Earth-fault Relay SPAJ 110 C. Product Guide

Similar documents
Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Residual overvoltage relay

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Synchro-check relay. Application

Feeder protection relay SPAA 341 C. Product Guide

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

Feeder protection relay

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

High impedance protection relay

Arc protection relay. Features Three-phase overcurrent function. Application

Arc protection relay. Features Three-phase overcurrent function. Application

SPAA 341 C Feeder protection relay

Feeder Protection Relay REF 610. Product Guide

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Communication Gateway COM 610. Product Guide

Motor Protection Relay REM 610. Product Guide

SPA-ZC 302. Profibus-DPV1/SPA Gateway. Product Guide. spa-zc302_rightco300

Data communication and reporting unit

Relion 611 series. 611 series Type Test Certificate

SPA-ZC 17. Bus connection module SPA-ZC 17. User s manual and Technical description. Tx SC Rx BB BM MB MM SPA / RS 485 POWER SLAVE 1 MASTER 0

SPA-ZC 200/SPA-ZC 202 IEC /SPA-gateway Modules. Installation Manual

Data communication and reporting unit

LON bus communication devices 1MRS MBG Page 1 Issued: April 1999 Status: New Data subject to change without notice

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

Protection Relays PHASE & RESIDUAL OVERCURRENT

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

General characteristics of C-type relay modules

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Relion 610 series. Voltage Protection REU610 Product Guide

SREDU Double Connection Option Card for Lon Star Coupler RER 111

Relion 610 series. Feeder Protection REF610 Product Guide

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

Protection and control. Sepam range Sepam 100 RT. Merlin Gerin Square D Telemecanique

Feeder Protection REF615. Product Guide

RER 123 Bus Connection Module. Technical Description

ekorrps MULTIFUNCTIONAL PROTECTION UNIT CONFIGURATION AND GENERAL CHARACTERISTICS LIB

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

Voltage Transducer UMT516 / MT516

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Multifunction Transducer MT440

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

For Transmission, Distribution and Machinery protection.

Contact protection relay

GRD130 - FEATURES APPLICATION

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

DRTS 33. The new generation of advanced three phase relay test set

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

Power Products. Station Automation COM600 Product Guide

Devices raised mounting

Solid-state Timer H3YN

Binary output and supervision 520CSD01 Data sheet

NPW800R RETROFITTING. Power and Volatge Protection Relay

Switching relay CT-IRE with 1 c/o (SPDT) contact

RT4B-110V/12A RECTIFIER

RM4JA01F current measurement relay RM4-J - range ma V AC

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

RUC industrial relays of small dimensions

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Electronic timer CT-ARS.11

Busbar protection REB 670

RT4F-120V/20A-WAC RECTIFIER

Relays for Various Protection Applications / 7SV600

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)

Protection relays.

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Model Number Structure

Electronic timer CT-AHD.22

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Electronic timer CT-ERS.21

Section 4 Ground-Fault Protection Devices

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

GE Energy Connections Grid Solutions MMLZ. Technical Data Sheet Auxiliary Modules. Publication reference: MMLZ/EN TDS/B

VIP 40/45 VIP 400/410

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

Analog output 520AOD01 Data sheet

LED Driver Compact fixed output

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

RM4JA32MW current measurement relay RM4-J - range A V AC DC

Feeder/ Motor Protection Relay VAMP 40

Bulletin 290/291 ArmorStart LT Distributed Motor Controllers Specifications

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

FL MC 2000E (SM40) LC

Electronic timer CT-ERD.12

Transcription:

Issued: April 1999 Status: Updated Version: C/12.04.2006 Data subject to change without notice Features Low-set neutral overcurrent stage with definite time or inverse time characteristic High-set neutral overcurrent stage with definite time characteristic Output relay functions to be freely configured Flexible adaptation to different types of application Serial interface for connecting the relay to a fibre-optic object bus and substation and network control systems Digital display of setting values, neutral current measured, memorized fault values and more Continuous self-supervision with auto-diagnostics of hardware and software Member of the SPACOM product family and ABB s Distribution Automation system CE marking according to the EC directive for EMC Application The earth-fault relay is designed to be used for selective earth-fault protection, either primary or back-up protection, in solidly earthed or low-resistance earthed power systems. The relay has two protection stages: a low-set overcurrent stage I 0 > and a high-set overcurrent stage I 0 >>. The low-set stage operates with definite-time characteristic or with inverse-time characteristic, while the high-set stage operates with definite time characteristic only. The earth-fault relay is used both as primary and back-up earth-fault protection relay for feeders, transformers, generators and motors. The relay can be configured to cooperate with a residual voltage relay used for blocking/deblocking the operation of the earth-fault relay. 3

Design The earth-fault relay is a secondary relay that is connected to the current transformers of the object to be protected. The earth-fault current can be measured either via a set of three phase current transformers in a residual current connection or a window-type core-balance current transformer. When a core-balance current transformer is used, it should be secured that the repeatability of the current transformer is sufficient also at high earth-fault currents. When an earth-fault occurs, the relay delivers an alarm signal, trips the circuit breaker or starts an external auto-reclose relay, depending on the application and the configuration of the relay. When the energizing current exceeds the set start value I 0 > of the low-set stage, the earthfault relay starts. When, at definite time operation, the set operate time t> or, at IDMT operation, the calculated operate time t>, expires, the relay operates. In the same way the high-set stage starts once its set start value I 0 >> is exceeded and, when the set operate time t>> expires, the relay operates. The low-set stage of the earth-fault relay can be given either definite-time or inverse-time characteristic. At inverse time characteristic four inverse time curve sets with different steepness are available: Normal inverse, Very inverse, Extremely inverse and Long-time inverse. These curve sets comply with the BS 142 and IEC 255 standards. The start signal from the earth-fault relay is received as contact function. The start signal can be used, for instance, for blocking cooperating protection relays. The relay contains one optically isolated logic input for external incoming control signals, generally blocking signals. Data communication The relay is provided with a serial interface on the rear panel. By means of a bus connection module type SPA-ZC 17 or SPA-ZC 21 the relay can be connected to the fibre-optic SPA bus. The bus connection module type SPA-ZC 21 is powered from the host relay, whereas the bus connection module SPA- ZC 17 is provided with a built-in power unit, which can be fed from an external secured power source. The relay communicates with higher-level data acquisition and control systems over the SPA bus. Self-supervision The relay incorporates a sophisticated selfsupervision system with auto-diagnosis, which increases the availability of the relay and the reliability of the system. The selfsupervision system continuously monitors the hardware and the software of the relay. The system also supervises the operation of the auxiliary supply module and the voltages generated by the module. When the self-supervision system detects a permanent internal relay fault, the IRF indicator on the relay front panel is lit. At the same time the output relay of the self-supervision system operates and a fault message is transmitted to the higher-level system over the serial bus. Further, in most fault situations, a fault code is shown in the display of the protection relay module. The fault code indicates the type of the fault that has been detected. Auxiliary supply voltage The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module versions are available: type SPTU 240S1 for the supply voltage range 80 265 V ac/dc and type SPTU 48S1 for the supply voltage range 18 80 V dc. The power supply module forms the internal voltages required by the protection relay and the I/O module. 4

Technical data Table 1: Energizing inputs Terminals 25-27 25-26 Rated current I n 1 A 5 A Thermal withstand continuously 4 A 20 A capability for 10 s 25 A 100 A for 1 s 100 A 500 A Dynamic current Half-wave value 250 A 1250 A withstand capability Input impedance <100 mω <20 mω Rated frequency f n, according to order 50 Hz or 60 Hz Table 2: Output contact ratings Type of contact Tripping Signalling Terminals 65-66, 68-69 70-71-72, 73-74-75, 77-78, 80-81 Rated voltage 250 V ac/dc Thermal withstand Carry continuously 5 A 5 A capability Make and carry for 0.5 s 30 A 10 A Make and carry for 3 s 15 A 8 A Breaking capacity for dc, 220 V dc 1 A 0.15 A when the 110 V dc 3 A 0.25 A control/signalling circuit time constant 48 V dc 5 A 1 A L/R 40 ms, at the control voltages Contact material AgCdO 2 Table 3: Control input, communication and power supply External control input Terminals 10-11 Control voltage level 18 265 V dc or 80 265 V ac Power consumption when input activated 2 20 ma Data communication Transmission mode Fibre-optic serial bus Data code ASCII Selectable data transfer rates 300, 1200, 2400, 4800 or 9600 Bd Fibre-optic bus for plastic fibre cables SPA-ZC 21BB connection module, for glass fibre cables SPA-ZC 21MM powered from the host relay Fibre-optic bus for plastic fibre cables SPA-ZC 17BB connection module with for glass fibre cables SPA-ZC 17MM a built-in power supply unit Auxiliary supply modules Power supply and I/O SPTU 240S1 80 265 V ac/dc modules and voltage SPTU 48S1 18 80 V dc ranges Power consumption under quiescent ~4 W conditions under operating conditions ~6 W 5

Technical data (cont d) Table 4: Earth-fault relay module SPCJ 1C8 Low-set current stage I 0 > High-set current stage I 0 >> Start current I 0 >, setting range 0.1 0.8 I n Start time, typically 60 ms Reset time, typically 60 ms Drop-off/pick-up ratio, typically 0.96 Selectable modes of operation Definite time characteristic Operate time t> 0.05 100 s Inverse definite minimum time (IDMT) characteristic Curve sets acc. to IEC 60255-4 and BS 142 Normal inverse Very inverse Extremely inverse Long-time inverse 0.05 1.00 ±2% of set value or ±25 ms Time multiplier k Operation time accuracy Definite time operation characteristic Class E at inverse 5 time operation Operation accuracy ±3% of set value Start current I 0 >> 0.1 4.0 I n and, infinite Start time, typically 50 ms Operate time t>> 0.05 100 s Reset time, typically 60 ms Drop-off/pick-up ratio, typically 0.96 Operation time accuracy ±2% of set value or ±25 ms Operation accuracy ±3% of set value Table 5: Tests and standards Test voltages Dielectric test voltage (IEC 60255-5) 2.0 kv, 50 Hz, 1 min Impulse test voltage (IEC 60255-5) 5 kv, 1.2/50 µs, 0.5 J Insulation resistance (IEC 60255-5) >100 MΩ, 500 V dc Interference tests High-frequency (1 MHz) disturbance 2.5 kv test (IEC 60255-22-1), common mode High-frequency (1 MHz) disturbance 1.0 kv test (IEC 60255-22-1), differential mode Fast transients (IEC 60255-22-4, class 4 kv, 5/50 ns III and IEC 61000-4-4), power supply inputs Fast transients (IEC 60255-22-4, class 2 kv, 5/50 ns III and IEC 61000-4-4), other inputs Electrostatic discharge 8 kv (IEC 60255-22-2 and IEC 61000-4-2), air discharge Electrostatic discharge 6 kv (IEC 60255-22-2 and IEC 61000-4-2), contact discharge Environmental conditions Service temperature range -10 +55 C Transport and storage temperature -40 +70 C range (IEC 60068-2-8) Damp heat test (IEC 60068-2-3) <95%, +40 C, 96 h Relative humidity (IEC 60068-2-30) 93 95%, +55 C, 6 cycles Degree of protection by enclosure IP 54 when flush mounted Weight 3 kg 6

Block diagram Fig. 1 Block diagram and sample connection diagram sspaj110 7

Mounting and dimensions Flush mounting 142 30 250 216 186 34 129 ±1 162 136 139 ±1 Panel cutout dim100 Fig. 2 Flush-mounting relay case (dimensions in mm) Semi-flush mounting a b Raising frame SPA-ZX 111 SPA-ZX 112 SPA-ZX 113 a 176 136 96 b 74 114 154 SFM100_1 Fig. 3 Semi-flush mounting relay case (dimensions in mm) Mounting in 19 inch cabinets and frames An ancillary mounting plate, height 4U (~177 mm), is recommended to be used when the protection relays are to be mounted in 19 inch frames or cabinets. The ancillary mounting plate type SPA-ZX 104 accommodates three relays, type SPA-ZX 105 two relays and type SPA-ZX 106 one relay. Projecting mounting When projecting mounting is preferred, a relay case type SPA-ZX 110 is used. The relay case for projecting mounting is provided with front connectors. SPA-ZX104 SPA-ZX105 SPA-ZX106 +0,4 482,6 0 (19") SPA-ZX110 SPA-ZX115 10 158 115 ø6 263 312 292 101,6 21,5 7 +0,4 177 0 (4U) 115 6 98 104_6_10 Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm) 8

Ordering When ordering, please specify: Ordering information Ordering example 1. Type designation and quantity, 5 pieces 2. Order number RS 421 010-AA 3. Rated values I n =5 A, f n =50 Hz 4. Auxiliary voltage U aux =110 V dc 5. Accessories - 6. Special requirements - Order numbers Earth-fault relay without test adapter Earth-fault relay including test adapter RTXP 18 The last two letters of the order number indicate the rated frequency f n and the auxiliary voltage U aux of the relay as follows: RS 421 010-AA, CA, DA, FA RS 421 210-AA, CA, DA, FA AA equals f n = 50 Hz and U aux = 80 265 V ac/dc CA equals f n = 50 Hz and U aux = 18 80 V dc DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc References Additional information Manual Earth-fault relay 1MRS 750801-MUM EN 9

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation