MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation and Operation Manual

Similar documents
MicroVision Timer MICROPROCESSOR TIMER CONTROLLER. Installation Operation Manual Rev.F Page 1 of 30

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

Manual. ZIG-NANO Wireless Transmitter. Installation Maintenance Repair Manual CONNECTED ON:01

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual

MicroVision Boiler MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation Operation Manual Rev. D Page 1 of 34

MicroVision Boiler MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation Operation Manual Rev. B Page 1 of 30

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

Zonit μats TM Users Guide μats1-lv Version 1.2

MAXIMA + Series ROTARY LEVEL CONTROL

TC-9102 Series Surface Mount Temperature Controllers

SureTest Model ST 1D Instructions

OPERATION MANUAL MODEL TT-LP

Progressive Industries, Inc. EMS Electrical Management System

MAXIMA+ Series Rotary Level Indicator

EMS. Electrical Management System. Progressive Industries Incorporated Morrisville, North Carolina

MYRIAD LC1 LEVEL CONTROLLER INSTRUCTION MANUAL

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Pump-Down Controller MODEL mA Input Scalable 4-20mA Output Duplex Pump Alternation Hand-Off-Auto Controls Dual Run-time Meters

SLA Battery Capacity Analyzer

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

MAXIOM. Data Sheet. Lighting Relay Panel. Overview Leverage the Power of BAS Integration

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Total Protection Solutions Surge Protective Devices SurgeTrack Series: 080, 120, 160, 240, 300 and 400

The power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.

700 Series 200 Amp Clamp Meters

MicroVision MICROPROCESSOR BASED WATER TREATMENT CONTROLLER. Installation Operation Manual Rev. M Page 1 of 43

Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Tempco Instruction Manual

Surge Protective Devices Installation, Operation and Maintenance Manual. ServiceTrack ST Series: 080, 120, 160, 200, 240, 300 and 400

Long-time range model (0.1 min to 10 h) 24 VAC; SPDT H3RN-1 H3RN-11 12, 24 VDC DPST-NO H3RN-2 H3RN-21

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

USB 2.0 CAT5E/6/7 EXTENDER

Global Water globalw.com. Global Water. Instrumentation, Inc.

USER GUIDE. AXIS T8120 Midspan 15 W 1-port ENGLISH

AS1008-P AS1026-P AS2008-P AS2024-P User Manual

Manual. Water Vend Controller Model ESDI WARNING! ELECTRICAL SHOCK HAZARD! AUTHORIZED PERSONNEL ONLY. EXPOSED 120 VAC ON CIRCUIT BOARD

MAXIMA + Series ROTARY LEVEL CONTROL

Installation and Operation Manual. ETV Platinum Plus. Electronic Tempering Valve with Safeguard WARNING

Model HM-535 Power Supply Installation and Service Instructions

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

SP6R Level Controller Operation Manual

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

Operation Manual CX20 1/8 DIN Microcomputer Based Conductivity/Resistivity Controller

User's Guide. Extech AM A AC Analog Clamp Meter

MC 11 EB-2 Power supply cabinet with external bus, AC version

Sapling Converter Box

Instruction Manual Standard Multi-Position Stirrers Advanced Multi-Position Stirrers

User Manual. Item no.: Otto Graf GmbH Carl-Zeiss-Str. 2-6 Tel.: +49(0) Kunststofferzeugnisse D Teningen Fax: +49(0)

MICRO GROW GREENHOUSE SYSTEMS, INC

EMS Electrical Management System

Operation Manual CX10 1/8 DIN Microcomputer Based Conductivity/Resistivity Controller

USER MANUAL. MODEL 1225 ParaLink TM Parallel Short Range Modem. SALES OFFICE (301) TECHNICAL SUPPORT (301)

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

CDD4 Duct Carbon Dioxide Transmitter

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

Tracer VM Bluetooth Interface

LC2300 Level Controller Installation and Maintenance Instructions

G2M Control Board Installation and Operations Manual

Pulse LED Instruction Guide

User's Guide. Phase Sequence and Motor Rotation Tester Model

Seven Channel Remote Control

EMS Electrical Management System

ATS22D47S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

DISCONTINUED PRODUCT DISCONTINUED PRODUCT

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100hp)

Installation, Operation & Maintenance Instructions / Technical Document

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp)

Mini Digital Multimeter

LAKEWOOD INSTRUMENTS MODEL 1575e WATER TREATMENT CONTROLLER

Tank Console Instruction Manual

LCI User Manual mantracourt.com

ELECTRA-flo / SD. Thermal Airflow & Temperature With Dual Analog Output. Installation, Operation and Maintenance Manual

AP41 / AP81 SERIES TIME SWITCHES

Elapsed Timer Control Panel

INSTALLATION INSTRUCTIONS FOR THE MINI-KEY SYSTEM. Doc Rev B

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

Operation Manual. Concorde 600 Power Supply. *This instrument is intended for laboratory use only.

PanelView Plus/VersaView CE Terminals and Display Modules

Digital Lighting Systems, Inc. PD216. Two Channel Dimmer and Switch Packs PROTOCOL USER'S MANUAL. PD216-UM Rev. E - 02/03

E2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information

NI PXI-1042 Series Power Supply Shuttle

Bluetooth Enabled Access Control MODEL BG-FE. Operating Instructions

B2800 FLOW MONITOR. - For Liquid Meters - PROGRAMMING & INSTALLATION MANUAL Simplified Version

INSTRUCTION MANUAL. Instruction Manual. Analog Multi-Tube Vortexer Digital Multi-Tube Vortexer

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

6 10/100/1000TX + 2G Fiber Industrial Ethernet Switch User Manual

Manual Control Unit GFC 32

HomePro ZRF113. Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2

Operating Instructions. For. Level Control Module. Model SSR 1000

T775S Series 2000 Expansion Module

Transcription:

MICROtrac MICROPROCESSOR BASED WATER TREATMENT CONTROLLER Installation and Operation Manual

MICROtrac Warranty Pulsafeeder, Inc. warrants MICROtrac control systems (including the conductivity sensor) of its manufacture to be free of defects in material or workmanship. Liability under this policy extends for 24 months from date of shipment. The manufacturer's liability is limited to repair or replacement of any failed equipment or part, which is proven defective in material or workmanship upon completion of the manufacturer's examination. This warranty does not include removal or installation costs and in no event shall the manufacturer's liability exceed the selling price of such equipment or part. The manufacturer disclaims all liability for damage to its products through improper installation, maintenance, use, or attempts to operate such products beyond their functional capacity, intentionally or otherwise, or any unauthorized repair. The manufacturer is not responsible for consequential or other damages, injuries, or expense incurred through the use of its products. The above warranty is in lieu of any other warranty, whether expressed or implied. The manufacturer makes no warranty of fitness or merchantability. No agent of ours is authorized to provide any warranty other than the above. 2

Table of Contents 1. INTRODUCTION... 4 2. INSTALLATION... 4 2.1 Controller Location...4 2.2 Sensor Installation...4 3. ELECTRICAL WIRING... 6 3.1 Electrical Connections...7 4. SYSTEM OPERATION... 9 4.1 Front Panel... 9 4.2 System Functions...10 4.3 Controller Programming... 11 4.3.1 Control Modes...11 4.3.2 Conductivity Set Point... 12 4.4 Alarm Conditions...13 5. SENSOR CALIBRATION... 14 6. FACTORY DEFAULT VALUES...14 7. SPECIFICATIONS... 14 8. TROUBLE SHOOTING GUIDE...16 9. CONTROLLER MOUNTING DIMENSIONS... 17 10. ADDENDUM: MICROTRAC PC BOARD REPLACEMENT... 18 11. MICROTRAC FACTORY SERVICE POLICY...19 3

1. Introduction Your microprocessor-based controller has been designed to monitor and control the conductivity of your process water. The controller energizes two relay outputs based on a bleed and feed mode of operation. - When the conductivity measurement goes above the user defined set point, (2) two relays are energized until the conductivity goes below the set point minus the fixed differential value. The feed relay will also de-energize when the user programmable feed limit time is reached. - Optional - The feed control relay will energize based on a percentage of a 10 minute feed cycle. Your controller may or may not have the following optional configurations: Pigtails (pre-wired) The controller is pre-wired with a power cord and drop down receptacles for plugging in control devices such as a solenoid valve or a metering pump. Flow Switch The controller is supplied with a flow switch that is installed into the process flow line to signal the controller that your system has water flowing. When there is a no flow state, the controller will not energize the outputs. 2. Installation 2.1 Controller Location Select a mounting location convenient to grounded electrical and plumbing connections. Mount the controller on a wall or other vertical surface with adequate lighting at a comfortable level. Remove the four screws that retain the front panel and remove it, mounting passages are located in each of the four corners in the back of the enclosure (See page 15). Installation should comply with all national, state and local codes. Avoid locations where the controller would be subjected to extreme cold or heat {less than 0 F (-17,8 C) or greater than 122 F (50 C)}, direct sunlight, vibration, vapors, liquid spills or EMI (electromagnetic interference; e.g., strong radio transmission and electric motors). The controller could be damaged and void the warranty! 2.2 Sensor Installation The controller is supplied with a temperature compensated conductivity sensor (probe). Install the sensor at some point in your process where chemical and water are thoroughly mixed. If the sensor is to be placed in a tank or sump, ensure that it is installed so that the black shrink-wrapped part of the probe cable is not submerged. The probe should also be located in a position where adequate flow is going across and through the probe. 4

Fig. 1: Typical Installation Fig. 2: Probe Alignment For maximum accuracy, make sure that the conductivity sensor is installed so the liquid stream passes straight through the round probe hole (see Fig.2). 5

Flow Sensor If your controller is provided with a flow switch, install the flow switch so that flow enters into the bottom of the provided flow switch tee, and out of the side of the tee. The flow switch must always be installed in a vertical position so that the sensor wire is coming out of the top, and the internal (red) flow shuttle is able to rise when there is flow and drop when there is not flow. The flow switch is activated when 1 GPM (3.8 LPM) is going through it, and is deactivated when the flow drops below 1 GPM (3.8 LPM). 3. Electrical Wiring 1 The controller electronic circuitry is fuse protected. Use of a surge protector and Ground Fault Circuit Interrupter (GFCI) are strongly recommended! Controller must be wired in accordance with all applicable electrical codes. Input power must be 120 or 220VAC Single Phase. Trained service personnel are required for all electrical connections. This product does not contain operator serviceable parts. Devices attached to any Relay connection must be Single Phase and rated for the same voltage as the input voltage to the product. (e. g. 120VAC MicroTrac controllers support 120VAC relay attached devices exclusively and 220VAC MicroTrac controller support 220VAC relay attached devices exclusively.) Do not apply power until this condition is verified. Input power cord must be disconnected from power source prior to opening the product s enclosure and making any electrical connections. The controller should be connected to a dedicated power branch (i.e., its own wiring, circuit breaker, etc.). For best results, the ground should be independent (true earth) not shared. A switch or circuit-breaker, marked as the unit s disconnecting device should be included in the installation. It should be in close proximity to the unit and easily reached by the user. 1 Trained service personnel are required for all electrical connections. This product does not contain operator serviceable parts. 6

Pre-wired controllers are supplied with 6 ft (1,8 m), 18 AWG (1,2 mm 2 ) 3-wire grounded power cords and clearly marked 18 AWG (1,2 mm 2 ) 3-wire grounded receptacle cords for all controlled line voltage outputs. Controllers that are to use electrical conduit are factory pre-drilled with easily accessible connections for hard wiring of input and output power connections. Use only 16 AWG (1,5 mm 2 ) or 18 AWG (1,2 mm 2 ) wire for conduit power and load connections. 3.1 Electrical Connections 2 If your controller was not ordered as a pre-wired controller, hard wiring will be required. With the main power disconnected from the controller, loosen the four screws that retain the front panel of the controller and remove the front panel. There are five terminal block connectors inside the controller that will need to be wired. Supply power The controllers supply power is identified on the main PC board as location PL3 (refer to Fig. 3 on page 8). There are three connections identified on the board for this terminal block, HOT (LINE), RTN (return or Neutral), and Ground. Flow and Water Meter Inputs These two inputs are located on connector PL2. This is where the two wires from the flow switch or water meter will connect. Polarity on this terminal block is not important. If your controller is not equipped with a flow switch, there should be a jumper wire installed across PL2. (See Fig.3) Dose/Feed (metering pump) This control output is identified on the controller PC board as location PL4. The terminal block connections for PL4 are HOT (LINE), RTN (return or Neutral), and Ground. This control output can drive pumping equipment based on the bleed and feed with limit timer mode. This output energizes when the programmed conductivity set point is exceeded. This output will de-energize when the conductivity reading falls below the set point minus the fixed set point differential (-5% of set point) or when the programmed feed limit time is exceeded. Optional - This output energizes for a programmed percentage of a fixed 10 minute feed cycle. The controller is fused at 5 amps maximum. Both output devices combined can not exceed 5 amps of current. 2 Trained service personnel are required for all electrical connections. This product does not contain operator serviceable parts. 7

Bleed (solenoid valve) This control output is identified on the controller PC board as location PL5. The terminal block connections for PL5 are HOT (LINE), RTN (return or Neutral), and Ground. This control output will energize when the programmed conductivity set point is exceeded. This output will de-energize when the conductivity reading falls below the set point minus the fixed set point differential (-5% of set point). Conductivity Probe The controller is supplied with one temperature compensated conductivity sensor. The sensor connects to PL1 of the controller PC board. Match the wire color from the probe with the text next to connector PL1. PUMP (3-WIRE) HOT RET (NORMALLY OPEN) (EARTH / CHASSIS GROUND) (RETURN/NEUTRAL) FUSES F1 5A RET HOT DOSE PL4 DIP SWITCH CONDUCTIVITY SENSOR BLACK BROWN ORANGE RED PL1 RET HOT SUPPLY PL3 ON DIP F2 5A SW1 1 2 3 4 MOTORIZED BALL VALVE (4-WIRE) (RETURN / NEUTRAL) (EARTH / CHASSIS GROUND) (NORMALLY / OPEN) (NORMALLY / CLOSED) HOT RET no HOT nc HOT RET PL5 BLEED PL2 COM FLOW COM WATER METER SUPPLY POWER FLOW SWITCH CONTACT METER TOROIDAL PROBE Fig. 3: Wire Connections 3 These connections are made using a green terminal block that uses screws to retain a wire inserted into the square openings as seen below. Using a small flat head insulated screwdriver, loosen the screw enough to allow clearance for the wire, then insert the wire and tighten the screw securely. Controllers without an external flow detection switch must have a jumper installed across the flow switch input, PL2 (see Fig.3). Fig. 4: Terminal Block 3 Trained service personnel are required for all electrical connections. This product does not contain operator serviceable parts. 8

4. System Operation BEFORE APPLYING POWER, INSURE THAT DEVICES BEING CONTROLLED BY THIS CONTROLLER ARE NOT IN A POSITION TO CAUSE HARM OR DAMAGE IF ENERGIZED UPON INITIAL START-UP. DISPLAY SCREEN Bleed us Set Point Feed m MICROtrac Front panel Fig. 5 4.1 Front Panel The front panel of the controller has a 4-digit LCD display, four LED indicators, and three pushbuttons that are used for programming and controller monitoring. The LCD display is used to display the system conductivity as well as various system parameters during programming. The LED s are used to indicate what mode or function the controller is operating in. The m (MODE) button is used to enter programming mode and to view the controller parameters. The up and down arrows are used to change the controller settings once in programming mode. 9

4.2 System Functions Bleed us The bleed LED will light when the bleed relay is energized in normal operation or when the controller is displaying the bleed limit time setting. When in programming mode this LED will flash indicating it is okay to change the bleed limit time setting. The us LED will light when the controller is displaying the system conductivity reading. The controller displays this during normal operation or when there has been no button activity for 30 seconds. When calibrating the probe this LED will flash indicating it is okay to change the probe conductivity value. Set Point The set point LED will light when the controller is displaying the conductivity set point. The set point is the conductivity value that will energize the Bleed and Dose relays. When in programming mode this LED will flash indicating it is okay to change the set point setting. Feed This LED will light when the Dose or feed relay is energized. When in programming mode this LED will flash indicating it is okay to change the feed limit time setting. Mode Selection The controller s mode of operation is selected by the switch settings of SW1 located on the PC board, see Fig. 3. DIP SWITCH SETTINGS 1 2 3 4 LIMIT TIMER *OFF *OFF *OFF X WATER METER OFF OFF ON X % POST BLEED OFF ON OFF X PERCENT TIMER ON OFF OFF X FALLING SET POINT X X X OFF RISING SET POINT X X X *ON * DEFAULT SETTING limit timer with a rising set point. 10

4.3 Controller Programming Press the Mode button to advance to the setting to be changed indicated by the function s LED. To enter programming mode press and hold the Mode [m] button for five seconds. The function s LED will begin to flash when the programming mode has been activated. Use the [Up]/[Down] buttons to modify the programmable parameters. During programming normal controller operation is suspended. If no keys are pressed for 30 seconds the controller will exit programming mode and return to normal operation. 4.3.1 Control Modes Listed below are the different control modes of the MicroTrac controller. Each control mode uses simple parameters for user modifications. Limit Timer - This control mode causes the Bleed and Feed output to energize when the conductivity exceeds the Conductivity setpoint. The Bleed and Feed limit timers can be activated to prevent over-feeding of chemicals. LED Range Function BLEED 0-08:00 hh:mm Optional limit timer. Set this value to the maximum amount of time a Bleed cycle should take before going into an alarm condition. Leaving this timer set to 0 disables this function. The time value is adjusted in 15 minute increments. us 1-9,999 This shows the current conductivity value. Set Point 1-9,999 Conductivity Setpoint. Set this value to the maximum conductivity value before the Bleed output energizes. Feed 0-8:00 hh:mm Optional limit timer. Set this value to the maximum amount of time the Feed output should energize before going into an alarm condition. Once this timer expires the Feed output will de-energize. The time value is adjusted in 15 minute increments. Water Meter This control mode causes the Feed output to energize when a programmed number of pulses are detected on the water meter input terminal. % Post Bleed This control mode causes the Feed output to energize following a Bleed cycle. The amount of time the Feed output stays energized is based on the programmed percentage of the prior Bleed cycle. 11

LED Range Function BLEED 0-08:00 hh:mm Optional limit timer. Set this value to the maximum amount of time a Bleed cycle should take before going into an alarm condition. Leaving this timer set to 0 disables this function. The time value is adjusted in 15 minute increments. us 1-9,999 This shows the current conductivity value. Set Point 1-9,999 Conductivity Setpoint. Set this value to the maximum conductivity value before the Bleed output energizes. Feed Percent + Time Percentage Set this value to a percentage of the prior Bleed cycle the Feed output should energize. Example: Percent=25, Bleed cycle took 14 minutes, the Feed output would energize for 25% of 14 minutes, or 3.5 minutes. Range = 0-100. Time Optional limit timer. Set this value to the maximum amount of time the Feed output should energize before going into an alarm condition. Once this timer expires the Feed output will de-energize. Range = 0-08:00, hh:mm. The time value is adjusted in 15 minute increments. Percent Timer This control mode causes the Feed output to energize based on a percentage of a fixed time cycle. The cycle time is base on a fixed 10-minute cycle. Once the 10-minute cycle completes the cycle will be restarted again. LED Range Function BLEED 0-08:00 hh:mm Optional limit timer. Set this value to the maximum amount of time a Bleed cycle should take before going into an alarm condition. Leaving this timer set to 0 disables this function. us 1-9,999 This shows the current conductivity value. Set Point 1-9,999 Conductivity Setpoint. Set this value to the maximum conductivity value before the Bleed output energizes. Feed Percent Percentage Set this value to a percentage of the 10-minute cycle time. Example: Percent=20, cycle time of 10 minutes, the Feed output would energize for 20% of 10 minutes, or 2 minutes. Range = 0-100. 4.3.2 Conductivity Set Point Set this value to the highest conductivity point the controller will allow before a bleed and feed cycle begins. When the system conductivity reaches this set point the bleed and feed control outputs will energize. When the system conductivity falls to the conductivity set point minus 5% the bleed and feed cycle will terminate and the control outputs will de-energize. The Conductivity Set Point can be changed with the [Up]/[Down] buttons once in programming mode. The maximum setting is 9999 us/cm. To save the set point, press the Mode [m] button. 12

The set point differential is fixed at 5% below the set point. For example, if the set point is set to 1000uS/cm the bleed and feed outputs will energize at 1000uS/cm and de-energize at 950uS/cm. 4.4 Alarm Conditions Flow Alarm With a loss of flow the two (red) LED s will flash and the display will read Err Flo. The outputs will de-energize. This alarm will reset automatically with the resumption of flow. Feed Limit Timer Alarm When the Feed Limit time is exceeded the two red LED s and the blue LED will flash and the display will read Err Lit and the Feed relay will de-energize. This alarm is reset by: pressing the M (Mode) button, a flow cycle, or conductivity reaching the set point and differential. Bleed Limit Timer Alarm When the Bleed Limit time is exceeded the two red LED s and the green LED will flash and the display will read Err Lit. This alarm is reset by: pressing the M (Mode) button, a flow cycle, or conductivity reaching the set point and differential. This will not de-energize the bleed relay, only reset the timer. Bleed and Feed Limit Timer Alarm When the Bleed and Feed Limit time is exceeded, all the LED s will flash and the display will read Err Lit. This alarm is reset by pressing the M (Mode) button, a flow cycle, or conductivity reaching the set point and differential. Bleed Limit Alarms: will not de-energize the Bleed relay. Conductivity Over Range Alarm (Rising Set Point) If the conductivity is over 9,999uS/cm, all the LED s will flash and the display will read Err 9,999 and the Bleed relay will remain on. This alarm is reset by pressing the M (Mode) button once the conductivity is within range. Both Limit Timers will reset if the conductivity reading changes to above or below the set point and differential. 13

5. Sensor Calibration The controller is factory calibrated and requires no user adjustments. Some deviation in the reading may be expected when compared to a hand-held tester. However, if you wish to perform a calibration, follow this procedure: 1. Place the probe in the process that it will normally be installed in and allow flow across the probe for approximately 15 minutes. This will allow the probe temperature to equalize. 2. While the us LED is steady press and hold the m mode button for five seconds until the controller flashes Cal. Release the m button. 1. The controller will now display the actual conductivity reading from the probe. Use the up and down buttons to change the reading until it matches your hand-held s reading. If you press and hold the up or down buttons, the displayed value will change very quickly. 4. When finished press the m button once. IMPORTANT! For optimum performance, make sure that the system conductivity is near the set point that you intend to operate the system. The calibration process is now complete. 6. Factory Default Values Set point: Bleed Limit timer: Feed Limit timer: 7. Specifications Controller Enclosure Enclosure Dimensions Power supply Fuses Display Set Point range Set Point differential (Hysteresis) Accuracy 1500µS/cm 00:00, HH:MM 00:00, HH:MM NEMA 4X / Designed to meet IP65 6.4 in. x 2.5 in. x 3.2 in. (163 x 64 x 82mm) 120 or 220 VAC, 50/60 Hz. F1 & F2: 5A, IEC 60127-2 250 VAC Time-Lag T F3: 1A, 2AG, Time Lag, 250VAC (Note: F1 is not serviceable in the field.) All fuses are UL, CSA recognized or listed. LCD 0-9,999 µs/cm range 1µS/cm resolution 0-9,999 µs/cm range 1µS/cm increments Fixed 5% below the set point +/- 2% of scale 14

Maximum Relay Output Current 120 VAC 4A Resistive/General use 4LRA/FLA, 1/10HP (motors) 220 VAC 4A Resistive/General use Not rated for motors Probe Maximum temperature Temperature compensation range Maximum pressure Probe type Maximum cable length Materials of construction Thread size Maximum outside diameter Flow Switch Maximum temperature Maximum pressure Activate flow rate Materials of construction 122 F (50 C) 32 F 122 F (0 50 C) 125 PSI (8.6 BAR) Toroidal 98.4 Feet (30 Meters) Polypropylene.5 in. Standard thread - excludes tee and reducer bushing 1.5 in. (38 mm)- Excludes Tee and Reducer 127 F (52 C) 125 PSI (8,6 BAR) Approximately 1 GPM (3,785 LPM) PVC and Glass filled Polypropylene Flow Switch Conductivity probe with tee Fig. 6 Fig. 7 15

8. Trouble Shooting Guide Symptom Probable Cause Possible Solution Controller does not power up Controller powers up but displays "Flo Err" Controller powers up but displays "Cond Err" Controller powers up but displays "Lit Err" Controller powers up but displays "9999 Err" Conductivity reading on controller does not match a hand-held reading. No power supplied to controller Insure that correct voltage is supplied to controller. Check circuit breaker supplying power to the controller. Fuse is blown Check/replace fuse (see Figure 3, Page 8) Probe wiring incorrect Check probe wiring (see Figure 3, Page 8) Insufficient flow through flow switch Flow switch not connected. Flow switch stuck. Flow switch cap bad. Bad shuttle. Ensure there is enough of a pressure differential from the inlet of the flow switch and the outlet to achieve at least 1 GPM (3.8 LPM) of flow Check flow switch connections (see Figure 3, Page 8) Clean flow sensor Check for wire integrity or replace flow cap. Replace shuttle Loose conductivity probe wire Check probe wiring (See Figure 3, Page 8) Bad Conductivity probe User set Limit timer has expired Conductivity over maximum range Probe wiring incorrect Bad Conductivity probe Conductivity reading is within specification. Replace probe. Reset limit by pressing the M (Mode) button Reduce the system conductivity. Reset limit by pressing the M (Mode) button when conductivity is back in range. Check probe wiring (see Figure 3, Page8) Replace sensor Due to variations in hand-held meters, conductivity standard solutions, temperature compensation, and the controller s accuracy of +/- 2% of scale, the reading on the controller may not match that of your hand-held tester. 16

9. Controller Mounting Dimensions Fig. 8 17

10. Addendum: MicroTrac PC Board Replacement 4 Disconnect input power cord from AC Mains Receptacle prior to opening the MicroTrac controller. With the input power disconnected, the MicroTrac LCD and LEDs will be off. 1. Remove the four screws that retain the front panel and remove it. 2. Unplug Bleed, Supply and Dose Terminal Blocks. 3. Using and insulated screw driver, remove 4 PCB mounting screws located at each corner of the PCB assembly. 4. Remove the MicroTrac PCBA to be replaced from the enclosure. Note: the flow, water meter and probe cables are still attached. 5. Install the new MicroTrac PCBA into the top enclosure. Ensure that the LCD, buttons and LEDs are correctly aligned in the top enclosure. 6. Secure the new board with the 4 mounting screws located at each corner of the MicroTrac PCB Assembly (PCBA). 7. Transfer the flow, water meter and probe cables from the MicroTrac PCBA being replaced to the new PCBA. Ensure that connections match the silkscreen on the new MicroTrac PCBA. 8. Plug the Bleed, Supply and Dose Terminal Blocks into the new MicroTrac PCBA. Ensure that connections match the silkscreen on the new PCBA. 9. With an ohm meter, check that the center conductor of the Supply Terminal Block is connected to the ground terminal of the disconnected input power cord. 10. Set SW1 on the new MicroTrac PCBA to the same settings as the MicroTrac PCBA being replaced. 11. Visually inspect all connections. 12. Use an ohm meter on the disconnected plug of the input power cord and check for low resistances (less than 1 ohm) between Line to Line and line to ground. 13. Disconnect the meter, remove all tools and power the MicroTrac on. The display will the splash screen and start menu will be shown. 4 Trained service personnel are required for all electrical connections. This product does not contain operator serviceable parts. 18

11. MICROtrac Factory Service Policy Your MICROtrac controller is a state of the art microprocessor based controller. If you are experiencing a problem with your Microtrac controller, first consult the troubleshooting guide in this manual. If the problem cannot be resolved contact Technical Services for assistance. PULSAFEEDER INC. (SPO) 27101 AIRPORT ROAD PUNTA GORDA, FL 33982 941-575-3800 Trained technicians are available to help diagnose your controller or process problems. All returns require a Return Authorization number to be issued by Pulsafeeder. Parts purchased to correct a warranty issue may be credited after an examination of original parts by Pulsafeeder. Warranty parts returned as defective which test good will be sent back freight collect. No credit will be issued on any replacement electronic parts. Any modifications or out-of-warranty repairs will be subject to associate parts and labor costs. 19

EC Declaration of Conformity We, Pulsafeeder Inc., declare under sole responsibility that Microtrac equipment to which this declaration relates is in sole conformity with relevant sections of the applicable EC standards and other normative documents listed on this document. If changes are made to the product which is covered by this declaration of conformity, the declaration of conformity is no longer valid. - Radiated emissions EN 61326 - Harmonic current emissions (EN 61000-3-2-1995+A14:1998) - Voltage fluctuations and flicker (EN 61000-3-3: 1995) - Electrostatic Discharge Immunity Test (EN 61000-4-2:95) - Radiated immunity test (EN 61000-4-3:96) - Electrical Fast Transient/Burst Immunity Test (EN 61000-4-4:95) - Surge Immunity Test (EN 61000-4-5:95) - Immunity to conducted disturbances (EN 61000-4-6:96) - Power Frequency Magnetic Field Immunity Test (EN 61000-4-8:93) - Voltage Dips, Short Interruptions and Voltage Variations Immunity Tests (EN61000-4-11:1994) - 2002/96/EG (WEEE) compliant - RoHS compliant 20

USA Pulsafeeder, Inc. 27101 Airport Road Punta Gorda, FL 33982 USA (941) 575-3800 www.pulsa.com European Union (EU) PULSAFEEDER-Europe Via Kennedy, 12-20090 Segrate Milano Italy 21