i-3 Control Technology Submittal Guide www.usa.siemens.com/i-3
Contents P1 Series Lighting Panel 4-6 i-3 Controller 7 SIPOD specifications 7-8 Inputs and Communications 9 Protocol Connections System Connections 10 Typical Application 11 Emergency Lighting Circuits 12
The simple, cost-effective lighting control that reduces energy costs. The Siemens i-3 is integrated in a standard P1 series lighting panelboard. It leverages the latest Microsoft Windows technology to incorporate an innovative touch screen System Controller. i-3 can be commissioned locally via the touch screen or with an off line (computer) software configuration tool. The configuration file is transferred to the system using a standard USB interface without factory involvement. Whether mounted individually or in an IPS Switchboard, Siemens i-3 provides faster installation, smaller footprints, and easier commissioning, at lower cost.
i-3 Control Technology P1 Series Lighting Panel P1 Lighting Control Panel with i-3 Control Technology Main Breaker: 250A Max. Main Lugs Only: 250A Max. 480Y/277V Maximum 3x 4W Specifications General: i-3 Lighting Control Panels comply with the following standards: - UL 50 Enclosures - UL 67 Panelboards - UL 916 Energy Management - UL 489 Breakers - CA Title 24 Date: Quote #: Job Name: Panel Description: Note: You have requested access to specifications from documents that are writable and amendable by the user. As a result the user-modified document may present technical variances or discrepancies from Siemens Energy & Automation, Inc. s (the Company ) actual product capabilities. User understands this risk and acknowledges that specifications are subject to review and approval by the Company prior to order acceptance. The Company does not accept any responsibility for amendments, modifications, deletions or charges made to these documents by the user without review and approval by qualified Company representatives. Operating Conditions: - Operating: 23 F to 104 F (-5 C to 40 C) - Storage: -13 F to 158 F (-25 C to 70 C) Controllers: I/O and System: - I/O Mapping - Configurable Zones - 20 Schedules (System Controller Only) - LCD Touchscreen (System Controller Only) - USB Interface (System Controller Only) Protocols: - Modbus RTU - Modbus TCP/IP - EIB - BACnet MSTP (only for integration with SBT APOGEE) I/O: - Up to 32 2-wire or 16 3-wire digital inputs - Up to 2 analog inputs and 2 analog outputs SIPODS: - 15, 20, 25 and 30 amp 1 Pole and 2 pole - UL 489 circuit breaker accessory - Rated for 500,000 operation at full load - Same short circuit ratings as BQD breaker BQD Circuit Breaker Interrupting Ratings System Voltage (AC) 120V 240V 277V 480Y/277V 1-p 15A, 20A, 25A, 30A 65kA - 14kA - 2-p 15A, 20A, 25A, 30A - 65kA - 14kA Main Lug Gutter Amp Rating End Gutter (Inches) 125 10.50 11.50 250 10.50 11.50 Neutral Location (Inches) Branch Breaker Side Gutter Branch Breakers BQD + SIPOD Combo 3.25 BQD 5.50 BL 6.375 Wiring Space (Inches) 4
i-3 Control Technology P1 Series Lighting Panel Features J i-ntegration - Reduced electrical room size - Reduced total installation cost - Small foot print - up to 2 panels of 42 circuits in one section of IPS J i-nstallation - For use in new and existing Siemens installations - Reduced wiring complexity over traditional systems - Fits standard P1 lighting panelboard enclosures - Reduced labor costs J i-nterface - Dry-contact, Modbus, EIB, and Analog - USB interface - Commissioning wizards - Touch panel J P1 Panel Size - 18 Circuits - 30 Circuits - 42 Circuits J Service Information - 3 ph/4-w, 480Y/277V AC, 208Y/120V AC - 1 ph/3-w, 120/240V AC - Up to 250A J System is UL 916 listed J Panel is UL 67 listed J Panel enclosure is UL 50 listed Note: This device/system may only be set up and used in conjunction with the instruction manuals. Installation, maintenance and operation of this device/system may only be performed by qualified personnel. Within the context of these instructions, qualified persons are defined as persons who have the skills and knowledge related to the construction and operation of the electrical equipment and installations and have received safety training to recognize and avoid the hazards involved. 5
S,KXKDDKCKMV,,HV,, JSKKJXISDKKKXKX XMCKJCHJUEIER WMKCK SIEMENS ;F,RKKVC,XMC CMVNVHFJHJ DKDCVIFKKFK DLCVOOOOORKK i-3 Control Technology Components Layout MLO/Main Breaker Space Enclosure Mounting Hole (4X) BQD Breaker Data Rail SIPOD Data Rail Ribbon Cable Class 2 Wire Barrier CONTROL TECHNOLOGY Class 2 Wire Barrier Neutral Extension Neutral Extension Ground Bar Controller 6
i-3 Control Technology i-3 Controller 1 4 5 F Features J I/O Controller - Dry-contact inputs - Modbus RTU - Modbus TCP/IP - I/O mapping and outupt groups - Analog inputs - Fluorescent dimming J System Controller - USB interface - Dry-contact inputs - Modbus RTU and TCP/IP - I/O mapping and output groups - Touch screen panel - Event scheduling and zoning - Basic setup (wizard driven) - Tools and override B C G 8 A Communication wiring access (through deadfront) B USB interface (remote configuration/local download) C Modbus protocols (RTU and TCP/IP) D Touch screen E Easy commissioning wizards F Event scheduling and zoning G Digital inputs (32 - two wire) H Analog inputs and outputs SIPOD The SIPOD is a UL 489 circuit breaker accessory for the Siemens BQD circuit breaker and assumes the short circuit rating of the circuit breaker. See BQD circuit breaker interrupter ratings. B CD System Interrupting Ratings (Amps RMS) Voltage 120V AC 240V AC 277V AC 480Y/277V AC 1-pole 15-20A 65,000-14,000-2-pole 15-20A - 65,000-14,000 A E F A Blow-closed mechanism B Manual override (for contact closing) C Maglatch mechanism D Extended life 500,000 + loaded operations E Same lug size as BQD circuit breaker F Integrated electronics 7
i-3 Control Technology The SIPOD SIPOD Manual Override 2-Pole SIPOD - 2-Pole BQD Breaker Assembly Manual Override Switch SIPOD 30 Amp device also available SIPOD Top View SIPOD Connection to Data Rail (Communications Bus) Manual Override SIPOD Load Lug SIPOD Connector Mechanical Status Indicator Tang/ Conductor Tab 8
i-3 Control Technology Inputs and Communications Protocol Connections TD B (+) TD A (-) RD B (+) RD A (-) GRND ModBus Connection Input Common Input q q q Input Common Input Low Voltage Switch Inputs Low Voltage Control Terminals 9
SIEMENS CONTROL TECHNOLOGY S,KXKDDKCKMV,,HV,, ;F,RKKVC,XMC JSKKJXISDKKKXKX CMVNVHFJHJ XMCKJCHJUEIER WMKCK DKDCVIFKKFK DLCVOOOOORKK i-3 Control Technology System Connections Layout System Controller I/O Board I/O Board I/O Board To next panel (Up to 8 panels total) Low voltage switch inputs Low voltage switch inputs Low voltage switch inputs Low voltage switch inputs Twisted pair, 18 AWG solid copper wire (Maximum total wire length 3,300 ft.) Twisted pair, 18 AWG solid copper wire with EIB connector (Recommended: Belden 6320) Low voltage switch inputs connector Building Automation System (ModBus Master) I/O Board I/O Board I/O Board I/O Board To next panel (Up to 247 panels total)* Low voltage switch inputs Low voltage switch inputs Low voltage switch inputs Low voltage switch inputs Modbus communications bus (22-18 AWG shielded copper wire) 10 Modbus and low voltage switch inputs connector *In groups of 32 or less I/O Controllers
i-3 Control Technology Typical Application Override Switch for after hours use. System can be set to turn the lights off after a specific time. It can also be set to blink the lights. Output to Lights Load wire connected to SIPOD breaker combination. Controller inside 11
i-3 Control Technology Emergency Lighting Circuits Application 12
Notes:
Notes:
Notes:
Siemens Industry, Inc. Building Technologies Division 5400 Triangle Parkway Norcross, GA 30092 1-877-757-5002 Ncssc.siemens@sylvania.com For literature and software downloads visit: www.usa.siemens.com/i-3 2010 Siemens Industry, Inc. Siemens is a registered trademark of Siemens AG. Product names mentioned may be trademarks or registered trademarks of their respective companies. Specifications are subject to change without notice. All rights reserved. LCIM-SUBMT-0310 Printed in USA www.usa.siemens.com/i-3