Operating Instructions VEGAMET 381

Similar documents
Operating Instructions SU 600 Ex

Operating Instructions

DT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions

Operating Instruction

Signal conditioning instruments for level switches. Conductive VEGATOR 256C VEGATOR 532 VEGATOR 631. Product Information

Indication and adjustment. LG Remote Interface Operating Instructions 06/2015

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

VEGAMET 381 VEGAMET 624 VEGAMET 625

Intrinsically safe batch controller Batching Master 110i

Operating Instructions VEGAMET 391. Signal conditioning and display instrument for level sensors ma/hart. Document ID: 36032

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

Indication and Adjustment Product Information VEGADIS 61. Level Switching Pressure

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

Operating instructions. Standstill monitor A / / 2011

Operating Instructions VEGAMET 391. Signal conditioning and display instrument for level sensors ma/hart. Document ID: 36032

Display Panel BAT 100 LSN. en Operation Guide

Operating Instructions for Digital Thermometers. Model: DTM

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

OPERATING INSTRUCTIONS

Type 6150 AS-Interface Module. Type 3372 Electropneumatic Actuator with AS-interface module. Mounting and Operating Instructions EB 6150 EN

SD1. Differential Controller. Operating and Installation Instructions F2 72.3

Operating Instructions

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Signal conditioning instruments VEGASCAN 693. Product Information

CMC III Universal Sensor

Product and functional description

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz)

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

English. Operating manual. Limit switch GS125. Keep for future reference. Ventures / brands of GHM

Supplementary instructions. Plug connector Harting HAN 7D. For point level sensors. Document ID: 34456

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1

584 5WG AB_1 DELTA

Supplementary instructions. Plug connector Harting HAN 8D. for continuously measuring sensors. Document ID: 30376

WG 20. The WG 20 achieves an extraordinarily. accuracy for hazardous-area. applications.

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Operating instructions. Switching amplifier DN0210 DN / / 2015

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

Operating Instructions

CMC III Temperature/Humidity Sensor

PHOENIX CONTACT Features

GREISINGER electronic GmbH. D Regenstauf, Hans-Sachs-Straße 26. T-Logg 120 W -... T-Logg 120 K -...

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

DALI Professional Controller-4. Control unit Operating instructions

Industriefunkuhren. Technical Manual. Signal Converter. for DIN Rail Mounting Series 4800xx-yy ENGLISH

Operating Instructions Differential Pressure Transducer PS27

Operating instructions. Speed monitor D / / 2014

Product and functional description

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Product and functional description

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Documentation. KM2604 and KM2614. Four channel relay module. Version: Date:

External level devices for conductive point level switch

Immersion Temperature Sensors

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006

PI-EX-ME-2NAM/COC-24VDC

ETD-BL-1T-OFF-CC- 10S

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

Product and functional description

Product and functional description

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Product and functional description

Mounting and Operating Instructions EB EN. Electric Actuators Type 5824 without fail-safe action Type 5825 with fail-safe action

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

JUMO Quantum PID100/PID200/PID300

Operation and Installation Manual

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Type Quickstart (from device Version 2)

PI-EX-ME-2NAM/COC-120VAC

MINI MCR-SL-PT100-UI(-SP)(-NC)

Installation- and Operating instructions for CU Port USB 3.0 Hub. Version: 1.1 Date:

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26

BA505C 2-wire 4/20mA manual setpoint station Issue 6

Status display unit with P-bus connection

PSR UC/ESAM4/3X1/1X2/B

VariTrans P Standard-Signal Isolators

Operating Instructions. VEGA DataViewer. Software for archive, administration and display of DTM data. Document ID: 51547

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

DINALOG A 144 x 36 A1400 Light-Strip Indicator

MULTICHANNEL DATA RECORDERS

Separating and protective. Separating and protective instruments. VEGATRENN 149AEx Separator type KFDO Barrier type Product Information

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

Documentation. KM10xx. Terminal Modules with Digital Inputs. Version: Date:

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Installation- and Operating instructions for CU Port USB 2.0 Hub. Version: 1.3 Date:

Operating instructions Monitor FD-2 DR2005 DR / / 2007

Operating instructions Safety-monitoring module SE-304 C. 1. About this document. Content

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

Operating instructions Evaluation system for flow sensors VS / / 2013

Electronic Temperature Controller. Instruction Manual Version

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Transcription:

Operating Instructions VEGAMET 381 in out

Contents Contents 1 About this document... 4 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety... 6 2.1 Authorised personnel... 6 2.2 Appropriate use... 6 2.3 Warning about misuse... 6 2.4 General safety instructions... 6 2.5 CE conformity... 7 2.6 Environmentally responsible behaviour... 7 3 Product description... 8 3.1 Configuration... 8 3.2 Principle of operation... 8 3.3 Adjustment... 8 3.4 Storage and transport... 9 4 Mounting... 10 4.1 Mounting procedure... 10 2 VEGAMET 381

Contents 5 Connecting to power supply... 12 5.1 Sensor connection... 12 5.2 Terminal assignment... 13 6 Set-up... 14 6.1 Adjustment system... 14 6.2 Adjustment... 16 6.3 Adjustment... 22 6.4 Reset... 25 7 Diagnostics... 26 7.1 Simulation... 26 7.2 Fault messages... 26 6 Dismounting... 28 6.1 Dismounting procedure... 28 6.2 Disposal... 28 Supplement... 29 Technical data... 29 Dimensions... 31 VEGAMET 381 3

About this document 1 About this document 1.1 Function This operating instructions manual gives you all the information you need for quick set-up and safe operation of VEGAMET 381. Please read this manual before you start set-up. 1.2 Target group This operating instructions manual is directed to trained specialist staff. The contents of this manual should be made available to these personnel and put into practice by them. 1.3 Symbolism used Information, tip, note This symbol indicates helpful additional information. Caution This symbol informs you of a dangerous situation that could occur. Ignoring this cautionary note can impair the person and/or the instrument. Ex applications This symbol indicates special instructions for Ex applications. 4 VEGAMET 381

About this document > List The dot set in front indicates a list with no implied sequence. Action This arrow indicates a single action. 1 Sequence Numbers set in front indicate successive steps in a procedure. VEGAMET 381 5

For your safety 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must only be carried out by trained and authorised personnel. For safety and warranty reasons, any internal work on the instruments must only be carried out by VEGA personnel. 2.2 Appropriate use VEGAMET 381 is a digital signal conditioning instrument with integrated level switches and current output for panel, surface or rail mounting with LC display for digital and quasianalogue demonstration. 2.3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g. vessel overfill or damage to system parts through incorrect mounting or setting. 2.4 General safety instructions VEGAMET 381 is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules. 6 VEGAMET 381

For your safety 2.5 CE conformity VEGAMET 381 is in CE conformity with EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50081-1: 1992 Susceptibility EN 50082-2: 1995 NSR EN 61010-1: 1993. 2.6 Environmentally responsible behaviour Protection of the environment is one of our most important duties. That is why we have introduced an environmental management system with the goal of continuously improving company environmental protection. The environmental management system is certified acc. to DIN EN 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: Chapter 3.4 Storage and transport Chapter 6.2 Disposal. VEGAMET 381 7

Product description 3 Product description 3.1 Configuration Scope of delivery The scope of delivery encompasses: VEGAMET 381 indicating and signal conditioning instrument mounting set documentation this operating instructions manual. 3.2 Principle of operation VEGAMET 381 is a single signal conditioning instrument with integrated level switches and display for continuously measuring instruments. It is also used as signal conditioning instrument and power supply unit for 4 20 ma sensors. The instrument is suitable for panel as well as surface mounting. Any sensor delivering a 4 20 ma signal can be connected to the measuring circuit of VEGAMET 381. 3.3 Adjustment Adjustment is carried out via the integrated keys and a 16-step rotary switch. 8 VEGAMET 381

Product description 3.4 Storage and transport Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test acc. to DIN 55439. The packaging consists of environmental-friendly, recyclable cardboard. Dispose of the packing material via specialised recycling companies. Storage and transport temperature Storage and transport temperature -40 +80 C Relative humidity 20 85 %. VEGAMET 381 9

Mounting 4 Mounting 4.1 Mounting procedure VEGAMET 381 indicating instrument can be either mounted directly to the wall (by means of three screws), plugged on carrier rail 35 x 7.5 acc. to DIN EN 50 022 or lowered into a front panel. Carrier rail mounting Place the adapter plate (A) to the rear of VEGAMET 381 (spring of the adapter plate to the bottom) and tighten the plate with screw B (M4 x 6). Place VEGAMET 381 from the bottom to the carrier rail (C) and push the instrument to the top until it snaps in. A B C 43,5 61 Fig. 1: Carrier rail mounting Wall mounting Insert the metal sleeve (D) from top into the housing cut-out. Fasten the instrument with three screws (ø max. 4 mm) directly to the wall. 10 VEGAMET 381

Mounting D 105 80 ø 4,5* Fig. 2: Wall mounting Front panel mounting Remove the two pluggable terminal boards (F) and terminal board (K) to the top. Screw the pin (H) to the rear of VEGAMET 381 and tighten with a screwdriver. Insert VEGAMET 381 from the front into the front panel (E). Push the terminal strap (G) from the back to the pin (H) and pull it with the knurled nut (I) against the front panel (E). E F G H I 92 ~90 Fig. 3: Panel mounting VEGAMET 381 11 K

Connecting to power supply 5 Connecting to power supply 5.1 Sensor connection Note Switch off power supply before starting connection work. Active operation 4... 20 ma + - 1 2 Sensor 1 2 on % VEGAMET 381 Power supply Fig. 4: Active operation (I a ) 1) Passive operation 4... 20 ma output + - 1 2 1 Sensor 2 on % VEGAMET 381 1) Active or passive operation selectable. See Adjustment Power supply Fig. 5: Passive operation (I p ) 1) 12 VEGAMET 381

Connecting to power supply 5.2 Terminal assignment Sensor input + - Current output + - 1 2 3 4 1 2 1 2 on % VEGAMET 381 18 171615 14131211 10 9 8 7 6 5 Fail safe relay Relay 2 Relay 1 N- L1+ Power supply Fig. 6: Terminal assignment When switching on power supply, the software version of VEGAMET 381 is displayed for approx. 7 seconds. VEGAMET 381 13

Set-up 6 Set-up 6.1 Adjustment system 1 4 Fig. 7 3 1 Control lamps: 1 - LED (yellow) Level relay 1 2 - LED (yellow) Level relay 2 - LED (red) Fail safe relay on - LED (green) Power supply 2 Plus key 3 Minus key 4 Protective cover 5 Shackle 6 Rotary switch 7 Digital indication The figures in brackets relate to the information in illustration 7. To open the protective cover (4), insert a screwdriver into the two slots marked with arrows. Turn the screwdriver by a quarter turn and the protective cover (4) opens. 14 VEGAMET 381

Set-up To protect the instrument against unauthorized adjustment, the protective cover (4) of VEGAMET 381 can be sealed. Insert the seal wire with closed cover in the top left corner through the hole of the lug. Designation: In practice it has proven to mark VEGAMET. Information on the appropriate measurement loop and the respective unit of the indicated value help to avoid failures and misunderstandings. On the housing, a shackle (5) is provided for designation. Here you can insert one of the supplied labels. Rotary switch (6) 0 - OPERATE/Simulation = Indication of the measured value/simulation 1 - Relay 1 on = Relay 1 on 2 - Relay 1 off = Relay 1 off 3 - Relay 2 on = Relay 2 on 4 - Relay 2 off = Relay 2 off 5 - Decimal point = Decimal point 6 - Display max = Scaled indication at 100 % 7 - Display min = Scaled indication at 0 % 8 - Out 0 20 ma, Out 4 20 ma = Current output 9 - t i = Integration time A - Offset correction = Offset correction B - Live adjustment min. (% adjustable) C - Live adjustment max. (% adjustable) D - Dry adjustment min. (ma) E - Dry adjustment max. (ma) F - IN active/passive current input With the rotary switch (16 steps) you select the appropriate function. To move to Simulation, you have to push the plus and minus key simultaneously for approx. 3 seconds in rotary switch position 0 (Operate). VEGAMET 381 15

Set-up If you are in the simulation mode, the VEGA logo on the display flashes. To switch off the simulation mode, you have to push again the two keys for approx. 3 seconds. If no key is pushed, the indication resets automatically to OPERATE after approx. 60 minutes. Plus/Minus keys (2 and 3) With these two key you modify the value of the digital indication. If you hold the key pushed, the digital indication changes its value with raising speed. Save the value by pushing both keys simultaneously. This display indicates briefly Save. 6.2 Adjustment When switching on power supply, the LEDs of the relays light briefly and the display indicates for approx. 7 seconds the software version of VEGAMET 381. The numbers in brackets relate to figure 7 under 6.1 (Adjustment system). Course Choose the requested mode with the rotary switch (6). Push one of the two keys (2 or 3). The digital indication (7) begins to flash. Push one of the two keys to change the value of the digital indication appropriately. If the rotary switch (6) is set to OPERATE, the keys (2 and 3) are without function. Save the value by pushing both keys simultaneously. 16 VEGAMET 381

Set-up Example - an upright cylindrical (linear) vessel with a content of 2700 l. - the max. volume is 2650 l, the min. volume 50 l. - the level sensor in the vessel is a pressure transmitter (passive) providing a standardized 4 20 ma signal. - for further processing you need an additional 4 20 ma output signal. - the full and empty adjustment was carried out correctly. The sensor delivers the following values: Max. volume (display max.) 20 ma = 2650 l Min. level (display min.) 4 ma = 50 l - relay 1 should switch on an emptying pump at a volume of 90 % and switch off the pump at a volume of 10 %. Choose the parameters of your application: IN active/passive current input (F) Set the input type: In-A = active current input (I a ) In-P = passive current input (I p ) For the given example choose In-A (active current input). Save the value by pushing both keys simultaneously. Current output Set the rotary switch (6) to position 8. With the keys (2 and 3) you can choose between measured value output 4 20 ma or 0 20 ma. For the given example choose 4-20. The display indications have the following meaning: 0-20 = 0 20 ma; 4-20 = 4 20 ma VEGAMET 381 17

Set-up Save the value by pushing the two keys simultaneously. The contents for 0 % and 100 % must be entered for scaling the indication in VEGAMET 381. The vessel must not be empty or full. Proceed as follows to enter the two values: Decimal point As the range of the example tank is from 50 l to 2650 l, you require all four positions of the digital indication. Set the rotary switch (6) to position 5 (Decimal Point). By pushing the keys (2 and 3) you move the decimal point. Save the value by pushing the two keys simultaneously. Scaled indication at 0 % Set the rotary switch (6) to position 7 (Display min.). Push the plus key (2) to increase the indicating value or the minus key (3) to reduce the indicating value. If you keep the key pushed, the digital indication (7) changes the indicating value quicker. For the given example, set the digital indication (7) to the value 50. Save the value by pushing the two keys simultaneously. 18 VEGAMET 381

Set-up Scaled indication at 100 % Set the rotary switch (6) to position 6 (Display max.). Push the plus key (2) to increase the indicating value or the mouse key (3) to reduce the indicating value. For the given example, set the digital indication (7) to the value 2650. Save the value by pushing the two keys simultaneously. Relay Set the rotary switch (6) to position 1 (relay 1 on). You can change the value of the indication with the keys (2 and 3). For the given example, set the digital indication (7) to the value 90.0 (90.0 %). Hence the internal relay 1 switches on when this value is reached. Save the value by pushing the two keys simultaneously. Set the rotary switch (6) to position 2 (relay 1 off). You can change the value of the indication with the keys (2 and 3). For the given example, set the digital indication (7) to the value 10.0 (10.0 %). Hence the internal relay 1 switches off when this value is decreased. The appropriate relay control lamp (1) lights when the relay is energised. If the switching points are too close together (< 0.1 %), the appropriate LED flashes. The relay takes the safe condition. In mode Operate a fault signal is displayed. If you want to control further relays, proceed in the same way as for relay 1. The positions for adjustment of the appropriate relays are stated in the list of the rotary switch (6) under Adjustment. VEGAMET 381 19

Set-up Note If you want to change the mode (i.e. the switching function of the relays) you have to exchange the on and off values (see fig. 4.2) Mode A (overfill protection) Switching on point < Switching off point If you adjust e.g. mode A (overfill protection) for relay 1, you have to enter with position 1 (relay 1 on) of the rotary switch (6) the lowest value and with position 2 (relay 1 off) the higher value. Hence relay 1 is switched off when the max. level is reached (deenergised condition) and switched on when min. level is reached. Mode B (dry run protection) Switching on point > Switching off point If you adjust mode B (dry run protection) for relay 1, you have to enter with position 1 (relay 1 on) of the rotary switch (6) the higher value and with position 2 (relay 1 off) the lower value. Hence relay 1 is switched on when the max. level is reached and switched off when min. level is reached (deenergised condition). 20 VEGAMET 381

Set-up 1 off (on) on (off) t LED 2 on off 3 on off Fig. 7: 1 Level 2 Mode A 3 Mode B Integration time If you want to adjust an integration time (reaction delay), set the rotary switch (6) to position 9. With the keys (2 and 3) you can save the value of the indication (0 to 250 seconds). Save the value by pushing the keys simultaneously. VEGAMET 381 21

Set-up 6.3 Adjustment You can carry out the adjustment with medium or without. To carry out an adjustment with medium, it is necessary that you know the percentage values of the actual filling. Adjustment with medium In this case you have to enter the percentage values for min. and max. corresponding to the actual filling. It is not important if you first enter the min. or the max. value. If you know e.g. that the filling is actually 80 %, enter the value 80.0 in rotary switch position C. If the filling is then e.g. 10 %, you have to enter the value 10.0 in rotary switch position B. The higher the difference between the two adjustment points, the more precise the measurement over the complete curve. Ideal would be the adjustment at 0 % and 100 %. For practical reasons it is not always possible to completely empty or fill a vessel. However, the difference between the two adjustment points should be at least 10 % of the sensor range. 22 VEGAMET 381

Set-up Adjustment without medium For this adjustment you have to enter two sensor current values (4 20 ma) corresponding to the 0 % and 100 % levels. Adjustment example You know the sensor data, i.e. that the sensor delivery a current of 4.2 ma at 0 % filling and a current of 15.5 ma at 100 % filling. Enter these values in the rotary switch positions E and D. Enter 15.5 (100 % value) in position E. Enter 4.2 (0 % value) in position D. VEGAMET 381 23

Set-up Offset correction By default, pressure transmitters are adjusted in a certain position. If the transmitter is installed in another position, the measuring range will be shifted. Make sure that the sensor is unpressurised. To make an offset correction, set rotary switch (6) to position A (Offset correction). Now the display indicates the actual sensor current in ma. Push the plus and minus keys (2 and 3) simultaneous. The measuring range does not change, but is shifted completely. Save the value by pushing the two keys simultaneously. All entered values are transferred and saved in an EEPROM memory. They remain there even in case of a voltage loss. Sensor input You can switch over between active and passive sensor input. In-A - Active operation: The sensor is powered by VEGAMET 381. Sensors connected in this configuration are called passive sensors. VEGAMET 381 acts like a current source. In-P - Passive operation: VEGAMET 381 is connected to the sensor cable (current input 4 20 ma). Sensors connected in this configuration are called active sensors. VEGAMET 381 acts like a consumer. 24 VEGAMET 381

Set-up 6.4 Reset A reset can be made on VEGAMET 381. All adjusted values are then reset to default. Interrupt the power supply of VEGAMET 381. Push the plug and minus keys (2 and 3) simultaneously and hold them pushed. Switch on the power supply. The display shows -RES-. The instrument carries out a reset. VEGAMET 381 has the following reset default values. Reset default values - Relay switching on points 10.0 % - Relay switching off points 100.0 % - Display min. 0 - Display max. 1000 - Decimal point 888.8 - Integration time 0 s - Offset correction 0 µa - Current output 4 20 ma - Min. adjustment 0 % = 4 ma - Max. adjustment 100 % = 20 ma - Sensor input I active VEGAMET 381 25

Diagnostics 7 Diagnostics 7.1 Simulation The numbers in brackets relate to illustration 7 under 6.1 Adjustment system. Set the rotary switch (6) to position 0 OPERATE. Now keep the two keys (2 and 3) pushed for approx. 3 seconds. The actual measured value is taken over and flashes. The simulation is immediately active. With the keys (2 and 3) you can change the value of the indication. You can set any value in the scaled range and test the function of the current output and the integrated output relay. To interrupt the simulation, you have to push the two keys simultaneously for approx. 3 secs. The simulation is automatically interrupted after 60 minutes. 7.2 Fault messages The following fault messages can be displayed:? E003 Error during the self-test > Relays deenergise (safe condition), current output 22 ma. Carry out a reset (see 6.4 Reset). All adjusted values will be reset to default. If the error appears again, you have to return the instrument to our repair department.? E014 Short-circuit > Relays deenergise (safe condition), current output 22 ma. Sensor current > 21 ma. Check the terminals and the connection cable to the sensor. 26 VEGAMET 381

Diagnostics? E015 Line break > Relays deenergise (safe condition), current output: 22 ma. Sensor current < 3.6 ma. Check the terminals and the connection cable to the sensor. Probably there is no sensor connected or the sensor input is set to I passive and the connected sensor is a passive sensor.? E016 Adjustment > Empty/full exchanged? E017 Adjustment > Span too small (delta < 300µA)? E021 Scaling, difference too small > Repeat the setting 6.2 Adjustment. Increase the difference between the two indication values? E110 Relay switching points, difference too small > The LEDs of the concerned relay are flashing. The concerned relay deenergised (safe condition). Repeat the setting 6.2 Adjustment. Increase the difference between the two relay switching points. VEGAMET 381 27

Dismounting 6 Dismounting 6.1 Dismounting procedure Take note of chapters 4 Mounting and carry out the listed steps in reverse order. 6.2 Disposal VEGAMET 381 consists of materials which can be recycled by specialised recycling companies. We have purposely designed the electronic modules to be easily separable. Mark the instrument as scrap and dispose of it according to government regulations (electronic scrap ordinance, etc. ). Materials: see technical data If you cannot dispose of the instrument properly, please contact us concerning disposal methods or return. 28 VEGAMET 381

Supplement Supplement Technical data General Series instrument for panel or wall mounting or rail mounting 35 x 7.5 Dimensions W = 96 mm, H = 104 mm, D = 90 mm Weight approx. 400 g Housing material plastic ABS/POM Terminal cross section max. 2.5 mm 2 Ambient conditions Permissible ambient temperature -20 C +60 C Storage and transport temperature -40 C +85 C Temperature error 0.01 %/K Electrical protective measures Protection class II Overvoltage category II Protection - wall or rail mounting IP 20 - panel mounting IP 40 Power supply Power supply Power consumption 20 253 V AC/DC 7 VA VEGAMET 381 29

Supplement Sensor input 4 20 ma active/passive (floating) Resolution 0.01 % (16 µa) Linearity error 0.1 % Transmission analogue Connection cable to the sensor 2-wire I active - sensor power supply 19.5 15 V (range 4... 20 ma) - short-circuit current limitation approx. 30 ma I passive - internal resistance < 250 Ohm (range 4... 20 ma) Terminal voltage - at 4 ma 19.5 V - at 20 ma 14.5 V Adjustment range - empty adjustment 3.8 20.2 A - full adjustment 4.1 20.5 ma - min. adjustment difference 300 µa Current output 0/4 20 ma (signal circuit, floating) Resolution 0.1 % or 20 µa (range 0/4... 20 ma) max. load 500 Ω Fault signal 22 ma Linearity error 0.1 % Temperature error 0.01 %/K Relay output Number of relays 2 level relay, 1 fail safe relay Turn-on voltage min. 10 mv max. 250 V AC, 250 V DC Switching current min. 10 µa max. 3 A AC, 1 A DC Breaking capacity max. 54 W DC, 500 VA AC Indicating of switching status LED lights - relay energised LED of - relay deenergised Digital indication Zero point (0 %) -9999 9999 Final point (100 %) -9999 9999 Decimal point individually selectable 30 VEGAMET 381

Supplement Dimensions 1 2 1 2 92 102 111 % on 96 VEGAMET 381 19 69 2 96 VEGAMET 381 31