FSIR-100 Wireless IR Commissioning Tool User Guide CONTENTS Using The FSIR-100 Commissioning Tool... 1 Batteries... 1 Navigation... 2... 2 IR Communication... 2 Screens... 3 Home Menu...3...3...5...5 s...6 HBP-111... 7 HBP-111 Screens... 8 Home Menu...8...8...9...10 Load Toggle...10...10 Troubleshooting...10 USING THE FSIR-100 COMMISSIONING TOOL The FSIR-100 Wireless IR Commissioning Tool is a handheld tool for changing defaults and testing of WattStopper devices.it provides wireless access to the devices for parameter changes and testing. The FSIR-100 display shows menus and prompts to lead you through each process. The navigation pad provides a simple way to navigate through the customization fields. Within a certain mounting height of the sensor, the FSIR- 100 allows modification of the system without requiring ladders or tools; simply with a touch of a few buttons. The FSIR-100 IR transceiver allows bi-directional communication between the device and the FSIR-100 commissioning tool. Simple menu screens let you see the current status of the sensor and make changes. It can change device parameters such as high/low mode, sensitivity, time delay, cut off and more. With the FSIR-100 you can also establish and store device parameter profiles. BATTERIES The FSIR-100 operates on three standard 1.5V AAA Alkaline batteries or three rechargeable AAA NiMH batteries. The battery status displays in the upper right corner of the display. Three bars next to BAT= indicates a full battery charge. A warning appears on the display when the battery level falls below a minimum acceptable level. To conserve battery power, the FSIR-100 automatically shuts off 10 minutes after the last key press. If communication is not successful, (if possible) move closer to the sensor. If still not successful, there may be too much IR interference from other sources. Programming the unit at night when there is no daylight available may be the only way to communicate with the sensor.
5E4 NAVIGATION Navigate from one field to another using (up) or (down) arrow keys. The active field is indicated by flashing (alternates) between yellow text on black background and black text on yellow background. Power On/Off HBP-111 BAT= IR tx/rx IR COMMUNICATION IR communication can be affected by the mounting height of the sensor and high ambient lighting such as direct daylight or electric light such as floodlights, and some halogen, fluorescent lamps, LED s. When trying to communicate with the device, be sure to be positioned under the sensor without any obstructions. Every time the commissionng tool establishes communication with the device, the controlled load will cycle. Back Left Down Home/Main Menu Up Right/Next 15'-30' Once active, use the button to move to a menu or function within the active field. Value fields are used to adjust parameter settings. They are shown in less-than/ greater-than symbols: <value>. Once active, change them using(left) and(right) arrow keys. The right key increments and the left key decrements a value. ions wraparound if you continue to press the key beyond maximum or minimum values. Moving away from the value field overwrites the original value. The Home button takes you to the main menu. The Back button can be thought of as an undo function. It takes you back one screen. Changes that were in process prior to pressing the key are lost. * Distance may vary depending on the lighting environment Occupancy Sensor LOAD 14-18 AWG Solid CU Wire Only High/Low PIR 230 VAC, 50 Hz 1200W max ballast LINE NEUT 800.879.8585 www.wattstopper.com Class 2 Wiring Only 18-20 AWG Solid CU Wire Only GRND DIM- (grey) DIM+ (violet) 15195r1 The is a motion sensor that dims lighting from high to low based on movement. This slim, low-profile sensor is designed for installation inside the bottom of a light fixture body. The PIR lens module connects to the through a 1.30 diameter hole in the bottom of the fixture. The sensors use passive infrared (PIR) sensing technology that reacts to changes in infrared energy (moving body heat) within the coverage area. Once the sensor stops detecting movement and the time delay elapses lights will go from high to low mode and eventually to an OFF position if it is desired. Sensors must directly see motion of a person or moving object to detect them, so careful consideration must be given to sensor luminaire placement and lens selection. Avoid placing the sensor where obstructions may block the sensor s line of sight. Call 800-879-8585 for Technical Support
COMPONENTS PIR Sensor Light Sensor IR Transmitter Motion Indicator Red LED IR Receiver SCREENS Home Menu High Mode HBP-111 BAT = The Home (or Main) menu displays after the powerup process completes. It contains information on the battery status and sensor menu choices. the up or down buttons to highlight the desired sensor then press. the Left/Right Arrow to Increase or Decrease Volts When the sensor detects motion the dimming control output ramps up to the selected HIGH light level (default is 10V). Range: 0 V to 10 V Increments: 0.2 V To program the with the selected parameters go to and press the button. The controlled load should cycle once the sensor is updated. Low Mode s allow you to select the different sensor parameters such as: High/ Low Mode, Time Delay, Cut Off, Sensitivity, Setpoint and Ramp/Fade rates. the Left/Right Arrow to Increase or Decrease Volts After the sensor stops detecting motion and the time delay expires the dimming control output fades down to the selected LOW light level (default is 1V). Range: OFF, 0 V to 9.8 V Increments: 0.2 V Visit our web site for FAQs: www.wattstopper.com
Time Delay the Left/Right Arrow to Raise or Lower Time Delay Cut Off the Left/Right Arrow to Increase or Decrease Cut Off Sensitivity the Left/Right Arrow to Increase or Decrease Sensitivity Hold Off Setpoint the Left/Right Arrow to Increase or Decrease Setpoint The time period that must elapse after the last time the sensor detects motion for the lights to fade to LOW mode (default is 5 min). Range: 30 sec, 1 min to 30 min Increments: 1 min The time period that must elapse after the lights fade to Low Mode and the sensor detects no motion for the lights to turn OFF (default is 1 hour). Range: Disable (No cut off, lights will stay in low mode) 1 min to 59 min, 1 hr to 5 hr (press and hold should cause to move faster through the increments) Increments: 1 min or 1 hr The response of the PIR detector to motion within the sensor s coverage area (default is max). Range and Sequence: On-Fix, Off-Fix, Low, Med, Max (On-Fix: relay closed, occupancy detection disabled; Off-Fix, relay open, occupancy detection disabled. The selectable ambient light level threshold that will hold the lights off or at LOW level when the sensor detects motion (default is Disable). Range: Auto, Disable, 1 fc to 250 fc Increments: 1 fc (press and hold should cause to move faster thru the increments) Sequence: Disable, 1 fc to 250 fc The Auto option invokes an automatic calibration procedure to establish an appropriate setpoint based upon the contribution of the electric light. As part of this procedure, the controlled load is turned on to warm up the lamp, and then it is switched off and on eight times, terminating in an off state. After this process, a new setpoint value is automatically calculated. During this time, communication to the is disabled. Next Time Delay: <30 Sec> to View More Settings Ramp Up PRIOR SAVE Fade Down Photocell On/Off Time period for light level to increase from LOW to HIGH (default is Disable; light/load switches instantly). Range: Disable, 1 sec to 60 sec Increments: 1 sec Time period for light level to decrease from HIGH to LOW (default is Disable; light/load switches instantly). Range: Disable, 1 sec to 60 sec Increments: 1 sec When the light level exceeds this setting, the lights will turn off even when the space is occupied. Once the light level exceeds this setting, the sensor will wait and monitor for a short period of time in order to confirm the light level increase is not temporary before forcing the lights to go off. When light level goes below the settings, the light will turn on even without motion detection. This feature is disabled by default. If using this setting in combination with the Hold Off setpoint, there must be at least 10fc of dead band between the two settings. The Photocell setpoint is automatically set to maintain at least 10fc of dead band above the Hold Off setpoint to help avoid load cycling. Prior the Left/Right Arrow to Increase or Decrease Sec PRIOR SAVE the Left/Right Arrow to Increase or Decrease Sec PRIOR SAVE the Down Arrow to PRIOR PRIOR SAVE To view more settings go to and press the button To go back to previous settings go to PRIOR and press the button. Call 800-879-8585 for Technical Support
Send PRIOR SAVE the Down Arrow to To program the with the selected parameters go to and press the button. The controlled load should cycle once the sensor is updated. Light Level Light Level: <15> Displays the light level at the. The light level reading can be used as a reference for setpoint adjustments. Save To Save these New Settings parameters as one of the profiles go to SAVE and press the button. Done Light Level: <15> To go to the Home screen go to DONE and press the button. the Down Arrow to SAVE the Down Arrow to DONE Save Parms Save Parms Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Profile 6 Cancel the Up/Down Arrow to Profile s shortens timeouts for High/Low and Cut Off, to allow quick verification of settings. disables automatically after 5 minutes. R ecall Profiles Current Settings Point to desired Occupancy Sensor Point and allow you to recall the parameters for a specific sensor. These are read only parameters. View High Mode: Low Mode: Time Delay: Sensitivity: <10 Volts> <1 Volts> <5 Min> <Max> DONE Highlight and press to view the Current Settings. Enable/Disable Enable the Left/Right Arrow to Enable or Disable Disable has been enabled. to View More Settings Light Level: Dis Dis 15 Dis To go back to previous settings go to PRIOR and press the button. the Down Arrow to PRIOR Visit our web site for FAQs: www.wattstopper.com
s s s s allow the user to select the saved parameter profiles. This feature is used when programming multiple s with the same parameters. Lock Settings IR communication locks to prevent unauthorized changes of parameters. R ecall Profiles To view more sensor configuration settings go to and press the button. Recall Parms Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Profile 6 Cancel the Up/Down Arrow to a Specific Profile Time Delay: <30 Sec> ing a specific profile allow the user to also change the parameters such as: High/Low Mode, Time Delay, Cut Off, Sensitivity, Setpoint and Ramp/Fade rates. Lock Settings PRIOR Lock Settings Lock Delay <Disable> default settings communicate with the FSIR-100; however, this security feature limits communication only for authorized installers who have access to main power supply to the sensor. to set Lock Delay or press PRIOR to go back. PRIOR the Left/Right Arrow to Disable or set Lock Delay time Factory default Lock Delay setting is disabled and parameter can change with any FSIR-100 at anytime. To enable Lock Delay with time, select lock delay time and press to set delay time in the. Its parameter changes with the FSIR-100 will be locked after the specified timer expires from the last message. At the end of the specified time the will be locked unless there is a power cycle. Any locked sensor needs power cycling to initiate any commissioning through the FSIR-100. To permanently disable Lock Delay after power cycling, select Disable and press. Range: 10 min - 240 min Increments: 1 min Lock Settings Lock Delay <10 min> Highlight and press to enable lock settings. PRIOR SENSOR IS LOCKED This screen will appear if the is locked. If it is locked, cycle the power. Call 800-879-8585 for Technical Support
HBP-111 The HBP High Bay Passive Infrared (PIR) Occupancy Sensor consists of two components. These components were developed to work as a convenient system and include both sensor and lens modules. HBP-111 sensor is designed for automatic lighting control in warehouses and other indoor high bay spaces. The lens is specifically engineered to provide reliable coverage from a wide range of mounting heights. Time Delay and Light Level settings for the HBP sensor can be adjusted via trimpots designated for each. The HBP-111 can also be commisioned remotely using a wireless configuration tool. The HBP occupancy sensor is designed to mount directly to a light fixture and control the load in the fixture. It can be wired to control all ballasts in the fixture. When motion is detected within the sensor s coverage area, the relay in the sensor closes, and lighting loads are automatically turned on. When motion is no longer detected for the duration of the time delay setting, the relay opens and the lighting load is turned off. The sensor s light level hold-off and time delay settings are factory preset at 300 foot candles and 15 minutes, respectively, which are suitable for most high bay applications. COMPONENTS PIR Sensor (do not touch) Push Button IR Transmitter IR Receiver Detection Indicator LED Light Level Adjustment Trimpot Time Delay Adjustment Trimpot Visit our web site for FAQs: www.wattstopper.com
HBP-111 SCREENS Home Menu HBP-111 HBP-111 BAT = The Home (or Main) menu displays after the powerup process completes. It contains information on the battery status and sensor menu choices. the up or down buttons to highlight the desired sensor then press. On Set point On Set point: Burn-In Mode: Walk-through: Visual Alert: the Left/Right Arrow to Increase or Decrease Set point The selectable ambient light level threshold that will hold the lights off when the sensor detects motion (default is 300 fc). Range: Disabled, 1 fc to 300 fc Increments: 1 fc (press and hold should cause to move faster thru the increments) Default: Disabled HBP-111 Configuration Load Toggle Time Delay Time Delay: Sensitivity: On Set point: Burn-In Mode: Walk-through: Visual Alert: <15 Mins> <Max> the Left/Right Arrow to Raise or Lower Time Delay Sensitivity Time Delay: Sensitivity: On Set point: Burn-In Mode: Walk-through: Visual Alert: the Left/Right Arrow to Increase or Decrease Sensitivity <15 Mins> <Max> allow you to select the different sensor parameters such as: Time Delay, Sensitivity, On Set point and Burn-In Mode. The time period that must elapse after the last time the sensor detects motion for the lights (default is 15 min). Range: 1 min to 30 min Increments: 1 min To program the HBP-111 with the selected parameters go to and press the button. The controlled load should cycle once the sensor is updated. The response of the PIR detector to motion within the sensor s coverage area (default is max). Range and Sequence: Low, Med, Max Burn-In Mode On Set point: Burn-In Mode: Walk-through: Visual Alert: the Left/Right Arrow to Enable or Disable Burn-In Walk-through Mode On Set point: Burn-In Mode: Walk-through: Visual Alert: the Left/Right Arrow to Enable or Disable Walk-through Visual Alert On Set point: Burn-In Mode: Walk-through: Visual Alert: the Left/Right Arrow to Enable or Disable Visual Alert When burn-in is enabled, the light load will turn On for 100 hours and remain on regardless of occupancy. The push button on the HBP-111 can be used to toggle the load and exit burn-in mode. The FSIR-100 can also be used to exit burn-in mode. Default: Disabled Walk-through mode provides a 3 min time delay for applications where occupancy is brief, such as a copy room, closet, etc. When enabled, if no activitity is detected after the first 30 sec from initial trigger, the sensor will turn the load off 3 min after the initial detection. If there is activity after the first 30 sec, the sensor will use the set time delay. Once the time delay has expired, the sensor will revert to using the standard walk-through mode time delay Default is Off. The sensor will toggle the load for 1 sec alerting the occupant that the set time delay will be reached within 1 min and turn the lighting off. This provides a visual indication so that the occupant can keep the lights on by moving within the coverage area if the space will still remain occupied. Default is Off. Call 800-879-8585 for Technical Support
Next On Set point: Burn-In Mode: Walk-through: Visual Alert: the Left/Right Arrow to go to more settings Service Mode Service Mode: <Dis> PRIOR SAVE the Left/Right Arrow to Enable or Disable Occupancy Mode To view more settings go to and press the button In Service Mode, motion detection is disabled. If you enable Service Mode, loads must be turned ON and OFF manually. When disabled (the default), the sensor functions normally. HBP-111 Configuration Load Toggle Current Settings Point to desired Occupancy Sensor Point and allow you to recall the parameters for a specific sensor. These are read only parameters. View On Set point: Burn-In Mode: Walk-through: Visual Alert: Highlight and press to view the current settings. Prior Service Mode: <Dis> To go back to previous settings go to PRIOR and press the button. the Left/Right Arrow to go to more settings Light Level PRIOR SAVE the Down Arrow to PRIOR Send Save Service Mode: <Dis> PRIOR SAVE the Down Arrow to Service Mode: <Dis> PRIOR SAVE To program the HBP-111 with the selected parameters go to and press the button. The controlled load should cycle once the sensor is updated. To Save these New Settings parameters as one of the profiles go to SAVE and press the button. Service Mode: <Dis> Light Level: <200> Done Service Mode: <Ena> Light Level: <200> the Down Arrow to DONE Presents light level to the HBP-111. The light level reading can be used as a reference for setpoint adjustments. To be able to Save these parameters as one of the profiles go to SAVE and press the button. To be able to go to the HBP-111 Home screen go to DONE and press the button. the Down Arrow to SAVE Save Parms Save HBP-111 Parms Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Profile 6 Cancel the Up/Down Arrow to Profile Visit our web site for FAQs: www.wattstopper.com
HBP-111 Configuration Load Toggle Enable/Disable HBP-111 ENABLE the Left/Right Arrow to Enable or Disable Load Toggle DISABLE HBP-111 Configuration L oad Toggle Point to desired Occupancy Sensor shortens the time delay to allow quick verification of HBP coverage for motion detection. disables automatically after 10 minutes. has been enabled. Used to turn the load ON and OFF from the FSIR-100. When occupancy mode is disabled, the light will remain ON or OFF depending on the last state. Options: ON, OFF Default: ON TROUBLESHOOTING Problem: Display does not come on when I press the Power On Button. Make sure the batteries are installed correctly. Make sure batteries are good. Problem: No Response Screen appears: No response from device Make sure that the device is not obstructed and try again. Move closer to the device. The angle may be too high, move closer so that you are directly underneath the sensor. If still not successful, there may be too much IR interference from other sources. Programming the unit at night when there is no daylight available may be the only way to communicate with the sensor. Make sure you are using the FSIR-100 and not the LMCT-100. Make sure the device is within range. Make sure the device you are pointing at is powered. For other issues not related to communication, consult the appropriate installation instructions or contact Technical Support at 800.879.8585. Point and HBP-111 Configuration L oad Toggle R ecall Profile Recall HBP-111 Parms Profile 1 Profile 2 Profile 3 Profile 4 Profile 5 Profile 6 Cancel the Up/Down Arrow to a Specific Profile s allow the user to select the saved parameter profiles. This feature is used when programming multiple HBP-111 s with the same parameters. High Mode: Low Mode: Time Delay: Sensitivity: Call 800-879-8585 for Technical Support
WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation. 2800 De La Cruz Boulevard, Santa Clara, CA 95050 800.879.8585 www.wattstopper.com 19071r2 3/2015 Please Recycle