Acti 9 Communication System

Similar documents
MultiTech Router Commissioning for Com X 200/210/510

Smart Mode Measurements

Galaxy Shore Connection 500 kva. Operation 04/

5521 Potentiometer Analog Input Module

TeSys UASILUFC5 - ASILUFC51 AS-i Communication Module

How Can I. Integrate a Third-Party Modbus Device with PowerSCADA Expert? System Technical Note PowerSCADA Expert V1.0

EcoStruxure Power Commission Installation Guide

Change Report Colors and Logo

Ethernet Modbus X80 Gateway Device Type Manager

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

TeSys T LTM R EtherNet/IP with a Third-Party PLC Quick Start Guide

PowerLogic ION7550 RTU option

5504 Thermocouple Analog Input Module

Packaging User Guide for Temperature Control M221 Project Template

SCADAPack E Idec PLC Interface Manual

Schneider Electric AB DH485 Protocol XBT N/R/RT

SCADAPack E Target 5 DF1 PLC Interface

ARA Automatic Recloser

LXM32. Explanation for detected error E 733F. Expert Support Machine Solution

StruxureWare Power Monitoring 7.0

5401 and 5402 Digital I/O Modules

TeSys U LULC07 Profibus DP Communication Module

Acti 9 Smartlink IEC/EN Functions

Symmetra MW kw 380/400/480 V Operation. UPS System with External Bypass 01/

How can I. Implement a cost-effective energy monitoring system for small to medium buildings using Com'X 510?

5403 and 5404 Digital Input Modules

SCADAPack E ISaGRAF Quick Start Guide

EIO /2011. Magelis HMISTO501. Zelio/Millenium Driver 07/2011 EIO

SoMachine Scan for Buttons Linked to ZBRN Modules Harmony ZBRN Library Guide

StruxureWare. Power Monitoring Expert 8.2 Hierarchy Manager Help Topics 7EN /2017

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

Schneider Electric Floating License Manager

Conext CL-60 Inverter Firmware Upgrade Process

Installation Instructions

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic ION7300 Series

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

XPSMCMx Fieldbus Expansion Modules Instruction Sheet (Original Language)

TeSys U Communication Variables

Modicon Premium PLCs TSX CSY 84 / 85 / 164

Schneider Electric License Manager

Electrical network protection Sepam series 20 Sepam series 40 Quick start

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

Enerlin'X IFE Switchboard Server IFE/EIFE Ethernet Interface

Clipsal Bus Couplers. Two Channel (SLC5102BCLEDL) and Four Channel (SLC5104BCL) for Use with C-Bus Wired Systems

Unity Pro OSLoader User Manual

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

PowerLogic TM Series E4800 Multi-Circuit Meters. Configuration Guide

How Can I. Integrate a Third-Party DNP3 Device? System Technical Note PowerSCADA Expert V1.0

Installation Guide. QBox-V6. Standalone/Spare V6 SDI QBox. Standalone/Spare V6 SDI QBox. Part No. A

Serial PROFIBUS Interface

Masterpact MTZ Micrologic X Control Unit

Square D Clipsal Pascal Automation Controller

PowerLogic TM Series EM4800 Multi-Circuit Meters. Configuration Guide

DOCA0069EN 10/2016. Ecoreach Online Help. Version /2016 DOCA0069EN-04.

multisys User manual Technical parameters D2-MSMT-1 Gateway from Modbus TCP to Modbus RTU, serial RS _EDEBDA _EN

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016.

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

BCM ULP Breaker Communication Module

TSXCUSBMBP USB Modbus Plus Communications Adapter User Manual eng

Com X 210, Com X 510 Technical Datasheet

ULP System ULP (Universal Logic Plug) System User Guide

Altivar - Lexium. Option modules DANGER S1A S1A /8 VW3A3601 / VW3A3608 VW3A3616 / VW3A3627 VW3A3619 VW3A3720 VW3A3721 VW3M3308

DOCA0093EN-00 10/2015. ULP System. ULP (Universal Logic Plug) System User Guide 10/2015 DOCA0093EN-00.

Digital encoder interface module 5/12/24 V DANGER

Communication Interface

DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents

SCADAPack E 5405 Digital Input Hardware Manual

Operating instructions. Switching amplifier DN0210 DN / / 2015

Conext EasyConfig Tool

ACCESS 9340/9360 Meter Input/Output Module

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

Generator Performance Guide 7EN /2015

170 ADM to 60 VDC Module Base / 170 ADO Pt. Relay Out Module Base. Version 1.0

5502 Differential Analog Input Module

Installation Instructions

Multi-Loader. User manual 06/ BBV48778

SAFETY PRECAUTIONS CAUTION WARNING CAUTION. Thank you for purchasing ig5a Series Profibus Communication Module

Installation Quick Reference Guide. BACnet Alarm v1.0

Distributed Power System SB3000 Synchronous Rectifier &RQILJXUDWLRQDQG3URJUDPPLQJ

Source-Transfer Application Guide

Table of Contents Product Overview Before using the product Installation Procedure... 5

iem3100 series / iem3200 series

B63/ NS MS. EtherNet/IP LINK

5910 Ethernet Gateway Module

Security Quick Start Guide

Wiring Instructions for Replacement of 2301A Load Sharing and Speed Controls with 2301D Load Sharing and Speed Controls

Manual Version: V1.00. Video Decoder Quick Guide

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

Installation Guide Modbus TCP Module

DOCA0069EN 09/2014. Ecoreach Online Help. Version /2014 DOCA0069EN-00.

Modbus Plus to Ethernet Bridge 174 CEV User Guide

Assembly and Operating Instructions. M2 module for BDC-i440 control units

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Operating instructions. Speed monitor D / / 2014

Installation Guide EtherNet/IP Module

Galaxy VX. UPS System Operation 02/

Transcription:

Acti 9 Communication System Diagnostics User Manual 05/2012 DOCA0042EN-00 www.schneider-electric.com

This document contains general descriptions and/or general technical specifications of the products mentioned. It cannot be used to determine the suitability or reliability of these products for specific user applications. It is the responsibility of each user or integrator to conduct the appropriate risk analysis in full, assessing and testing products as regards the application in which they will be used and the execution of this application. Neither Schneider Electric nor any of its affiliated companies or subsidiaries can be held responsible for incorrect use of the information contained in this document. If you have any suggestions for improvements or correction, or have found errors in this publication, please notify us. No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission from Schneider Electric. All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to ensure compliance with documented system data, only the manufacturer should perform repairs to components. When equipment is used for applications with technical safety requirements, follow the relevant instructions. Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operation. Failure to follow this instruction can result in injury or equipment damage. 2012 - Schneider Electric. All rights reserved. 2 DOCA0042EN-00 05/2012

Table of Contents Safety Precautions... 4 About This Manual... 5 General Flow Chart.... 6 Case 1 - Problem on All Devices on an Acti 9 Smartlink... 8 Case 2 - Problem on Changes of State Only... 10 Case 3 - Reflex ic60... 12 Case 4 - RCA...14 Case 5 - iact24....16 Case 6 - iatl24...18 Case 7 - Kilowatt-Hour Meter... 20 Case 8 - Other Products... 22 DOCA0042EN-00 05/2012 3

Safety Precautions Important Information TICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of one of these symbols to a "Danger" safety label on a device indicates that an electrical hazard exists, which will result in death or personal injury if the instructions are not followed. This is the safety alert symbol. It warns you of a risk of physical injury. You must comply strictly with the safety instructions associated with this symbol to avoid injuring yourself or putting your life in danger. DANGER DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which could result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation which could result in minor or moderate injury. TICE TICE indicates practices that do not involve the risk of bodily injury. PLEASE TE Electrical equipment should be installed, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this equipment. A qualified person is one who has skills and knowledge related to the construction, operation and installation of electrical equipment, and has undertaken safety training in how to identify and avoid the hazards involved. 4 DOCA0042EN-00 05/2012

About This Manual At a Glance Aim of This Document This manual provides diagnostic assistance in the form of logic diagrams. Area of Application The Acti 9 communication system can be easily integrated into any building management architecture. It combines command and control functions and protection functions designed for energy efficiency solutions in any type of environment. Based on the Modbus master protocol, the Acti 9 communication system allows data to be exchanged with switchboards in real time. Monitoring and command and control are therefore possible for each circuit or load. This system's pre-wired connectors can save time and prevent wiring errors during installation. Reference Documents Document Title Reference Instruction sheet for the iact24 auxiliary for the ict contactor S1B33421 Instruction sheet for the iatl24 auxiliary for the itl remote control switch S1B33422 Instruction sheet for the Acti 9 Smartlink S1B33423 Instruction sheet for the RCA ic60 remote control S1A4079001 Instruction sheet for the Reflex ic60 integrated control circuit breaker S1A5784801 Instruction sheet for the iem2000t meter S1A8936401 Instruction sheet for the iem3100, iem3110, iem3115 meters S1B46581 Instruction sheet for the iem3150, iem3155 meters S1B46583 Instruction sheet for the iem3200, iem3210, iem3215 meters S1B46598 Instruction sheet for the iem3250, iem3255 meters S1B46602 Reference manual for the RCA ic60 remote control for ic60 circuit breakers A9MA01EN Reference manual for the Reflex ic60 integrated control circuit breaker A9MA03EN User manual for the PowerLogic EGX300 Ethernet gateway EGX 63230-319-216 User manual for the Acti 9 communication system DOCA0004EN Technical advice on the Acti 9 Smartlink device CA908033EN You can download these technical publications and other technical information from our website at www.schneider-electric.com. User Comments We welcome your comments about this document. You can reach us by e-mail at techpub@schneider-electric.com. DOCA0042EN-00 05/2012 5

Acti 9 Smartlink Diagnostics General Flow Chart Comments Checks to be performed first: the Modbus master is operative and sending requests Problem on all Acti 9 Smartlinks in a Modbus master loop? Problem on a single Acti 9 device connected to the Acti 9 Smartlink? Problem on changes of state only? Checks: bbconformity of the Modbus master wiring rules b bpresence of the Modbus master network 24 V DC power supply Case 1 diagnostics page 8 Case 2 diagnostics page 10 6 DOCA0042EN-00 05/2012

Reflex ic60? Case 3 diagnostics page 12 RCA? Case 4 diagnostics page 14 iact24? Case 5 diagnostics page 16 iatl24? Case 6 diagnostics page 18 Schneider Electric kilowatt-hour meter? Case 7 diagnostics page 20 Other products? Case 8 diagnostics page 22 7 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 1 - Problem on All Devices on an Acti 9 Smartlink No communication or communication fault between the Modbus master and one of the Acti 9 Smartlink slaves. Note: the other Acti 9 Smartlinks, on the same Modbus master line, are operational. Comments Checks to be performed first: bbcheck the connection between the Modbus master and Acti 9 Smartlink bbcheck that the 24 V DC power supply is powered up bbcheck presence of the master transmission master line "Status" LED on? Check the 24 V DC power supply circuit Voltage present at the Acti 9 Smartlink 24 V terminals? Set the thumbwheels to the chosen slave address GREEN "Status" LED color? ORANGE Slave address checked? "Status" LED on? "COM" LED active? "COM" LED flashing? 8 DOCA0042EN-00 05/2012

Auto-go running (slave auto-configuration sequences) Wiring conformity checks : b bmodbus master (screening shield, twisted wires) b bground, polarity, 2 or 4 wires for all slaves, matching, etc. End of the Auto-go sequence? Brought into conformity? Communication established? One of the Acti 9 Smartlink channels is short-circuited or overloaded Intermittent loss of communication? Disconnect the pre-wired connectors individually one after another to identify the faulty channel Probable causes: EMC Probable causes: bblightning strike bb230 V on 24 V DC circuit bbemc Checks: conformity of the Modbus wiring rules (ground, polarity, 2 or 4 wires for all slaves, matching, etc.) Disconnection of channel x "Status" LED green? Have all the channels been disconnected? Consider replacing the Acti 9 Smartlink Find and eliminate the causes OK 9 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 2 - Problem on Changes of State Only Problem with an Acti 9 device connected to the Acti 9 Smartlink: changes of state not seen by the Modbus master. Note: products connected on the other channels are working. Comments Devices with 230 V AC power supply Devices without power supply Reflex ic60 iact24 iatl24 RCA iof+sd24 for ic60, iid, ARA, RCA OF+SD24 for C60, C120, DPN Checks to be performed first: bbcheck that the pre-wired connector is in place bbcheck that the link between the auxiliary and its product is working Device requiring a 230 V power supply? Device supplied with 230 V? Check the power supply circuit and whether the 230 V AC power supply is present at the terminals Check and consider replacing the pre-wired connector 10 DOCA0042EN-00 05/2012

Changes of state seen by the Modbus OK Consider replacing the device Consider that the Acti 9 Smartlink channel may be faulty 11 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 3 - Reflex ic60 Problem with an Reflex ic60 connected to the Acti 9 Smartlink: the Reflex ic60 cannot be controlled remotely master. Note: products connected on the other channels are working. Comments Checks to be performed first: bbcheck that the pre-wired connector is in place bbcheck the mode configured on Reflex ic60 bbcheck that it is consistent with the control circuit diagram Is the Reflex ic60 powered up? (LED on) Reclose the Reflex ic60 (handle on Auto) Check the 230 V AC control circuit power supply is present Is the handle on the Reflex ic60 on Auto? Overheat protection active. Wait for automatic restarting Is the Reflex ic60 powered up? (LED on) Consider replacing the Reflex ic60 Is the LED on the Reflex ic60 flashing red? Is from the PB on the front panel? 12 DOCA0042EN-00 05/2012

Alter the mode selected on the Reflex ic60 The configured mode is consistent with the control diagram? Check the wiring and position of the external switch "central-local" Is the Reflex ic60 in mode 3? Is input Y1 powered up? Is Consider replacing the Reflex ic60 Check and consider replacing the pre-wired connector Is Is OK Consider that the Acti 9 Smartlink channel may be faulty 13 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 4 - RCA Problem with an RCA connected to the Acti 9 Smartlink: the RCA cannot be controlled remotely master. Note: products connected on the other channels are working. Comments Checks to be performed first: bbcheck that the pre-wired connector is in place b bcheck that the mode configured on the RCA is consistent with the control circuit diagram Set the RCA switch to Auto Is the RCA powered up? (LED on) Check the 230 V AC control circuit power supply is present Is the RCA on Auto (switch)? Is the RCA powered up? (LED on) GREEN Color of the RCA LED? ORANGE Slowly RCA LED flashing? Quickly Overheat protection active. Wait for automatic restarting Mode 3 selected? On B The RCA inhibitor switch is? On A Check the wiring and position of the external switch "central-local"!! Control impossible if the circuit breaker has opened due to an electrical fault!! 14 DOCA0042EN-00 05/2012

Is the switch on central? Is local control possible? Is Check and consider replacing the pre-wired connector Is Consider replacing the RCA Is OK Consider that the Acti 9 Smartlink channel is faulty 15 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 5 - iact24 Problem with an iact24 connected to the Acti 9 Smartlink: the contactor cannot be controlled remotely master. Note: products connected on the other channels are working. Comments Checks to be performed first: bbcheck that the pre-wired connector is in place bbcheck that the yellow clips are in place on the iact24 and the ict bbcheck that the local control diagram is consistent with central control Voltage present on the Ph/N terminals? Check the position of the external switch AUTO - ON - OFF Check the 230 V AC control circuit power supply Voltage present on Y1? Contactor version with manual control? Set the contactor manual control to Auto Is the contactor manual control set to Auto? 16 DOCA0042EN-00 05/2012

Is Is local control possible? Check and consider replacing the pre-wired connector Is Consider replacing the iact24 (+ ict) Is OK Consider that the Acti 9 Smartlink channel may be faulty 17 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 6 - iatl24 Problem with an iatl24 connected to the Acti 9 Smartlink: the contactor cannot be controlled remotely master. Note: products connected on the other channels are working. Comments Checks to be performed first: bbcheck that the pre-wired connector is in place bbcheck that the yellow clips are in place on the iatl24 and the itl bbcheck that the local control diagram is consistent with central control Check the external switch position AUTO - ON - OFF Voltage present on the Ph/N terminals? Check the 230 V AC control circuit power supply Voltage present on Y1? Remote control switch version with AUTO-OFF switch? Set the remote control switch AUTO-OFF switch to Auto Is the remote control switch AUTO-OFF switch set to Auto? 18 DOCA0042EN-00 05/2012

Is Is local control possible? Check and consider replacing the pre-wired connector Is Consider replacing the iatl24 (+itl) Is OK Consider that the Acti 9 Smartlink channel may be faulty 19 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 7 - Kilowatt-Hour Meter Problem with a Schneider Electric kilowatt-hour meter connected to the Acti 9 Smartlink: bbno meter changes seen by the Modbus master. bbthe meter value does not match the estimate. Note: products connected on the other channels are working. Comments Checks to be performed first: bbcheck that the pre-wired connector is in place bbcheck the control circuit power supply is active Schneider Electric meters iem2000t iem2010 iem3110 iem3155 iem3210 iem3255 Voltage present on the Ph/N terminals? Check the 230 V AC control circuit power supply Meter changes on the front panel? (LED) Check the wiring and the load consumption on metered circuit Is current flowing through the metered circuit? 20 DOCA0042EN-00 05/2012

Meter changes on the front panel? (LED) Meter changes seen by the Modbus Check and consider replacing the pre-wired connector Meter changes seen by the Modbus Consider replacing the kilowatt-hour meter Does the meter value match the estimated value? Meter changes seen by the Modbus Check that the pulse weight is correctly configured Consider that the Acti 9 Smartlink channel may be faulty OK 21 DOCA0042EN-00 05/2012

Acti 9 Smartlink Diagnostics Case 8 - Other Products Problem with a device not equipped with a Ti24 interface connected to the Acti 9 Smartlink (Schneider Electric or third-party products) Note: products connected on the other channels are working. Comments Checks to be performed first depending on device configuration: check that the link between the auxiliary and its product is working. Device requiring an auxiliary power supply (230 V, 24 V, etc.) Device powered up? Check the power supply circuit and whether the auxiliary voltage is present Changes of state seen by the Modbus Check the input circuit wiring 22 DOCA0042EN-00 05/2012

Is remote Check the control circuit wiring at the Acti 9 Smartlink output OK 23 DOCA0042EN-00 05/2012

DOCA0042EN-00 Schneider Electric Industries SAS 35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex www.schneider-electric.com Owing to changes in standards and equipment, the characteristics given in the text and images in this document are not binding until they have been confirmed with us. 05/2012