Cover sheet System Architectures With SIMATIC PCS 7/OPEN OS SIMATIC PCS 7 Application Description November 202 Applications & Tools Answers for industry.
Siemens Industry Online Support This document originates from the Siemens Industry Online Support. The following link takes you directly to the download page of this document: http://support.automation.siemens.com/ww/view/en/49740087 Notice: The functions and solutions described in this document are mainly limited to the realization of the automation task. In addition, please note that suitable security measures in compliance with the applicable Industrial Security standards must be taken, if your system is interconnected with other parts of the plant, the company's network or the Internet. More information can be found under the entry ID 50203404. http://support.automation.siemens.com/ww/view/en/50203404 Copyright Siemens AG 202 All rights reserved For further information on this topic, you may also actively use our Technical Forum in the Service & Support Portal. Share your questions, suggestions or problems and discuss them with our strong forum community: http://www.siemens.de/forum-applications 2.0, Entry ID: 49740087
s Basic Systems Redundant Systems 2 PCS 7 Systems With PCS 7/OPEN OS 3 SIMATIC PCS 7 Internet Links 4 History 5 Copyright Siemens AG 202 All rights reserved.0, Entry ID: 49740087 3
Warranty and Liability Warranty and Liability Note The application examples are not binding and do not claim to be complete regarding configuration, equipment and any eventuality. The application examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. These application examples do not relieve you of your responsibility to use sound practices in application, installation, operation and maintenance. When using these application examples, you recognize that we will not be liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these application examples at any time without prior notice. If there are any deviations between the recommendations provided in this application example and other Siemens publications (e.g. catalogs), the contents of the other documents shall have priority. Copyright Siemens AG 202 All rights reserved We do not accept any liability for the information contained in this document. Any claims against us based on whatever legal reason resulting from the use of the examples, information, programs, engineering and performance data etc., described in this application example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act ( Produkthaftungsgesetz ), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or violation of fundamental contractual obligations ( wesentliche Vertragspflichten ). The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change in the burden of proof to your detriment. It is not permissible to transfer or copy these application examples or excerpts thereof without express authorization from Siemens Industry Sector. 4.0, Entry ID: 49740087
Preface Preface Objective of this application SIMATIC PCS 7/OPEN OS enables the PCS 7-compliant integration of external systems and controllers into a PCS 7 OS environment. Connection is realized with the well-established OPC standard. This document will assist you in selecting a suitable architecture based on the number of inputs and outputs, the degree of system availability and the required network topologies. Core topics of this application This document describes the basic structures of SIMATIC PCS 7/OPEN OS architectures and components. The individual architectures are complemented with different options and configuration variants. SIMATIC PCS 7 is a highly scalable process control system which, due to redundancy and optional hardware and software functions, offers a great number of possible topologies. Validity of application SIMATIC PCS 7 V7. with the technological component PCS 7/OPEN OS Copyright Siemens AG 202 All rights reserved Topics not covered by this application solution The hardware and software lists described in this document are only example configurations. The architectures may as well be modeled with alternative hardware components. The lists include the main PCS 7 components. Not included is further peripheral equipment, such as network cable, power supply unit, monitor, keyboard and mouse which must be ordered separately. The lists neither include components of the third-party systems. For further information about configuration with PCS 7/OPEN OS, please refer to the document Integration of Third-Party Systems with SIMATIC PCS 7/OPEN OS on the download page of this entry: http://support.automation.siemens.com/ww/view/en/49740087 Standard architectures with SIMATIC PCS 7 are available under: http://support.automation.siemens.com/ww/view/en/3220963 Details on the sales and delivery release for PCS 7/OPEN OS can be found at: http://support.automation.siemens.com/ww/view/en/3742348.0, Entry ID: 49740087 5
Table of Contents Table of Contents Copyright Siemens AG 202 All rights reserved Warranty and Liability... 4 Preface... 5 Basic Systems... 7. Standalone system with PCS 7/OPEN OS... 7.2 Single station with PCS 7/OPEN OS... 8.3 Client (on ES) server with PCS 7/OPEN OS... 9.4 Client server with PCS 7/OPEN OS... 0 2 Redundant Systems... 2 2. Redundant OS server with PCS 7/OPEN OS... 2 2.2 OS server with PCS 7/OPEN OS and redundant OPC servers... 4 2.3 Redundant pair of OS servers with PCS 7/OPEN OS and redundant OPC servers... 6 3 PCS 7 Systems with PCS 7/OPEN OS... 8 3. PCS 7 standalone system with PCS 7/OPEN OS... 9 3.2 PCS 7 system with PCS 7/OPEN OS and shared OS servers... 20 3.3 PCS 7 system with PCS 7/OPEN OS and separate OS servers... 22 4 Internet Links... 24 5 History... 24 6.0, Entry ID: 49740087
Basic Systems Basic Systems In the following configuration examples, only the PCS 7/OPEN OS side is considered. The presented configurations, however, can be easily extended by an AS and a PCS 7 project.. Standalone system with PCS 7/OPEN OS On a standalone system with PCS 7/OPEN OS, several individual controllers may be integrated in one PCS 7 OS without a PCS 7 AS project. This requires the use of a computer on which both the PCS 7 Engineering System, as well as the PCS 7 Operator System can be operated. Figure - Copyright Siemens AG 202 All rights reserved Table - Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-2CB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO 250), including OS runtime mode Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S.0, Entry ID: 49740087 7
Basic Systems.2 Single station with PCS 7/OPEN OS This configuration comprises a PCS 7 OS Single Station and a PCS 7 Engineering Station. The main advantage of this layout is that it allows engineering and operation activities at one time. Figure -2 Copyright Siemens AG 202 All rights reserved Table -2 Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation Operator system server 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE SVR03 6EQ2 00-2AA7-3BA0 PCS 7/OPEN OS Single Station Pack V7. (PO 250) Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S 8.0, Entry ID: 49740087
Basic Systems.3 Client (on ES) server with PCS 7/OPEN OS This configuration comprises a PCS 7 OS server with PCS 7/OPEN OS and a PCS 7 ES with an OS client. Operator control and monitoring can be effected either on the OS server or on the engineering station which serves as a client at the same time. Figure -3 Copyright Siemens AG 202 All rights reserved Table -3 Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation 6ES7 658-2CX7-0YA5 PCS 7 OS CLIENT Software Operator system server 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE SVR03 6EQ2 00-2HA7-3BA0 PCS 7/OPEN OS Server Pack V7. (PO 250) Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S.0, Entry ID: 49740087 9
Basic Systems.4 Client server with PCS 7/OPEN OS This configuration comprises a PCS 7 client/server architecture with several clients and PCS 7/OPEN OS. With this type of architecture, operator control and monitoring can be performed by several persons. Figure -4 Copyright Siemens AG 202 All rights reserved Table -4 Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation Operator system server 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE SVR03 6EQ2 00-2HA7-3BA0 PCS 7/OPEN OS Server Pack V7. (PO 250) 0.0, Entry ID: 49740087
Basic Systems Operator system client 6ES7 660-0EA02-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C CLIENT WXP 2 6ES7 658-2CX7-0YA5 PCS 7 OS CLIENT software 2 Terminal bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Copyright Siemens AG 202 All rights reserved.0, Entry ID: 49740087
2 Redundant Systems 2 Redundant Systems The following configuration examples only refer to the PCS 7/OPEN OS side with the redundant hardware components, though all configurations presented below can be easily extended by an AS and a PCS 7 project. 2. Redundant OS server with PCS 7/OPEN OS This configuration comprises a client/server architecture with several clients and a redundant PCS 7/OPEN OS server. Figure 2- Copyright Siemens AG 202 All rights reserved Table 2- Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation Operator system server 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE SVR03 2 2.0, Entry ID: 49740087
2 Redundant Systems 6EQ2 00-2AA7-3BA0 PCS 7/OPEN OS Redundant Server Pack V7. (PO 250) Redundant monitoring of the OPC servers is effected by means of a script. Operator system client 6ES7 660-0EA02-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C CLIENT WXP 2 6ES7 658-2CX7-0YA5 PCS 7 OS Client software 2 Terminal bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S 2 Copyright Siemens AG 202 All rights reserved.0, Entry ID: 49740087 3
2 Redundant Systems 2.2 OS server with PCS 7/OPEN OS and redundant OPC servers With OPC servers, true redundancy is usually not achieved. Instead of a redundant pair of OPC servers, two OPC servers are installed which provide the same data for OPC client applications. When using an ordinary OPC server, the OPC server status is analyzed with the help of a redundancy manager. This redundancy manager is not included in the delivery scope of PCS 7/OPEN OS. Figure 2-2 Copyright Siemens AG 202 All rights reserved Table 2-2 Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation Operator system server 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE SVR03 4.0, Entry ID: 49740087
2 Redundant Systems 6EQ2 00-2AA7-3BA0 PCS 7/OPEN OS Single Station Pack V7. (PO 250) Operator system client 6ES7 660-0EA02-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C CLIENT WXP 2 6ES7 658-2CX7-0YA5 PCS 7 OS CLIENT software 2 Terminal bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Copyright Siemens AG 202 All rights reserved.0, Entry ID: 49740087 5
2 Redundant Systems 2.3 Redundant pair of OS servers with PCS 7/OPEN OS and redundant OPC servers If two OPC servers are used, these are often referred to as redundant OPC servers. In fact, however, there are just two OPC servers publishing the same data management without synchronization. In this case, each OS server is connected separately to one of the OPC servers. Communication monitoring on the servers must be realized with the help of an additional script. Figure 2-3 Copyright Siemens AG 202 All rights reserved Table 2-3 Engineering system 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation Operator system server 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE SVR03 2 6.0, Entry ID: 49740087
2 Redundant Systems 6EQ2 00-2AA7-3BA0 PCS 7/OPEN OS Redundant Server Pack V7. (PO 250) Redundant monitoring of the OPC servers is effected by means of a script. Operator system client 6ES7 660-0EA02-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C CLIENT WXP 2 6ES7 658-2CX7-0YA5 PCS 7 OS Client software 2 Terminal bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S 2 Copyright Siemens AG 202 All rights reserved.0, Entry ID: 49740087 7
3 PCS 7 Systems with PCS 7/OPEN OS 3 PCS 7 Systems with PCS 7/OPEN OS When planning a PCS 7 system with PCS 7/OPEN OS we differentiate between two initial situations:. An existing PCS 7 system shall be expanded with PCS 7/OPEN OS. 2. A new system shall be set up with PCS 7 and PCS 7/OPEN OS. Depending on the specific initial situation, you will require different software packages. So you can select one of the following variants: Copyright Siemens AG 202 All rights reserved Expanding an existing PCS 7 system with PCS 7/OPEN OS Table 3- Product code Engineering system 6ES7 658-5AF7-0YA5 Description PCS 7 ENG AS/OS UNLIMITED The existing systems are already equipped with the PCS 7 standard software. 6EQ2 00-XX7-3BA5 PCS 7/OPEN OS Engineering Component Option V7. Operator system server 6ES7 658-2BC7-0YA0 PCS 7 OS SERVER 2000 PO The existing systems are already equipped with the PCS 7 standard software. 6EQ2 00-2XX7-3BA0 PCS 7/OPEN OS Runtime Component Option V7. Operator system client 6ES7 658-2CX7-0YA5 SOFTWARE PCS 7 OS CLIENT The existing systems are already equipped with the PCS 7 standard software. Setting up a new PCS 7 system with PCS 7/OPEN OS Table 3-2 Product code Engineering system 6EQ2 00-BB7-3BA5 6ES7 658-AF7-0YA5 Operator system server Description PCS 7/OPEN OS Engineering Pack V7. (PO unlimited) The software package includes the PCS 7 OS configuration software. PCS 7 ENG V7.0 AS UNLIMITED software 6EQ2 00-2HA7-3BA0 PCS 7/OPEN OS Server Pack V7. The software package includes the standard PCS 7 OS server. Furthermore, a variant for redundant systems or standalone systems may be selected. Operator system client 6ES7 658-2CX7-0YA5 PCS 7 OS Software Client V7. 8.0, Entry ID: 49740087
3 PCS 7 Systems with PCS 7/OPEN OS 3. PCS 7 standalone system with PCS 7/OPEN OS This architecture comprises a PCS 7 standalone station with PCS 7/OPEN OS. Engineering and Runtime are executed on the same system. Figure 3- Copyright Siemens AG 202 All rights reserved Table 3-3 Engineering system / Operator system (new setup) 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-2CB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO 250), including OS runtime mode 6ES7 658-AF7-0YA5 SIMATIC PCS 7 ENG V7.0 AS UNLIMITED software Engineering system / operator system (expansion) 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6ES7 658-5AB7-0YA5 SOFTWARE PCS 7 ENG AS/OS 000 PO AS AND OS RT 6EQ2 00-XX7-3BA5 PCS 7/OPEN OS Engineering Component Option V7. Automation system 6ES7 654-8CJ0-3BB0 PCS 7 SINGLE AS CPU 46-3PN WITH 4MB RAM Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S.0, Entry ID: 49740087 9
3 PCS 7 Systems with PCS 7/OPEN OS 3.2 PCS 7 system with PCS 7/OPEN OS and shared OS servers This architecture shows a PCS 7 system with PCS 7/OPEN OS. The PCS 7 OS server and the PCS 7/OPEN OS server are realized on a redundant server.. Figure 3-2 Copyright Siemens AG 202 All rights reserved Table 3-4 Engineering system (new setup) 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation 6ES7 658-AF7-0YA5 SIMATIC PCS 7 ENG V7.0 AS UNLIMITED software 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE Engineering system (expansion) 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 20.0, Entry ID: 49740087
3 PCS 7 Systems with PCS 7/OPEN OS Copyright Siemens AG 202 All rights reserved 6ES7 658-5AF7-0YA5 PCS 7 ENG AS/OS UNLIMITED 6EQ2 00-XX7-3BA5 PCS 7/OPEN OS Engineering Component Option V7. 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE Operator system server (new setup) 6ES7 660-0DE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER IE 2 SVR03 6EQ2 00-2AA7-3BA0 PCS 7/OPEN OS Redundant Server Pack V7. (PO 250) Redundant monitoring of the OPC servers is effected by means of a script. 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE This software package is required for redundant automation systems. Operator system server (expansion) 6ES7 660-0DE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER IE 2 SVR03 6ES7 652-3BC7-2YA0 SOFTWARE PCS 7 OS SERVER REDUNDANCY 2000 PO 6EQ2 00-2XX7-3BA0 PCS 7/OPEN OS Runtime Component Option V7. Redundant monitoring of the OPC servers is effected by means of a script. 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE This software package is required for redundant automation systems. Operator system client 6ES7 660-0EA02-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C CLIENT WXP 2 6ES7 658-2CX7-0YA5 PCS 7 OS Client software 2 Automation system 6ES7 656-8CM33-CB0 CONTROLLER AS47-4-2H; AC 0A for 20/230V0A, 4MB W/RED. PS OPT; 2x9 SLOT RACK, 00 PO AS RT The AS PO RT license can be extended as required in steps of 00, 000 or 0000. Terminal bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S 4.0, Entry ID: 49740087 2
3 PCS 7 Systems with PCS 7/OPEN OS 3.3 PCS 7 system with PCS 7/OPEN OS and separate OS servers This architecture shows a PCS 7 system with PCS 7/OPEN OS. The PCS 7 OS server and the PCS 7/OPEN OS server are realized on separate redundant systems. Figure 3-3 Copyright Siemens AG 202 All rights reserved Table 3-5 Engineering system (new setup) 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 6EQ2 00-BB7-3BA5 PCS 7/OPEN OS Engineering Pack V7. (PO unlimited), including 2 hours OS test operation 6ES7 658-AF7-0YA5 SIMATIC PCS 7 ENG V7.0 AS UNLIMITED software 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE Engineering system (expansion) 6ES7 660-0AC3-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C ES/OS BCE WXP 22.0, Entry ID: 49740087
3 PCS 7 Systems with PCS 7/OPEN OS Copyright Siemens AG 202 All rights reserved 6ES7 658-5AF7-0YA5 PCS 7 ENG AS/OS UNLIMITED 6EQ2 00-XX7-3BA5 PCS 7/OPEN OS Engineering Component Option V7. 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE Operator system server (PCS 7) 6ES7 660-0DE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER IE 2 SVR03 6ES7 652-3BC7-2YA0 PCS 7 OS SERVER REDUNDANCY V7.0 2000 PO 6GK 76-0HB7-3AC0 SIMATIC NET, REDCONNECT UPGRADE This software package is required for redundant automation systems Operator system server (PCS 7/OPEN OS) 6ES7 660-0CE3-2BA0 PCS 7 INDUSTRIAL WORKSTATION IPC547C OS SERVER BCE 2 SVR03 6EQ2 00-2AA7-3BA0 PCS 7/OPEN OS Redundant Server Pack V7. (PO 250) Redundant monitoring of the OPC servers is effected by means of a script. Operator system client 6ES7 660-0EA02-2AA0 PCS7 INDUSTRIAL WORKSTATION IPC547C CLIENT WXP 2 6ES7 658-2CX7-0YA5 PCS 7 OS Client software 2 Automation system 6ES7 656-8CM33-CB0 CONTROLLER AS47-4-2H; AC 0A for 20/230V0A, 4MB W/RED. PS OPT; 2x9 SLOT RACK, 00 PO AS RT The AS PO RT license can be extended as required in steps of 00, 000 or 0000. Terminal bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S Plant bus 6GK5 208-0BA0-2AA3 MANAGED IE Switch SCALANCE X208 0/00MBIT/S 4.0, Entry ID: 49740087 23
4 Internet Links 4 Internet Links This list is by no means complete and only presents a selection of suitable information. Table 4- Topic \\ Link to this document \2\ Siemens Industry Online Support \3\ PCS 7/OPEN OS Sales and Delivery Release \4\ PCS 7 Standard Architectures Title http://support.automation.siemens.com/ww/view/en/49740087 http://support.automation.siemens.com http://support.automation.siemens.com/ww/view/en/3742348 http://support.automation.siemens.com/ww/view/en/3220963 Copyright Siemens AG 202 All rights reserved 5 History Table 5- Version Date Revisions V.0 /202 First issue V. 04/207 A defective link was removed 24.0, Entry ID: 49740087