Model B2800. Flow Monitor

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

Transcription:

Specialists in Liquid Level Indication MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 05-17-16 Supersedes: 09-30-11 1. INTRODUCTION The Jerguson Model MTII4200 is a 4-20 ma, loop-powered HART compatible level transmitter intended to be used in conjunction with the Jerguson Magnicator II magnetic liquid level gage. The part number designator for the MTII4200 can be found below. COMM OPTION: H=4-20mA w/ HART MTII4200-#-#-#-#-#-#-###/### ACTIVE SENSING LENGTH IN INCHES HOUSING: A= ALUMINUM w/ WINDOW (STD.) S= STAINLESS STEEL w/ WINDOW BA= ALUMINUM w/o WINDOW TRANSMITTER ORIENTATION: A= TOP LEFT HAND (STD.) B= TOP RIGHT HAND C= BOTTOM RIGHT HAND D= BOTTOM LEFT HAND MAX SENSING LENGTH IN INCHES, ON 6 INCH INCREMENTS MOUNTING STYLE: S= STRAIGHT (STD.) H= HIGH TEMP EXTENDED ALARM SETTING: L= 3.85 ma (DEFAULT) H= 22.5 ma LCD DISPLAY: M= ma OUTPUT (DEFAULT) I= INCHES P= PERCENTAGE There are two main components that make up the MTII4200. These two components are the electronics housing and the sensor housing (see Figs. 1 & 2). These two components are assembled at the factory and should not be separated in the field. Figure 1. MTII4200-H-A-D-x-x-S-xxx/xxx Straight Bottom Left Hand Assembly FOR V19961-E1= 9.313 (REF.) FOR V20816-E6 & V21037-T= 8.688 (REF.) MAX ACTIVE SENSING LENGTH (3.500) DETERMINED BY SE POSITION AT ASSEMBLY

Figure 2. MTII4200-H-A-D-x-x-H-xxx/xxx Bent Bottom Left Hand Angled Assembly MAX. ACTIVE SENSING LENGTH (3.500) DETERMIND BY SE POSITION AT ASSEMBLY 2. PRODUCT DESCRIPTION The MTII4200 liquid level sensor is a multifunctional transmitter with 4-20 ma loop and HART. It provides an analog output of level and the HART digital protocol. Outputs can be monitored using 4-20 ma signal output, a HART device (hand-held or PC-compatible software), the integral display, or all of the above. The MTII4200 transmitters are available in a single cavity explosion-proof enclosure. 2.1 MTII4200 Transmitter Specifications PARAMETER LEVEL OUTPUT Measured Variable: Output: Full Range: Non-linearity: Repeatability: Sensor Operating Temperature: GAUGE LOOP Input Voltage Range: Reverse Polarity Protection: Series diodes Transient Protection: SPECIFICATIONS Liquid level, interface level 4-20 ma, HART 12 to 228 in. (46 to 579 cm) 0.020% F.S. (Independent BSL) or 1/32 in. (0.794 mm)* 0.005% F.S. or 0.005 in. (0.127 mm)* -40 to 300 F (-40 to 149 C) Ambient 10.5 to 36 VDC Stage 1: line-to-ground surge suppressors; 2500 Amps peak (8/20 µsec.) Stage 2: line-to-line and line-to-ground transient suppressors; 1500 Watts peak (10/1000 µsec.)

CALIBRATION Zero Adjust Range: Span Adjust Range: Anywhere within the active length Full Scale 0.5 ft. (152 mm) from zero 2.2 Theory of Operation ENVIRONMENTAL Humidity: Electronics Operating Temperature: Vessel Pressure: FIELD INSTALLATION Mounting: Wiring: DISPLAY Measured Variables: Update Rate: 0 to 100% R.H., non-condensing -30 to 160 F (-34 to 71 C) ambient Dependent on float pressure rating, On side of magnetic level gage via brackets and hose clamps 2-wire connection, Shielded Twisted Pair to screw terminals through a 3/4 in. NPT conduit opening. Min 18 AWG/ Max 12 AWG Level 3 seconds HART COMMUNICATIONS Method of Communication: Frequency Shift Keying (FSK) conforms with Bell 202 Modem Standard with respect to baud rate and digital 1 and 0 frequencies. Baud Rate: 1200 BPS Digital 0 Frequency: 2200 Hz Digital 1 Frequency: 1200 Hz Data Byte Structure: 1 Start Bit, 8 Data Bits, 1 Odd Parity Bit, 1 Stop Bit Digital Process Variable Rate: Poll/Response Model 2.0 per second AGENCY APPROVALS Factory Mutual (FM) Explosion-proof: Class I, Div 1, Groups B, C, D The MTII4200 transmitters precisely sense the position of an external float by applying an interrogation pulse to a waveguide medium. This current pulse causes a magnetic field to instantly surround the waveguide. The magnet installed within the float also creates a magnetic field. Where the magnetic fields from the waveguide and float intersect, a rotational force is created (waveguide twist). This, in turn, creates a torsional sonic pulse that travels along the waveguide. The head of the transmitter houses the sensing circuit, which detects the torsional sonic pulse and converts it to an electrical pulse. The distance from a reference point to the float is determined by measuring the time interval between the initiating current pulse and the return pulse and knowing the precise speed of these pulses. The time interval is converted into a 4-20 ma loop signal. 3. INSTALLATION/MOUNTING Mounting The MTII4200 is designed to mount directly to the outside of the Magnicator II chamber. 1. Secure the transmitter to the chamber using the supplied hose clamps. 2. Align the low and high level range markings on the sensor housing with the actual measurement range. 3. Ensure that the clamps are tight. 4. To test if the gauge is properly tightened, pull up on the electronics housing. The gauge should not move.

4. ELECTRICAL CONNECTIONS AND WIRING PROCEDURES Electrical Connections Connect the 24 VDC power supply to the electronics module using the screw terminal block on the electronics module. A typical wiring arrangement is shown in Figure 3. Figure 3 Wiring Diagram For explosion-proof installations, wiring shall be in accordance with the National Electric Code ANSI/NFPA 70, Article 501-30. Shielded twisted pair of Min 18 AWG/ Max 12 AWG should be used. Cable capacitance shall be less than 30 pf per foot. 4.1 Cable Specifications Parameter Specification Minimum Cable Size: Min 18 AWG/ Max 12 AWG Cable Type: Shielded Twisted Pair or Multiple Pair with Overall Shield Maximum Cable Length: Shielded Twisted Pair: 10,000 ft. (3,048 m) Multiple Pair with Overall Shield: 5,000 ft. (1,524 m) 4.2 Safety Recommendations for MTII4200 Transmitter Always follow applicable local and national electrical codes and observe polarity when making electrical connections. Never make electrical connections to the MTII4200 transmitter with power turned on. Make sure that no wire strands are loose or sticking out of the terminal block connection which could short and cause a problem. Make sure that no wire strands, including shield, are in contact with the electronic module enclosure. The electronics module enclosure is grounded through internal circuitry and electrically isolated from the explosion-proof enclosure. 5. SYSTEM CHECK After completing the MTII4200 wiring, the system is ready to be checked out. Apply power to the unit. Using a DC voltmeter, measure the voltage at loop #1 connections. The voltage must be a minimum of 10.5V. If the voltage levels are too low, shut down the system. Check for shorts, power supply voltage, and excessive loop resistance. 5.1 Loop #1 Test To test loop #1 on a bench, move the float along the operational range of the MTII4200 transmitter. If functioning properly, the output current will change as the float moves. An output current of less than 4 ma or greater than 20 ma could indicate a problem with the MTII4200 transmitter.

6. MAINTENANCE Magnicator II liquid level gauges use magnetostrictive technology and only have one moving part the float. This technology ensures no scheduled maintenance or re-calibration is required. 6.1 Removal of Electronic Puck The MTII4200 gauge is designed so that the user may remove the electronics module for any reason. 1. Turn off power to transmitter. 2. Remove cover from explosion-proof housing enclosure. 3. Gently pull out the electronic puck by raising equally on all sides of the round puck. Do not twist. 4. Pull electronic puck completely free of connector pins and spacer on block cover. 6.2 Installation of Electronic Puck 1. Verify power to transmitter is off. 2. Remove cover from explosion-proof housing enclosure. 3. Place electronics puck on top of mating connector pins (2 places) and spacer, and gently press down on puck. 4. Press down on puck until connection is made completely. 5. Install cover of enclosure before applying power. 7. ADJUSTMENTS FOR MTII4200 TRANSMITTERS (via HART) Refer to the documentation supplied with your specific HART software package or hand held communicator for details on performing sensor calibration. This section describes how the HART protocol is applied to the MTII4200 level transmitter only. Using the HART interface allows for calibration without having to remove the transmitter from the process and position the floats. The HART commands 35 and 65 are implemented for this function. Any measured output may be assigned to any variable. Loop #1 is always the primary variable (P.V.); normally level one is assigned to loop #1. Calibration set points for level one are given as the absolute displacement (in the appropriate units) from the tip of the sensor. For example, if the desired ZERO position for level one is given as 5 inches, the MTII4200 will produce 4 ma when the float is 5 inches from the tip of the transmitter. If the desired SPAN position for level one is given as 30 inches, the MTII4200 will produce 20 ma when the float is 35 inches from the tip of the transmitter. 7.1 HART Quick Start The MTII4200 transmitter can be re-calibrated using a Rosemount model 275 hand held terminal. Follow the simple instructions below to reset the low and high values for loop #1. Only loop #1 can be calibrated with the HART terminal. RULES: 1. Be sure the MTII4200 is connected to a clean 24 VDC power supply. Use a linear supply; it is not recommended to use a switching type power supply. Switching type power supplies have small ripples in the power that can adversely affect the operation of the transmitter. HART cannot tolerate more than a 25 mv voltage ripple. 2. If the unit is installed in a live application, place your automatic controllers in manual mode and be advised that the output current will change during calibration. 3. Follow safe working procedures as applicable for working on live equipment in a hazardous location. When safety is secured, remove housing cover.

4. Connect the HART communicator to the HART terminals labeled HART on the front panel display of the MTII4200 gauge. NOTE: Be sure you have the transmitter loop #1 connected to a load of 250 to 500 Ohms. A unit installed in a control loop is a good example of this loop load. You may also use a load resistor in the range of the above value. 5. Press the black and white "I/O" button on the HART terminal. The terminal will go into self-test, then into the main screen. If not connected properly, you will get a "No device found" message. 6. From the main screen, press keypad key #1, "Device Setup". 7. From the "Device Setup screen, press key #3, "Basic Setup". 8. Press key #3. You are now in "Range Values" screen. To set low value To set the low value (4 ma), select key #1, PV LRV (Process Variable, Lower Range Value). You are now in the PV LRV screen. The current low value is displayed. Below this value is a highlighted value. Key in the desired low value (example 3.00 in. is shown; if 4 inches is desired, key in 4.) When the new desired low value is keyed in, press the "enter" (F4) button located below the LCD display, right. To write the changed lower value to memory, press the "SEND" key now. Next you will see two "WARNING" screens that ask if you are sure. If your new low values are correct, press "OK" for both messages. This action resets the Lower Range Value, or 4 ma position into the transmitter's memory. Go back to the "Range Values" screen to verify that the new parameters have been accepted into the transmitter memory. NOTE: This value is determined by measuring from the end of the sensor housing farthest from the enclosure no matter which way the transmitter is mounted. You may now exit program mode or continue on to reset the upper value. If you choose to exit the program mode, replace the calibration jumper to the "ON position, and return your controllers to automatic. To set high value You should now be in the "Range Values" screen. To set the 20 ma (Upper Range), press key #2. You are now in the "PV URV" (Process Variable, Upper Range Value) screen. As in the lower value screen, the current value is displayed with a highlighted number below it. To change the upper value, key in the desired value. You may use whole numbers or whole numbers and decimal numbers (40 = 40 inches, or 40.5 = 40.50 inches). Whole numbers will be entered as their decimal equivalents by HART automatically. Key in the desired upper range value desired. Press the "Enter" (F4) button. You are back in the "Range Values" screen. If the numbers for lower and upper are correct, press the "Send" key. You will get a "WARNING!" Press the "OK" button. You will again get "WARNING!" Press OK" again. NOTE: This value is determined by measuring from the end of the sensor housing farthest from the enclosure no matter which way the transmitter is mounted. Startup is now complete. CAUTION! Never enter a value that is longer than the active length of the sensor. This is measured from the tip of the sensor to the calibration mark closest to the head of the transmitter. 7.2 Calibration The MTII4200 has three buttons for calibration: Enter Down Arrow Up Arrow 1.) Turn the power on to the unit. 2.) Wait for the self-diagnostics to complete. 3.) Press any button to start calibration mode. 4.) The screen will display Cal Lev 1?. 5.) The far right button is the Enter key. Pressing any button will cause the unit to enter calibration. Pressing all three buttons at any one time will exit the calibration mode.

6.) Press the Enter key. 7.) The screen will display Set Zero?. 8.) Move the float to the zero, (4mA), location. 9.) Press the Enter key. 10.) The screen will display Zero (corresponding number). 11.) Press Enter to reset the (corresponding number) to zero and hold for approximately 1-2 seconds. 12.) The screen will display Accept?. 13.) Press Enter (You have now set the zero point). 14.) The screen will display Cal Lev 1?. 15.) Press Enter. 16.) The screen will display Set Zero?. 17.) Press the arrow UP key (far left) so the screen will now display Set Span?. 18.) Move the float to the span location. 19.) Press Enter. 20.) The screen will display Span (corresponding number). 21.) Press Enter to reset the (corresponding number) to span and hold for approximately 1-3 seconds. 22.) The screen will display ACCEPT?. 23.) Press Ener (You have now set the span point). 24.) The screen will display Cal Lev 1?. 25.) Press and hold all three button simultaneously for 2-3 seconds to reset the unit. 26.) The zero (4mA) and span (20mA) set points are now configured. To calibrate or change the working range of the transmitter, press any button to enter Function Mode. Hit the enter button when the CAL LEV 1? prompt apprears. Calibrate Zero should now be on the display, if not press the Up or Down button until it is. Press the enter button to set the low level of the range. At this time, position the float magnet at the desired low level point and keep it there while pressing the Enter button and holding it down for approximately two seconds. Once done, ACCEPT should be on the display, press the Enter button. This is now your new low level for the range. Setting a new low level for the range does not change the high level position. To change the high level position, press Enter when CAL LEVEL 1? appears on the display. Press Enter again when Calibrate Span is displayed, using the Up and Down buttons if needed. Repeat the above steps beiginning with position the float magnet to change the high level of the range. When done, press all three buttons to exit Function Mode. 8. ALARM SETTINGS When a fault condition is detected by the internal microprocessor, the 4 to 20 ma current will go to the current selected. In the 4 ma alarm mode, when a fault is detected the output will be continuous at 3.8 0.1 ma. In the 20 ma alarm mode, when a fault is detected the output will be continuous ar 22.5 0.2 ma. 9. SPARE PARTS MTII4200 Transmitter (Puck) P/N: V19962HP MTII4200 I/O PCB P/N: V19962

16633 Foltz Parkway Strongsville, OH 44149 USA Telephone: +1 (440) 572-1500 Fax: +1 (440) 238-8828