FLOW MONITOR & TRANSMITTER

Similar documents
FLS M9.06 PH/ORP MONITOR. safety instructions. packing List

FLS M9.06. ph/orp MONITOR

Signet Pressure Transmitter

+GF+ SIGNET ph/orp Transmitter Instructions

Signet Flow Transmitter

Signet ph/orp Transmitter * *

Signet Temperature Transmitter

+GF+ SIGNET Conductivity/Resistivity Transmitter Instructions

SIGNET ph/orp Transmitter

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

SIGNET 5700 ph/orp Monitor - ORP Instructions

CDD Carbon Dioxide Transmitter

Signet 5700 ph/orp Monitor - ph Instructions

Contents. 1. Installation

The IQ240 panel mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

Conductivity Transmitters

MPS-32. Pressure Sensors MPS-32 2-Color Panel Mount. Features. Green Display. MPS-32 Programming Options

CDD4 Duct Carbon Dioxide Transmitter

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

Table of Contents. 1 Introduction Introduction Front Panel Description Rear Panel Description 3

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

Digital Indicator Solutions

High Voltage DC Meter

OPERATING INSTRUCTION

LAUREL. MAGNA Series Large Digit Displays for Counter / Totalizer Pulse Input ELECTRONICS, INC. Features. Description

The IQ300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

HIGH-VOLTAGE DC METER

Signet 5700 ph/orp Monitor - ORP Instructions

Trident and Trident X2 Digital Process and Temperature Panel Meter

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

TPE 1464 Series Pressure Transducer

7511 / / / 711 / / 731 / Preset 27

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

RТTH DUAL ROOM SWITCH

DIGITAL PANEL THERMOMETER

Tachometer Panel, PE3

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

Batch Controller with numerical keypad, remote control inputs and 3 control / alarm / pulse outputs

SIGNET Level Transmitter

Signet 9900 Transmitter

TC 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC COUNTER

+GF+ SIGNET 5800CR Conductivity/Resistivity Monitor Instructions

ZAVIO Outdoor IR Mini Dome. Quick Installation Guide

02/11/2015

Panel Mount Tachometer, T6

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

Photoelectric Sensor

The LT1300 wall mount load cell indicator is a precision digital indicator for load cell and strain gauge applications.

1.6. Counters, Panel Meters, Tachometers and Timers. Contents Description Fusion Integrated Machine Control Standards and Certifications...

Signet 2552 Metal Magmeter Flow Sensors

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations

Multi-Point Gas Detection and Control System

Universal counter UZ 9648 Counting - length measurement - metering - positioning

14 Pressure Measurement. Measuring Devices Description Pressure range Connection Device Page

Tempco Instruction Manual

Rotork Fairchild PAX1 Linear Actuator User s Manual

Signet ph/orp Transmitter

Classification Enclosure rating Input voltage Type of

Setpoint adjuster SG 9648 Output standard signals 0/ ma or 0/ V DC

INDICATOR FOR PROCESS CONTROL. Love Controls. LCI108J-0x INSTRUCTION MANUAL. EDITION: January Valid for models with software version P-1

SX90 Process Controller

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

Retro-reflective photoelectric sensors. Dimensioned drawing. Receiver Transmitter Optical axis LED yellow 90 turning connector. Electrical connection

Operating instructions. Switching amplifier DN0210 DN / / 2015

DINALOG A 144 x 36 A1400 Light-Strip Indicator

V E1B Snap-in I/O Module

GFC114. Low Power Flow Computer FEATURES

FLS F3.00 PADDLEWHEEL FLOW SENSOR APPLICATIONS MAIN FEATURES

V E2B Snap-in I/O Module

CDD4 Series Room CO2 Transmitter Installation Instructions

RXTH DUAL ROOM SENSOR / SWITCH

MICRO SERIES PROCESS DISPLAYS LARGE DIGIT MODELS

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2

Autoranging True RMS Multimeter User Manual

mxcontrol Multifunction Controller

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Carbon Monoxide (CO) Gas Detection and Control System

Option 2. Nil. Note 1) Option 1. Note With waterproof seal and mounting screw. With waterproof seal and mounting screw. 48 conversion adapter

DIGITAL ANZEIGE. for Industry Applications. Series PAXP, PAXDP. Key-Features:

Multi-Point Gas Detection and Control System

DIGITAL DISPLAY. for Industry Applications. Series WAY-SSI. Key-Features:

Dual Channel Monitor for Measurement of Speed and Ratio with SIL1 requirements Series D224.xx

Process Analysis Systems. Stratos Pro A4 MSPH/MSPH. Chem Energy Pharm Food Water. Connection

OPLC Installation Guide

InBin-P Pressure switches from 5 Pa Pa

DM650VI SENSOR/WALL MOUNTED VOLTAGE/mA DISPLAY

2. Actuator B: Ball type P: Pin type F: Flat type

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

Mechanically Activated Device for Dry Run Protection in Applications with LORENTZ Solar Pump Systems

DIGITAL PANEL THERMOMETER

PRO VPR100 Series ViPR Multi Channel Monitoring System

Operating instructions. Speed monitor D / / 2014

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

X Year mfg

DIGITAL DISPLAY. for Industry Applications. Series PAXD. Key-Features:

Transcription:

FLS M9.02 FLOW MONITOR & TRANSMITTER SAFETY INSTRUCTIONS General Statements Do not install and service the product without following the Instruction Manual. This item is designed to be connected to other instruments which can be hazardous if used improperly. Read and follow all associated instrument manuals before using with it. Product installation and wiring connections should only be performed by qualified staff. Do not modify product construction. Installation and Commissioning Statements Remove power to the instrument before wiring input and output connections. Do not exceed maximum specifications using the instrument. To clean the unit, use only chemical compatible products. PACKING LIST Please verify that the product is complete and without any damage. The following items must be included: M9.02 Monitor Instruction Manual for M9.02 Monitor Instruction Manual for F3.00 Sensor (only for M9.02.XX Field Mount Monitor). 1

DESCRIPTION The new FLS M9.02 is a powerful flow monitor designed to convert the frequency signal of FLS flow sensors into a flow rate. M9.02 is equipped with a wide full graphic display 4 which shows measured values clearly and a lot of other useful information. Moreover, due to a multicolor display plus a powerful backlight, measurement status can be determined easily from afar also. A tutorial software guarantees a mistake-proof and fast set up of every parameters. Calibration can be performed just fixing installation features or using a reference value through a new in-line calibration. A 4-20mA output is available to remote flow rate to a external device. A proper combination of digital outputs allows customized setups for any process to be controlled. CONNECTIONS TO INSTRUMENTS F3.00 F3.20 F6.30 F3.10 F3.05 F6.60 F6.61 F111 M9.02 x x - X - X X X ULF F3.80 ph/ ORP200 ph/ ORP400 ph/ ORP600 C150/ 200 C100/ C300 C6.30 M9.02 X X - - - - - - TECHNICAL DATA General Associated sensors: FLS hall effect flow sensors with frequency output or FLS F6.60 flow magmeters Materials: - Case: ABS - Display window: PC - Panel & Wall gasket: silicone rubber - Keypad: 5-button silicone rubber Display: - LC full graphic display - Backlight version: 3-colors - Backlight activation: User adjustable with 5 levels of timing - Update rate: 1 second - Enclosure: IP65 front input range (frequency): 0 1500Hz input accuracy (frequency): 0,5% 2

Electrical Supply Voltage: 12 to 24 VDC ± 10% regulated FLS hall effect flow Sensor power: - 5 VDC @ < 20 ma - Optically isolated from current loop - Short circuit protected 1 x Current output: - 4-20 ma, isolated, fully adjustable and reversible - Max loop impedance: 800 Ω @ 24 VDC - 250 Ω @ 12 VDC 2 x Solid State Relay output: - User selectable as MIN alarm, MAX alarm, Pulse Out, Window alarm, Off - Optically isolated, 50 ma MAX sink, 24 VDC MAX pull-up voltage - Max pulse/min: 300 - Hysteresis: User selectable 1 x Relay output: - User selectable as MIN alarm, MAX alarm, Pulse Out, Window alarm, Off - Mechanical SPDT contact - Expected mechanical life (min. operations): 10 7 - Expected electrical life (min. operations): 10 5 N.O./N.C. switching capacity 5A/240VAC - Max pulse/min: 60 - Hysteresis: User selectable Environmental Operating temperature: -20 to +70 C (-4 to 158 F) Storage temperature: -30 to +80 C (-22 to 176 F) Relative humidity: 0 to 95% not condensing Standards & Approvals Manufactured under ISO 9001 Manufactured under ISO 14001 CE RoHS Compliant GOST R 3

DIMENSIONS COMPACT MOUNTING PANEL MOUNTING WALL MOUNTING 4

Mechanical installation The flow monitor & transmitter is available just in one packaging for compact field version, panel or wall installation. The compact field version is mounted on top of the sensor using the compact mounting kit (F6.KC1), the panel version is installed using the panel mounting kit (M9.LN1), while the wall mounting version is got fixing the panel mounting version on the wall mounting kit (M9.KWX). The mounting kits can be ordered directly connected to the monitor or separately and then simply installed on it. Panel installation Fix instrument on the panel tightening by hand plastic nut (M9.LN1). Wall installation Use the panel mounting kit (M9.LN1) to fix the M9.02 on the dedicated frontal cutout of the wall mounting kit (M9.KWX). Tighten front screws of box and waterproof connectors of cables, internally mount caps on screw sites to get a IP65 watertight installation. 5

Compact installation The compact mounting kit (F6.KC1) includes the compact plastic adapter with gasket for IP65 watertight installation, sensor gasket, the compact cap and the locking ring. Lubricate the sensor gasket with silicone lubricant and mount it on the proper seat. Add the compact cap to the sensor and insert the sensor into the plastic adapter making sure the alignment tabs are seated in the fitting notches. Lock the sensor to the adapter: screw completely the locking ring. Tighten plastic nut to fix monitor on plastic adapter. WIRING General recommendation Always ensure the power supply is switched off before working on the device. Make wiring connections according to wiring diagrams. Terminals accept 26 to 12 AWG (0.08 to 2.5 mm2) Strip around 10 mm (0.4 ) of insulation from the wire tips and tin bare ends to avoid fraying. Ferrules are suggested when connecting more than one wire to a single terminal. Remove the upper part of the terminals for an easy cabling. Insert wire tip or ferrule completely into the terminal and fix with the screw until finger tight. Do not route the sensor, DC power, or 4-20mA cables in conduit containing AC power wiring. Electrical noise may interfere with sensor signal. Routing the sensor cable in grounded metal conduit can help prevent electrical noise and mechanical damage. Seal the cable entry points to prevent moisture damage. 6

Compact or Wall Installation Pull the electrical cables through liquid tight connectors. Use electrical cables with the proper external diameter for the liquid tight connector. PG11/PG9: external diameter between 2-7 mm (0.079-0.276 ) REAR TERMINAL VIEW Refer to dedicated sensor manual for its wiring. POWER/LOOP WIRING DIAGRAM Stand-alone application, no current loop used Connection to a PLC with built-in power supply (3 wire connection) 1 2 3 4 + VDC + LOOP - LOOP - VDC PLC Terminals 1 2 3 4 + VDC + LOOP - LOOP - VDC Internal PLC connection A Connection to a PLC/Instrument with ONE separate power supply PLC / Instrument 1 2 3 4 + VDC + LOOP - LOOP - VDC A or PLC / Instrument 1 + VDC 2 + LOOP 3 - LOOP 4 - VDC A 7

Connection to a PLC / Instrument with TWO separate power supplies PLC / Instrument 1 2 3 4 + VDC + LOOP - LOOP - VDC A or PLC / Instrument 1 2 3 4 + VDC + LOOP - LOOP - VDC A SOLID-STATE RELAY WIRING DIAGRAM (FOR SSR1 AND SSR2) Connection to a PLC with NPN input Connection to a PLC with PNP input Internal PLC connection PLC Power sup. Power sup. O.C. IN O.C. IN 8 N.O. 9 COM Imax = 50 ma Internal PLC connection PLC Power sup. Power sup. O.C. IN O.C. IN 8 N.O. 9 COM Imax = 50 ma Connection to a PLC / Instrument digital input with separate Power Supply Connection to a PLC / Instrument digital input for Voltage Free Contacts (REED) PLC / Instrument Digital INPUT Digital INPUT 10 Kohm 8 N.O. C 9 COM Imax = 50mA PLC DIGITAL INPUT N DIGITAL INPUT 2 DIGITAL INPUT 1 REF PLC Imax 8 N.O. 9 COM Imax = 50 ma Connection to an User AC or DC Power User 8 N.O. C 9 COM Imax = 50mA AC or DC Power User 8 N.O. 9 COM Imax = 50mA 8

Connection to an User +V Imax External Relay N.C. COM N.O. N.O. COM 8 9 Imax -V V= 12-24 VAC/VDC Imax = 50 ma The alarm is off during normal operation and goes ON according to Relay setting. If Imax > 50 ma use external Relay Connection to other FLS Instruments FLS monitor terminals 7 V+ 6 FREQ IN 5 GND 6B DIR 8 9 N.O. COM RELAY WIRING DIAGRAM The alarm is OFF during normal operation and goes ON according to Relay settings The alarm is ON during normal operation and goes OFF according to Relay settings RELAY 1 AC or DC Power Alarm 10 11 12 NC COM NO D AC or DC Power Alarm RELAY 1 10 NC 11 COM 12 NO D 9

OPERATIONAL OVERVIEW The M9.02 flow monitor and transmitter features a full graphic display and a five-button keypad for system set-up, calibration and operation. Full graphic display has a white backlight during standard conditions, a red backlight in case a set alarm is activated (MAX, MIN, WINDOW MODE; always with priority), a green backlight in case a external device control is activated (PULSE MODE). MENU DIRECTORY Settings Calibration VIEW LEVEL Outputs Rate Rate - Infinite Totalizer(S) Rate - Resettable Totalizer(S) Options Rate - Analog Output Item Code - Software Release Resettable totalizers can be reset using on view level Setting view 10

MENU LEVEL Installation Data Unit Volume Unit Correction Factor Auto Calibration 1 SSR 2 SSR 3 RELAY 4-20 ma Test Output Language Filter Backlight Rate Decimal Point Password Asec Bi-Directional Default Data Custom Calibration Contrast Outputs Activation Sensor Type Pipe Parameter Standard Pipe Pipe Diameter Internal Diameter EDIT LEVEL PUSH BUTTON to modify an item to scroll right to return to Menu without saving to save new settings K-Factor 11

OUTPUT MODE The M9.02 flow monitor and transmitter features 2 solid state relays and 1 mechanical relay in addition to an analog output 4-20mA. PROCEDURE FOR OUTPUTS SETTING - go to the Options menu - enter into the Outputs activation sub menu - enable output(s) - go to the Outputs menu - set the operating mode for each enabled output Monitor without digital output activated In case a digital output is enabled, a icon will appear In case a digital output is set, icon reports the operating mode In case set digital output is activated, the icon will turn to black (display turns green in case output is set to manage an external device, red to indicate a activated output as alarm) 12

Digital outputs can be set in the following way: MIN MODE (icon reports MIN) MAX MODE (icon reports MAX) Hysteresis Setpoint Setpoint Hysteresis Output relaxed Output energized Time Output relaxed Output energized Time WINDOW MODE (icon reports WDW) PULSE MODE (icon reports PLS) Setpoint Pulse duration Pulse duration Pulse duration Hysteresis Hysteresis Setpoint Output relaxed Output energized Time Volume Volume Volume Output relaxed Output energized 13

ORDERING DATA Part No. Description /Name Power supply Wire power Technology Sensor Input Output M9.02 Monitor M9.02.P1 Panel mount Monitor M9.02.W1 Wall mount Monitor M9.02.W2 Wall mount Monitor 110-230 VAC 3/4 wire M9.02.01 Monitor M9.02.02 Monitor M9.02.03 Monitor M9.02.04 Monitor M9.02.05 Monitor M9.02.06 Monitor 14

Part No. Description /Name Power supply Wire power Technology Sensor Input Output M9.02.07 Monitor M9.02.08 Monitor M9.02.09 Monitor M9.02.10 Monitor M9.02.11 Monitor M9.02.12 Monitor M9.02.13 Monitor M9.02.14 Monitor M9.02.15 Monitor M9.02.16 Monitor 15

ACCESSORIES Part No. Name Description F6.KC1 M9.KW1 M9.KW2 Compact mounting kit Wall mounting kit Wall mounting kit with power supply Plastic adapter with compact cap and locking nut (for M9.02 only) 144x144mm plastic box for wall installation of all panel mount monitors 144x144mm plastic box and 110/230VAC to 24 VDC power supply for wall installation of all panel mount monitors SPARE PARTS Part No. Name Description M9.SP4.1 PG 11 PG 11 complete cable gland (2 o-rings and cap) M9.LN1 Locking nut Plastic locking nut for M9.02 16 FIP - Formatura Iniezione Polimeri S.p.A. Loc. Pian di Parata 16015 Casella Genova - Italy Tel. +39 010 96211 Fax +39 010 9621209 www.flsnet.it IMM902E 05-2014