Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Similar documents
Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Installation / Control Technique

Safety Technique. SAFEMASTER C Multifunctional Safety Timer UG 6961

Safety Technique. SAFEMASTER C Multifunctional Safety Timer UG 6960

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

Installation / Control / Monitoring Technique

Installation / control / monitoring technique. CANopen PLC IL 5504, IN 5504 minimaster

Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910

Power Electronics. Semiconductor relay / - contactor

Safety technique. Emergency-stop monitor BH 5922, BL 5922 safemaster

Monitoring Technique. VARIMETER NA Voltage and Frequency Monitor RP 9811

Safety Technique. SAFEMASTER Light Curtain Controller With Selectable Operating Modes BH 5902/01MF2

Contact protection relay

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

H S11I1A I2A I3A I4A I5A I6A I7A I8A S21I1C I2C I3C I4C I5C I6C I7C I8C 14A I 15A I 16A 13A I 13B 14B 15B 16B M8540

PHOENIX CONTACT - 07/2006

QUINT-BUFFER/24DC/24DC/40

MINI-PS AC/10-15DC/8

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

02/11/2015

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

TRIO-DIODE/12-24DC/2X10/1X20

H S11I1A I2A I3A I4A I5A I6A I7A I8A S21I1C I2C I3C I4C I5C I6C I7C I8C 14A I 15A I 16A 13A I 13B 14B 15B 16B M8540

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

PHOENIX CONTACT - 01/2007

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PSR UC/ESAM4/3X1/1X2/B

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

Operating instructions. Standstill monitor A / / 2011

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

PSR DC/ESP4/2X1/1X2

02/11/2015

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Operating instructions. Speed monitor D / / 2014

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

02/11/2015

Datasheet - SLB 200-C04-1R

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

Electronic timer CT-ERS.21

QUINT-PS/ 1AC/24DC/ 5

RM4JA01F current measurement relay RM4-J - range ma V AC

08/07/2015

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

Three-phase monitoring relay

Electronic timer CT-ARS.11

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

ISOMETER isoev425 with coupling device AGH420

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

Monitoring Relays. SIRIUS 3UG Monitoring Relays for Stand-Alone Installation. Line monitoring. 8/62 Siemens IC Overview

Safe monitoring relays

Monitoring Technique. VARIMETER NA Voltage and Frequency Monitor RP 9811

RM35TF V AC

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Electronic timer CT-ERD.12

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

ETD-BL-1T-OFF-CC- 10S

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

Thermistor motor protection relay CM-MSS.21

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

Electronic timer CT-AHD.22

ENGLISH. Terminals 13, 14, 23, 24, 43, 44, 53, Web: Phone: Toll Free:

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

RM4TA32 three-phase network control relay RM4-T - range V

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

ABL8RPS24100 regulated SMPS - 1 or 2-phase V - 24 V - 10 A

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

MINI MCR-SL-UI-REL(-SP)

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

Redundancy unit CP-A RU

RM4JA32MW current measurement relay RM4-J - range A V AC DC

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

ABL8WPS24400 regulated SMPS - 3-phase V - 24 V - 40 A

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

STEP-PS/1AC/24DC/1.75

Zelio Control-modular measurement and control relays 1

BETRIEBSANLEITUNG TECHNICAL INSTRUCTION INTERFACE PSE2-SC-02 (24 V AC/DC) Version 1.4

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Monitoring Relays. 3UG Monitoring Relays for Electrical and Additional Measurements. Line monitoring 7/61. Overview

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Transcription:

Monitoring Technique VARIMETER PRO Multifunction Measuring Relay MK 93N, MH 93 268581 Product description MK 93N MH 93 The universal measuring relays MK 93N / MH 93 of the VARIMETER PRO series monitor up to 9 parameters simultaneously. These are under-, over-voltage, voltage range, voltage asymmetry, under-, overcurrent, cos phi, effective-, apparent- and reactive power, frequency and phase sequence, The measurement in 3-phase or single-phase systemes is very simple and without extensiv wiring. Because of the menue structure the multifunctional measuring relays can be used easyly and intuitively. The early detection of up-coming break downs and preventive maintenance avoid expensive damages. As user you profit from the reliability and availability of your plant. Function Diagram U H t Your Advantage Min-, Max. or window monitoring Simultaneous monitoring of up to 9 different parameters Simple configuration and fault diagnostic Different fault indications Large measuring range 3 AC 24... 69 V Auxiliary voltage ranges DC 24 V, AC 23 V or AC/DC... 4 V Early detection of irregular states Space and cost saving Reduced wiring Features Multifunction measuring relay acc. to EN 6255, VDE 435 Voltage monitoring (1- and 3-phase Current monitoring Frequency monitoring Power factor cos phi Phase sequence, phase failure, asymmetry Effective-, reactive- and apparent power Start up delay, on delay Adjustable hysteresis.2... 5 % of response Manual reset LCD for indication of the measuring s Relay output MK 93N 1 changeover contact MH 93 2 x 1 changeover contacts Relay function selectable (energized/de-energized on trip As option with plugable terminal blocks for easy exchange of devices - with screw terminals - or with cage clamp terminals MK 93N Width 22,5 mm MH 93 Width 45 mm More Information I >I Hyst 14 t a t v M1624 t t MK 93N The MK93N has 1 relay output. Monitoring parameters can be set independently MH 93 The MH 93 has 2 relay outputs. Monitoring parameters can be set independently Each monitoring function can be assigned ro relay 1 and /or relay 2 Approvals and Marking Example overvoltage monitoring with closed circuit operation Applications Monitoring of single and 3-phase loads Emergency power supplies Voltage dependent switching at under- or overvoltage Voltage monitoring of portable equipment Motor protection on Phase failure Transformer protection on asymmetric load Frequency monitoring on inverter outputs All technical data in this list relate to the state at the moment of edition. We reserve the right for technical improvements and changes at any time. 1 1.7.13 en / 352

Circuit Diagrams Setting A1 + A2 A1 A2 k L1/i L2 L3 k L1/i L2 L3 21 Display Rel.2 active Error memory 1 active 12 14 12 14 22 24 Display Rel.1 active Error memory 2 active 12 14 12 14 21 22 24 M4 Change to setup mode (3...6s MK 93N. MH 93.12 Selection of Functions/Setting and measuring s Change to Run mode (3...6s Connection Terminals LED status indication Terminal designation Signal designation A1 (+, A2 Auxiliary voltage AC or DC L1/i, L2, L3 Voltage measuring input AC L1/i, k Current measuring path AC, 12, 14 Indicator relay (C/O contact 21, 22, 24 Indicator relay (C/O contact M1933_a Function After connecting the auxiliary supply to terminals A1-A2 the startup delay disables the monitoring function so that changes on the input have no influence on the relay output of the VARIMETER PRO. The device is in display (RUN mode and continuously measures the s. The buttons and toggle between the different s. Pressing for more than 3 sec starts the input mode. One or more measuring s can be assigned to the relay output. If the setting of at least one function is exceeded the relay switches and the display indicates this state. The display is inverted, flashes and shows measuring function and fault. The fault memory is selectable With button the fault memory can be deleted. On the unit MH93 it is possible to assign different s to the different relays so one can be used as pre-warning and the other as alarm output. Relay output 1 switches when exceeds the pre-warning setting of at least one assigned measuring function. If a second setting assigned to relay output 2 with the same measuring function the unit gives an Alarm signal. Indication The LED indicate the state. green LED U N red LED (flashes orange LED Cursor LCD Display on, when auxiliary voltage present at overload at current path No measurement, unit in input mode Active manual reset Manual reset activated flashes when memory mode is and relay in failure state. Reset with button " " Contact state of the output relays Remarks To provide correct function the measuring voltage on L1/L2 has to be at least 2 V. Load monitoring claims a symmetric load on all 3 phases as you have it usually with motors. The unit can also be used for single phase monitoring by bridging terminals L2 and L3 (the display then shows U min =. Overload within the current range is indicated by fast flashing of the LED. 2 1.7.13 en / 352

Operating UP / DOWN Display (Run - Mode After power up the relay is in display (Run mode. Scrolls the display to show one of the 1 possible s. If a s exceeds the setting, the s is indicated flashing on inverted display. In the case of a fault display the display always returns to the fault after pressing. If voltage is missing on the measuring input some s cannot be calculated and a no is shown. Input-Mode The measurement is interrupted, the relays are in failure state and the indicator LED has orange color Selection of parameters and setting of thresholds. ENTER Display (Run - Mode Manual reset, when manual reset is selected for output relay Reset works only when fault is removed Adjustable Parameter Limit s for Rel.1 and Rel.2 Selectable with buttons. U min U max Asym I Cos-j P Response undervoltage, Lowest phase to phase voltage (Undervoltage relay Response overvoltage, Highest phase to phase voltage L1, L2 or L3 (Overvoltage relay Response voltage asymmetry, Percentage of highest to lowest phase to phase voltage (Asymmetry relay Response current at current path L1 (< under- / > overcurrrent Response phase displacement between current and voltage (< under- / > overload monitor Response effective power 3-phase Independent of phase sequence switches at adjusted also at reverse power (< under- / > overload Factory setting 44 V 2 % > 8. A Input-Mode - Shifts cursor to the right - Saves the no-voltage safe - Pressing for more than 3 sec Change to display (Run mode. Display (Run - Mode - Pressing for more than 3 sec Change to input mode S Response apparent power 3-phase (< / > Q Response reactive power (< / > f Response frequency (range 1... 4 Hz ( < under / > overfrequency Hyst Hysteresis.2... 5 % of response 4. % Input-Mode - Shifts cursor to the left - Leave setting without saving t v On delay for relays (... 1 sec s Phseq Monitoring phase sequence ( / LCD-Display A / R Seting open- / closed circuit operation R <f >f Umin Sp Error storage ( / Rel.1 Rel.2 Sp1 Sp2 Rel.1 Rel.2 Sp1 Sp2 Rel.1 Rel.2 Sp1 Sp2 Rel.1 Rel.2 Sp1 Sp2 Setting of response s < Fault, when drops under set point > Fault, when exceeds set point measurement disabled If the adjusted threshold of at least one measuring function is exceeded, the corresponding relay output switches after the selected time delay tv and the fault is indicated on the display. Manual reset can be activated or de-activated and is operated with on the unit. Response s can be deactivated. ( Further Setting Parameter Selectable with buttons. t a Start up delay, when auxiliary voltage connected (.2... 1 sec in steps of.1 s Restore Factory Settings (Auslieferungszustand wiederherstellen Before auxiliary voltage connected press button. During start press and hold. Factory setting.2 s Indicator output Monitoring parameters can be set independently. The MK93N has 1 relay output. The MH 93 has 2 relay outputs. Each monitoring function can be assigned to Relay 1 and/or to Relay 2. The switching mode energized or de-energized on trip can be set in input mode. 3 1.7.13 en / 352

Operating Display (Run - mode Input-mode After connecting the auxiliary supply A1/A2 the unit is in display (Run mode Ph-Seq Ta Start up delay The display is inverted when a measured is exceeds the settings. With button the fault memory is reset. f The measured s can be toggled with the buttons. Q Pressing button for more than 3 sec the unit changes to input mode. S Rel2 Response for Rel2 variant MH In input mode the measurement is disabled, the relays are in failure mode and the indicator LED is orange. With the buttons the different setting s can be chosen. P Move cursor position 3s Rel1 Response for Rel1 One character to the right Cos-Phi One character to the left I Back to the Display (Run-Mode Press button 3 s OK New s stored Asym Umax RUN (Break 3s (OK 3s Break (cancel changes OK- (return with new settings or Press button 3 s; Break Values unchanged M1931 RUN on the display confirm with to change to display (Run mode. Umin Display (RUN Mode Display inverted when the is in failure state. Input-Mode Measurement interrupted, relays are in failure state, indicator LED orange color Scroll display between the 1 different measuring s. Chose Rel1, Rel2, T a and RUN As option address for RS485 Bus Reset fault memory Shift cursor to the left Chose parameter Change and set response s for Rel1 and Rel2. Shift cursor to the right For more the 3 sec, change to input mode For more than 3 sec, change to display mode Operating - Display - Menü (RUN Mode relay 1 energized relay 2 energized relay 1 and 2 energized Cursor flashes during time delay tv Cursordisplay Umin Umax Asym I Cos- P S Q f Ph- [V] [V] [%] [A] Phi [W] [VA] [var] [Hz] feld M2 4 1.7.13 en / 352

Operating Input-menu for relay 1 The menu for relay 2 is identically Sp 1 Sp 1 Sp 1 A/ R A/ R A/ R Phseq Pheq Pheq 1, 1, tv 1 tv 1 tv 1 Hyst Hyst >f [Hz] >f [Hz] <f [Hz] <f [Hz] >Q [var] >Q [var] <Q [var] <Q [var] >S [W] >S [W] <S [W] <S [W] >P [W] >P [W] <P [W] <P [W] >CosP >CosP <CosP <CosP >I [A] >I [A] 12, <I [A] <I [A] 1 Ta Asym [%] Asym [%] 44 Rel2 Umax [V] Umax [V] OK (store settings (OK 44 44 44 44 3s Rel1 Umin [V] Umin [V] Umin [V] Umin [V] Display mode RUN (Break 3s (OK 3s Break (cancel changes OK (return with new setting 5 1.7.13 en / 352

Operating - Setting valid for both relays - Start up delay t a... 1 s in steps of.1 s 1, 1, Ta Ta [s] Ta [s] Display mode RUN (Break 3s (OK 3s Break (Cancel changes OK (return wtih new settings M4_a Technical Data Technical Data Auxiliary Voltage A1/A2 Nominal auxiliary voltage U H MK 93N DC 24 V (.9... 1.1 x U H MH 93 AC 23 V, 4 V (.8... 1.1 x U H AC/DC... 4 V (.8... 1.1 x U H Nominal frequency 5 / 6 Hz Frequency range 45... 4 Hz Input current at DC 24 V 5 ma at AC 23 V 15 ma Current Measuring Input i / k Nominal current Measuring range Max. overload continuously short time < 1 s Nominal frequency Frequency range AC 12 A AC 1 ma... 12 A 16 A max. 25 A If current range is overloaded, the LED flashes fast 5 / 6 Hz 45... 4 Hz Voltage Measuring Input L1/L2/L3 Setting Range (absolute, via button and LCD-display MK 93N Nominal voltage Measuring range U M MH 93 Nominal voltage Measuring range U M Nominal frequency Frequency range 3 AC 4 V 3 AC 24... 4 V (,8... 1,1 x U M 3 AC 4 V / 69 V 3 AC 24... 4 V, 24... 69 V (,8... 1,1 x U M 5 / 6 Hz 1... 4 Hz Measuring accuracy at nominal frequency (in % of setting ± 4 % Hysteresis (in % of setting.2... 5 % of response Reaction time < 15 ms Adjustable on delay t v... 1 s (in steps of.1 s Adjustable start up delay t a.2... 1 s (in steps of.1 s 6 1.7.13 en / 352

Technical Data Standard Types Output Circuit (Rel1 /12/14; Rel2 21/22/24 Contacts MK 93N 1 changeover contact MH 93 1 changeover contact (Rel1 and 1 changeover contact (Rel2 Thermal current I th 2 x 4 A Switching capacity to AC 15 NO contacts 3 A / AC 23 V IEC/EN 6 947-5-1 NC contacts 1 A / AC 23 V IEC/EN 6 947-5-1 to DC 13 NO contacts 1 A / DC 24 V IEC/EN 6 947-5-1 NC contacts 1 A / DC 24 V IEC/EN 6 947-5-1 Electrical life to AC 15 at 3 A, AC 23 V 2 x 1 5 switch. cycl. IEC/EN 6 947-5-1 Permissible switching frequency 18 / h short circuit strength Max. fuse rating 4 A gl DIN VDE 66 Mechanical life 3 x 1 6 switching cycles General Data Nominal operating mode continuous operation Temperature range - 2... + 6 C (at range... - 2 C limited function of the LCD display Clearance and creepage distance rated impuls voltage / pollution degree 4 kv / 2 high voltage test IEC/EN 6 664-1 EMC Electrostatic discharge (ESD 8 kv (air IEC/EN 61-4-2 Fast transients 2 kv IEC/EN 61-4-4 Surge voltage 5 kv /.5J IEC/EN 61-4-5 HF-wire guided 1 V IEC/EN 61-4-6 Interference suppression Limit class A EN 61-6-4 Degree of protection Housing IP 4 DIN EN 6 529 Terminals IP 2 DIN EN 6 529 Housing thermoplastic with VO behaviour according to UL Subject 94 Vibration resistance Amplitude.35 mm, frequency 1... 55 Hz Climate resistance 2 / 6 / 4 EN 6 68-1 Wire connection DIN 46 228-1/-2/-3/-4 Screw terminal (fixed Insulation of wires or sleeve length Terminal block with screw terminals Max. cross section Insulation of wires or sleeve length Terminal block with cage clamp terminals Max. cross section 1 x 4 mm 2 solid or 1 x 2.5 mm 2 stranded ferruled (isolated or 2 x 1.5 mm 2 stranded ferruled (isolated or 2 x 2.5 mm 2 solid 8 mm 1 x 2.5 mm 2 solid or 1 x 2.5 mm 2 stranded ferruled (isolated 8 mm 1 x 4 mm 2 solid or 1 x 2.5 mm 2 stranded ferruled (isolated Min. cross section.5 mm 2 Insulation of wires or sleeve length 12 +.5 mm Wire fixing Plus-minus terminal screws M3,5 box terminals with wire protection or cage clamp terminals Mounting DIN rail EN 6 715 Weight MK 93N approx. 14 g MH 93 approx. 25 g MK 93N./22 3 AC 2... 44 V AC 12 A DC 24 V Article number 6363 Measuring voltage 3 AC 2... 44 V Measuring current AC 12 A Auxiliary voltage U H DC 24 V Output 1 changeover contact Width 22,5 mm MH 93.12/22 3 AC 2... 44 V AC 12 A AC 23 V Article number 63631 Measuring voltage 3 AC 2... 44 V Measuring current AC 12 A Auxiliary voltage U H AC 23 V Output 1 changeover contact (Rel1 and 1 changeover contact (Rel2 Width 45 mm Ordering Example MK 93N. /22 3 AC 2... 44 V AC 12 A DC 24 V Options with Pluggable Terminal Blocks Screw terminal (PS/plugin screw Notes Cage clamp terminal (PC/plugin cage clamp Removing the terminal blocks with cage clamp terminals Auxiliary voltage U H Measuring current U M Measuring voltage Type of terminals without indication terminal blocks fixed with screw terminals PC (plug in cage clamp pluggable terminal blocks with cage clamp terminals PS (plug in screw pluggable terminal blocks with screw terminals Contacts Type 1. The unit has to be disconnected. 2. Insert a screwdriver in the side recess of the front plate. 3. Turn the screwdriver to the right and left. 4. Please note that the terminal blocks have to be mounted on the belonging plug in terminations. Dimensions Width x height x depth MK 93N MH 93 22.5 x 9 x 97 mm 45 x 9 x 97 mm 7 1.7.13 en / 352

Safety notes Connection Example Dangerous voltage. Electric shock will result in death or serious injury. Disconnect all power supplies before servicing equipment. - Faults must only be removed when the relay is disconnected - The user has to make sure that the device and corresponding components are installed and wired according to the local rules and law (TUEV, VDE, Health and safety. L1 L2 L3 L N L1/i k L2 L3 A1 A2 MH93.12 - Settings must only be changed by trained staff taking into account the safety regulations. Installation work must only be done when power is disconnected. 12 14 21 22 24 - Observe proper grounding of all components U< P> +24V IN1 IN2 PLC input Set Up Procedure M194 The connection has to be made according to the connection examples. To connect the current of L1 the Terminals I and k are available. If the current to be measured exceeds the maximum continuous current of the input and external current transformer has to be used. If current is not measured input k remains unconnected. E. DOLD & SÖHNE KG D-784 Furtwangen PO Box 1251 Telephone (+49 77 23 / 654- Telefax (+49 77 23 / 654-356 e-mail dold-relays@dold.com internet http//www.dold.com 8 1.7.13 en / 352