Spring Test 5 due 4/26/2013

Similar documents
Spring Test 9 due 05/11/2013

Spring Test 16 due 06/14/2013

Spring Test 13 due 06/14/2013

Spring Test 17 due 06/14/2013

Fall Test 21 due 12/11/2012

Entry Level Assessment Blueprint Electrical Occupations

Electrical Plan Review

Electrical Integration of PV Systems. Ridha Hamidi, Ph.D.

R-LB R-LX Series Installation, Operation & Maintenance Manual

209/219/229 Multi-Pole Circuit Protectors 202 branch circuit applications such as EDP, air conditioners, panel boards

Page 1 of 34

AIR COOLED MODULAR RECTIFIER

Introduction to the Inspection Checklist for Rooftop Solar Photovoltaic (PV) Systems in Goshen, IN

Application Techniques CENTERLINE 2100 Motor Control Centers

Electrical Components and Equipment for General Use Self Inspection Checklist

The purpose of this document is to specify the power requirements for Core Health and Fitness LLC equipment.

CERTIFIED TEST REPORT

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)


HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

The General Provisions of the Contract, including General, Supplementary and Special Conditions, apply to the work specified in this Section.

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

1-Line Load Calculation Software. User s Manual APPROVED. Copyright 2013 Durand & Associates. Page 1

Meter Enclosure and Equipment Standards

Applying branch circuit breakers and supplementary protectors in North America

ASCO 920 Remote Control (RC) Switches

920 Remote Control (RC) Switches

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SECTION WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Stalking the Elusive and Somewhat Strange PV System

Emery County Senior Center Green River 06/07

Why is my AFCI tripping?

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP

UNDERCARPET CABLING SYSTEM For Power and Communications

Residential 1-Line Multifamily Instructions. User s Manual APPROVED. Copyright 2016 Durand & Associates. Page 1

1993 SPECIFICATIONS CSJ , ETC. & SPECIAL SPECIFICATION ITEM 6132 ARTERIAL TRAFFIC MANAGEMENT SYSTEM

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

Bulletin 1489 Circuit Breakers. Selection Guide

Second Revision No. 1-NFPA [ Global Comment ]

SECTION SWITCHBOARDS

Installation and Operation Manual

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

SURFACE CONTROLTrack INSTALLATION INSTRUCTIONS

More Questions from Inspectors Numerous PV Systems Pose Issues

Installation Notes TII Model 341 Protector

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

MFJ-1164B AC Line RFI Filter

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

Avanti HP Series Centrifuges Preinstallation

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

Instruction Manual HPH-8

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

Installing the Cisco AS5400XM Universal Gateway

Applying branch circuit breakers and supplementary protectors in North America

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

Basics of Industrial Electricity and Troubleshooting Electrical Control Circuits

E-Series General Specifications

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158

1. Coordination of series-rated devices is permitted where indicated on Drawings.

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

SECTION PANELBOARDS

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

SECTION SOLID-STATE REDUCED VOLTAGE STARTERS

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protectors Specifications Bulletin Number 1492, 1692

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Target Interface / Construction Compliance Inspection Checklist

HP R/T2200 UPS. Overview. Precautions. Installation Instructions. The HP UPS R/T2200 features power protection for loads up to 2200 VA/1600 W.

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

APL/UPL, 205/295 Series Magnetic Circuit Protectors

Target Interface / Construction Compliance Inspection Checklist

Standards Update Notice (SUN) Issued: July 28, 2017

File Ref: CP No.: CP1205 Rev. 0 Page: 1 of 25 CERTIFIED TEST REPORT. Cooper Power Systems. 28 kv Class 600 Amp 16.2 / 28.

Bulletin 1492-MC 1492-MCGA, -MCEA 1492-SP

The Real Impact of High Power PoE on Your IP Network

Brasch Washdown Unit Heaters

4.3. Switchboards. Contents Description Pow-R-Line Drawout Molded Case Circuit Breaker Switchboards Product Selection...

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

8 Submersible Motors Standard

It is acceptable to place all required information in the main element (such as G4010) and delete the sub-elements provided in this template.

UL 508 A standard-compliant design of industrial control panel

Target Interface / Construction Compliance Inspection Checklist

CITY OF BOISE SPECIFICATIONS FOR LIGHT EMITTING DIODE (LED) STREET LIGHTING Effective 1 Feb, 2018

60103 Circuit Breaker

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

SECTION WIRING DEVICES

High Voltage terminations and splice combinations with installed GCA kits were performance tested for this evaluation.

JK Series POWER DISTRIBUTION. Solid State Starters Medium Voltage A

PanelView Plus/VersaView CE Terminals and Display Modules

ETAP PowerStation 4.0

NOTICE. Operating Instructions 150W Power Pack. How to Calculate Wattage Load for 150W Power Pack EXAMPLE

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7)

User Manual. JS-ICON 624 PACK Portable Dimmer Pack. JOHNSON SYSTEMS INC. Spring

Transcription:

Spring Test 5 due 4/26/2013 Multiple Choice Identify the choice that best completes the statement or answers the question. 1. Where fixed multioutlet assemblies are employed, each feet or fraction thereof of each separate and continuous length shall be considered as one outlet of not less than 180 volt-amperes where the connected appliances are unlikely to be used simultaneously. a. 5 b. 6 c. 8 d. 10 e. 1 2. The principal determinants of operating temperature are. I. heat generated internally in the conductor as the result of load current flow II. the rate at which generated heat dissipates into the ambient medium III. adjacent load-carrying conductors IV. ambient temperature a. II & IV only c. I, II & IV only e. I, II & III only b. I & IV only d. I, II, III & IV f. III & IV only 3. The maximum allowable ampacity of a 750 kcmil XHHW aluminum conductor is amps when there are six current carrying conductors in the raceway, the raceway is installed in a wet location, and the ambient temperature surrounding the raceway is 22 degrees C a. 323.40 b. 365.40 c. 361.92 d. 348.00 4. Where reduced heating of the conductors results from motors operating on duty-cycle, intermittently, or from all motors not operating at one time, the feeder conductors a. are not allowed to have the ampacity reduced b. may have an ampacity less than specified if acceptable to the authority having jurisdiction c. must be sized not smaller than 125% of the largest motor connected to the feeder d. must be sized not smaller than 125% of the largest motor plus other loads 5. A conductor has a computed ampacity of 75 amps. What is the maximum standard ampere rating of the overcurrent protection device the NEC permits to protect this circuit? This is not a motor circuit or part of a multioutlet branch circuit supplying receptacles. a. 70 amperes b. 75 amperes c. 80 amperes d. 85 amperes 6. If a circuit breaker serves as the controller for a motor, and the motor is not in sight of the breaker, the NEC requires the. a. motor to be less than 2 hp b. breaker be able to be locked in the open position c. motor to be Code letter E d. breaker to have an interrupting rating of 25,000 A 7. shall be placed in all service-entrance motor control centers to isolate service busbars and terminals from the remainder of the motor control center. a. Barriers b. Switches c. Isolators d. Conductors e. Markers 8. Coaxial cable shall be permitted to deliver power to equipment that is directly associated with the radio frequency distribution system if the voltage is not over volts and if the current is supplied by a transformer or other device that has power-limiting characteristics. a. 90 b. 25 c. 70 d. 60 e. 30 9. Among the conductors listed below, all except are permitted to be connected in parallel.

a. 250 kcmil b. 2/0 AWG c. 1 AWG d. 1/0 AWG 10. What is the demand load for eighty receptacles located in a 15,000-square-foot office building? a. 180 b. 12,200 c. 14,400 d. 15,000 11. The ampacity of conductors is derated when the ambient temperature exceeds ºF. a. 30 b. 72 c. 86 d. 104 12. Communications wires and cables shall be separated at least inches from conductors of any electric light, power, Class 1, non power-limited fire alarm, or medium-power network-powered broadband communications circuits. a. 4 b. 6 c. 24 d. 2 e. 12 13. The installation of a fire alarm system requires a plenum cable to be run above the lay-in ceilings. Which of the following cable types is acceptable? I. CMR II. CMP III. FPLR IV. FPLP a. III or IV only c. I, II, or III only e. III only b. I or III only d. I, II, III, or IV f. II or IV only 14. Where motors are provided with terminal housings, the housings shall be and of substantial construction. I. nonmetallic II. metal a. either I or II b. II only c. I only d. neither I nor II 15. The ampacities provided by the NEC for conductors 0-2000 volts are based on temperature alone and do not take into consideration. a. insulation b. AWG c. CMA d. voltage drop 16. Listed communications cables installed in risers shall be. a. encased in a metal raceway b. located in a fireproof shaft having firestops at each floor c. either a or b d. neither a nor b 17. When conductors of different systems are installed in the same raceway, one system grounded conductor shall be white or gray. The other system grounded conductor shall be. a. green only b. white with an identifying colored stripe that is green c. white with an identifying colored stripe that is not green d. white only 18. For a raceway containing 30 current carrying conductors, the ampacity of each conductor shall be reduced to percent of that for a single conductor. a. 80 b. 70 c. 45 d. 50 19. Which of the following statements about a 2 AWG THHN copper conductor is correct? a. its maximum operating temperature is 90 C b. it has a nylon insulation c. its area is 0.067 square inches d. it has a DC resistance of 0.319 ohms per m/ft. 20. A motor control circuit. I. carries electric signals to the controller and carries the main power II. does not carry electric signals to the controller but does carry the main power III. carries the electric signals to the controller but does not carry main power

a. I only b. II only c. III only d. none of these 21. What is the area, in square inches, of a 8 AWG bare conductor in a raceway? a. 0.013 b. 0.017 c. 0.778 d. 0.809 22. For a feeder supplying household cooking equipment and electric clothes dryers, the maximum unbalanced load on the neutral conductor shall be considered as of the load on the ungrounded conductors. a. 40% b. 50% c. 70% d. 80% 23. Thermoplastic insulated fixture wire shall be durably marked with the AWG size, voltage rating and other required markings on the surface at intervals not exceeding inches. a. 6 b. 12 c. 18 d. 24 24. The minimum number of 120-volt, 15-amp lighting branch circuits required for a dwelling that has 70 30 ft. of livable space is. a. 2 b. 3 c. 4 d. 5 25. The grounded conductor, when insulated, shall have insulation. I. rated not less than 300 volts for solidly grounded neutral systems of 1 kv and over as described in section 250.184 II. which is suitable, other than color, for any ungrounded conductor of the same circuit on circuits of less than 1000 volts a. I only b. II only c. either I or II d. neither I nor II 26. Determine the maximum current setting permitted for overload protection for a motor that has a thermal protector integral with the motor, given the following information. * 7 1 / 2 hp - wound rotor type * two-phase, 4 wire, AC * 230 volts a. 19 amps b. 26.6 amps c. 29.6 amps d. 32.3 amps 27. A nipple contains six 6 AWG THW copper current-carrying conductors. The ampacity of each conductor would be amperes. a. 65 b. 50 c. 52 d. 45.5 28. The minimum number of 20-amp, 277-volt, lighting circuits required for a 150,000 ft 2 department store is. The actual connected lighting load is 400 kva. Assume breakers are not rated for continuous use. a. 72 b. 82 c. 91 d. 102 29. For general motor application, the fuse size for the motor branch circuit must be determined from. a. motor nameplate current c. NEC Tables b. NEMA standards d. Factory Mutual 30. A code letter D is marked on a motor nameplate. What is its locked-rotor kva per horsepower? a. 0-3.14 b. 3.15-3.54 c. 3.55-3.99 d. 4.0-4.49 31. Where installed in raceways, conductors of size AWG and larger shall be stranded. a. 16 b. 12 c. 10 d. 8 e. 14 32. When calculating the total load on a dwelling, what is the minimum VA that must be added for the two required small-appliance circuits? a. 1200 VA b. 1500 VA c. 2400 VA d. 3000 VA 33. What is the full load current of a 30 hp, 230-volt, 3-phase, synchronous motor with a 90% power factor? a. 63 amps b. 69.3 amps c. 76.23 amps d. 86.62 amps 34. What is the VA input of a fully-loaded, 5 hp, 230-volt, single-phase motor?

a. 746 b. 3,730 c. 6,440 d. 12,880 35. For a nonautomatically started motor, the overload protection shall be permitted to be shunted or cut out of the circuit during the starting period of the motor if the device by which the overload protection is shunted or cut out cannot be left in the starting position and if fuses or inverse time circuit breakers rated or set at not over percent of the full-load current of the motor are located in the circuit so as to be operative during the starting period of the motor. a. 140 b. 115 c. 125 d. 130 e. 400 36. Which of the following is not true? a. A demand factor from Table 220.55 could be applied to a household counter-mounted cooking unit of 1760 watts. b. Ten household clothes dryers have a demand factor of 50%. c. A demand factor from Table 220.55 could be applied to a 1 3 / 4 kw wall-mounted oven. d. Table 220.55 is permitted to be used for a branch circuit to a household range. 37. The demand factors of Table 220.42 apply to the computed load of feeders to areas in hospitals, hotels, and motels where the entire lighting is likely to be used one at a time, as in operating rooms, ballrooms, or dining rooms. a. shall b. shall not 38. Communications cables permitted where installed in vertical runs and penetrating more than one floor, or cables installed in vertical runs in a shaft, shall be Type. I. CMP II. CMG III. CMR a. I only c. III only e. II only b. I or II only d. I, II, or III f. I or III only 39. Table in the 2011 edition of the NEC is used as a reference for underground installations of network-powered broadband communications conductors and cables. a. 830.47 b. 300.5 c. 310.16 d. 830.15 40. When calculating the load for show window lighting, shall be included for this load. a. 120 VA per outlet c. 200 VA per linear ft. b. 280 VA per outlet d. 180 VA per linear ft. 41. optical fiber cables contain optical fibers and current-carrying electrical conductors. a. Composite b. Nonconductive c. Conductive 42. When using the optional calculation method for a dwelling unit service, all other loads above the initial 10 kw are to be listed at. a. 40% b. 50% c. 60% d. 75% 43. For a dwelling unit served by a single set of 3-wire, 120/240-volt or 208Y/120-volt service-entrance conductors with an ampacity of or greater, it is permissible to compute the feeder and service loads in accordance with 220.82(B) and (C) instead of the method specified in Part III of Article 220. a. 175 b. 125 c. 150 d. 100 44. Equipment terminations are permitted to be used with higher temperature-rated conductors at the ampacity of the higher-rated one, provided the equipment is and identified for use with the higher rated conductors. a. listed b. tested c. installed d. rated 45. The grounded conductor of a branch circuit that is 6 AWG or smaller shall be. I. without splices II. white or gray in color a. I only b. neither I nor II c. both I & II d. II only

46. Open conductors shall be supported on glass or porcelain knobs,. I. strain insulators II. brackets III. racks a. I only b. II only c. III only d. I, II or III 47. A previously unwired portion of an existing residence or a structural addition to an existing residence, either of which exceeds square feet, shall be computed in accordance with sections 220.12 and 220.14. a. 100 b. 250 c. 300 d. 500 48. Synchronous motors of the low-torque, low-speed type, such as are used to drive reciprocating compressors, pumps, and so forth, that start unloaded, do not require a fuse rating or circuit-breaker setting in excess of percent of full-load current. a. 150 b. 200 c. 250 d. 400 49. Ampacity of fixture wire is determined. a. by referring to ampacity Table 310.16 b. by calculation, using the expected temperature rise of the fixture c. from a table in Article 402 of the Code d. none of these 50. When installing a fire alarm system, survivability cable is typically used in a. a. single-story office building c. hospital b. restaurant d. school 51. The disconnecting means for motor circuits rated 600 volts, nominal, or less, shall have an ampacity rating of at least % of the FLC rating of the motor. a. 100 b. 115 c. 125 d. 135 e. 80 52. Conductors for a motor used in a short-time, intermittent, periodic, or varying duty application shall have an ampacity of not less than the percentages of the motor nameplate current ratings shown in Table. I. 430.148 II. 430.150 III. 430.7(B) IV. 430.22(E) a. II only c. I only e. I or II only b. III only d. IV only f. III or IV only

Spring Test 5 due 4/26/2013 Answer Section MULTIPLE CHOICE 1. ANS: A 2011 NEC: 220.14(H)(1) REF: 2011 NEC: 220.14(H)(1) OBJ: Obj 431.2 Worksheet NAT: Obj 431.2 ABank 2. ANS: D 2011 NEC: 310.15(A)(3) I-Note No.1 & (1) thru (4) REF: 2011 NEC: 310.15(A)(3) I-Note No.1 & (1) thru (4) OBJ: Obj 421.4 Worksheet NAT: Obj 421.4 ABank 3. ANS: A 385 A 80% 1.05 = 323.40 amps 2011 NEC: T. 310.15(B)(2)(a); T. 310.15(B)(3)(a) & T. 310.15(B)(16) REF: 2011 NEC: T. 310.15(B)(2)(a); T. 310.15(B)(3)(a) & T. 310.15(B)(16) 4. ANS: B 2011 NEC: 430.26 REF: 2011 NEC: 430.26 OBJ: Obj 430.1 Worksheet 5. ANS: C 2011 NEC: 240.4(B)(2)&(3) & 240.6(A) REF: 2011 NEC: 240.4(B)(2)&(3) & 240.6(A) OBJ: Obj 421.5 Worksheet 6. ANS: B 2011 NEC: 430.102(B) Exc REF: 2011 NEC: 430.102(B) Exc OBJ: Obj 430.1 Worksheet 7. ANS: A 2011 NEC: 430.97(E) REF: 2011 NEC: 430.97(E) OBJ: Obj 430.1 Worksheet 8. ANS: D 2011 NEC: 820.15 REF: 2011 NEC: 820.15 OBJ: 434 NEC Worksheet 9. ANS: C 2011 NEC: 310.10(H)(1) REF: 2011 NEC: 310.10(H)(1) NAT: Obj 421.4 ABank

10. ANS: D 80 180 VA = 14,400 [(10,000) 100%] + [(14,400 10,000) (50%)] = 10,000 + 2,200 = 12,200 VA versus 1 VA/SF 15000 SF = 15,000 VA 2011 NEC: 220.14(K); 220.44; T 220.44; 220.14(I) REF: 2011 NEC: 220.14(K); 220.44; T 220.44; 220.14(I) OBJ: Obj 431.2 Worksheet NAT: Obj 431.2 ABank 11. ANS: C 2011 NEC: T. 310.15(B)(16) REF: 2011 NEC: T. 310.15(B)(16) OBJ: Obj 421.5 Worksheet 12. ANS: D 2011 NEC: 800.133(A)(2) REF: 2011 NEC: 800.133(A)(2) OBJ: 434 NEC Worksheet 13. ANS: F 2011 NEC: T. 760.154(D) REF: 2011 NEC: T. 760.154(D) OBJ: Obj 433.3 Worksheet NAT: Obj 433.3 ABank 14. ANS: B 2011 NEC: 430.12(A) REF: 2011 NEC: 430.12(A) 15. ANS: D 2011 NEC: 310.15(A)(1) I-Note No. 1 REF: 2011 NEC: 310.15(A)(1) I-Note No. 1 OBJ: Obj 421.5 Worksheet 16. ANS: C 2011 NEC: 800.154; T. 800.154(a) REF: 2011 NEC: 800.154; T. 800.154(a) OBJ: 434 NEC Worksheet 17. ANS: C 2011 NEC: 200.6(D) REF: 2011 NEC: 200.6(D) NAT: Obj 421.4 ABank 18. ANS: C 2011 NEC: 310.15(B)(3) I-Note No. 2 REF: 2011 NEC: 310.15(B)(3) I-Note No. 2 OBJ: Obj 421.5 Worksheet 19. ANS: A 2011 NEC: T. 310.104(A) REF: 2011 NEC: T. 310.104(A) OBJ: Obj 421.4 Worksheet NAT: Obj 421.4 ABank 20. ANS: C

2011 NEC: 430.2 REF: 2011 NEC: 430.2 OBJ: Obj 430.1 Worksheet 21. ANS: B 2011 NEC: Ch 9-Table 8 & 310.106(C) REF: 2011 NEC: Ch 9-Table 8 & 310.106(C) NAT: Obj 421.4 ABank 22. ANS: C 2011 NEC: 220.61(B)(1) REF: 2011 NEC: 220.61(B)(1) OBJ: Obj 431.1 Worksheet 23. ANS: D 2011 NEC: 402.9(A) REF: 2011 NEC: 402.9(A) NAT: Obj 421.4 ABank 24. ANS: C (70 30 3 VA) = 6,300 VA 6,300 120 = 52.5 amps 53 15 = 3.5 4 circuits 2011 NEC: T. 220.12 REF: 2011 NEC: T. 220.12 OBJ: Obj 431.1 Worksheet 25. ANS: B 2011 NEC: 200.2(A) REF: 2011 NEC: 200.2(A) NAT: Obj 421.4 ABank 26. ANS: C 2011 NEC: T. 430.249 with 430.32(A)(2) REF: 2011 NEC: T. 430.249 with 430.32(A)(2) 27. ANS: A 2011 NEC: 310.15(B)(3) I-Note No. 2(2) REF: 2011 NEC: 310.15(B)(3) I-Note No. 2(2) 28. ANS: C Per 210.11(A), the connected load is used over the demand load when known. Lighting load is continuous, therefore use 125% (1.25) 400,000 1.25 = 500,000 VA 500,000 277 = 1,805 amps 1,805 20 = 90.25 91 ckts 2011 NEC: 210.19(A)(1) & 210.11(A)

REF: 2011 NEC: 210.19(A)(1) & 210.11(A) OBJ: Obj 431.2 Worksheet NAT: Obj 431.2 ABank 29. ANS: C 2011 NEC: 430.6(A)(1) & 430.52(C)(1) REF: 2011 NEC: 430.6(A)(1) & 430.52(C)(1) 30. ANS: D 2011 NEC: T. 430.7(B) REF: 2011 NEC: T. 430.7(B) OBJ: Obj 430.1 Worksheet 31. ANS: D 2011 NEC: 310.106(C) REF: 2011 NEC: 310.106(C) OBJ: Obj 421.4 Worksheet NAT: Obj 421.4 ABank 32. ANS: D 2011 NEC: 220.52(A) REF: 2011 NEC: 220.52(A) OBJ: Obj 431.1 Worksheet 33. ANS: B Due to 90% power factor - 6.3 1.1 = 69.3 2011 NEC: T. 430.250 REF: 2011 NEC: T. 430.250 34. ANS: C 2011 NEC: T. 430.248 REF: 2011 NEC: T. 430.248 35. ANS: E 2011 NEC: 430.35(A) REF: 2011 NEC: 430.35(A) 36. ANS: C 2011 NEC: 220.55; T. 220.55 REF: 2011 NEC: 220.55; T. 220.55 OBJ: Obj 431.1 Worksheet 37. ANS: B 2011 NEC: T. 220.42 *Note (below table) REF: 2011 NEC: T. 220.42 *Note (below table) OBJ: Obj 431.2 Worksheet NAT: Obj 431.2 ABank 38. ANS: F 2011 NEC: 800.154 & T. 800.154(a) REF: 2011 NEC: 800.154 & T. 800.154(a) OBJ: 434 NEC Worksheet 39. ANS: A 2011 NEC: 830.47(C)

REF: 2011 NEC: 830.47(C) OBJ: 434 NEC Worksheet 40. ANS: C 2011 NEC: 220.14(G)(2) REF: 2011 NEC: 220.14(G)(2) OBJ: Obj 431.2 Worksheet NAT: Obj 431.2 ABank 41. ANS: A 2011 NEC: 770.2 REF: 2011 NEC: 770.2 OBJ: 434 NEC Worksheet 42. ANS: A 2011 NEC: 220.82(B) REF: 2011 NEC: 220.82(B) 43. ANS: D 2011 NEC: 220.82(A) REF: 2011 NEC: 220.82(A) OBJ: Obj 431.1 Worksheet 44. ANS: A 2011 NEC: 110.14 REF: 2011 NEC: 110.14 45. ANS: D 2011 NEC: 200.6(A)(1) & (2) REF: 2011 NEC: 200.6(A)(1) & (2) NAT: Obj 421.4 ABank 46. ANS: D 2011 NEC: 225.12 REF: 2011 NEC: 225.12 NAT: Obj 421.4 ABank 47. ANS: D 2011 NEC: 220.16(A)(1) REF: 2011 NEC: 220.16(A)(1) OBJ: Obj 431.1 Worksheet 48. ANS: B 2011 NEC: T. 430.52 Note 3 REF: 2011 NEC: T. 430.52 Note 3 OBJ: Obj 430.1 Worksheet 49. ANS: C 2011 NEC: 402.5 REF: 2011 NEC: 402.5 50. ANS: C Best guess general knowledge REF: Gen Knowledge OBJ: Obj 433.3 Worksheet

NAT: Obj 433.3 ABank 51. ANS: B 2011 NEC: 430.110(A) REF: 2011 NEC: 430.110(A) OBJ: Obj 430.1 Worksheet 52. ANS: D 2011 NEC: 430.22(E) REF: 2011 NEC: 430.22(E) OBJ: Obj 430.1 Worksheet