F650 Firmware Release Notes / History (Rev 10)

Similar documents
UR Universal Relay Series

750/760 Feeder Management Relay Instruction Manual

G650. GE Consumer & Industrial Multilin. Generator Protection & Control System Instruction manual GEK A

F650 - More than Feeder Protection & Control. GE Consumer & Industrial Multilin

DNP3 Communications Protocol

UR Universal Relay Series

Multilin C650. Bay Control & Monitoring System. Flexible Control. Monitoring & Metering. EnerVista Software. Key Benefits.

UR Universal Relay Series

U lity network. system Q sys. Interconnected P sys. P load Q load. P gen Q gen. Generator network

GE Multilin 350 Feeder Protection Relay Specifications

UR Universal Relay Series

Function permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%

SIA-B. Overcurrent & Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered / Standard CTs. Main characteristics

Version 7.7x Release Notes

IEC Upgrade Instructions

CURRENT PROTECTION RELAY SMPR-1

MiCOM P521. Fast feeder differential protection

UR Universal Relay Series

GE Power Management. UR F60 Feeder Management Relay An integrated feeder protection and metering solution

Release 5.83 of the Universal Relay (UR) series introduces improvements for general and protection functions. Highlights of version 5.

UR Universal Relay Series

HighPROTEC Troubleshooting Guide

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

Metering Devices, Protective Relays, Software and Connectivity. Pre-Wired Control Power, Voltage and CT Inputs

Multilin 650 Family. Firmware v7.60, Software v7.60 Release Note. GE Grid Solutions. Summary

Multilin F650. Grid Solutions. Feeder Protection & Bay Controller. Protection & Control. Monitoring & Metering. EnerVista Software.

Bus Bar Protection Relay B-PRO 4000

Multilin F650. Feeder Protection & Bay Controller. Protection & Control. Monitoring & Metering. EnerVista Software. Key Benefits.

HighPROTEC Troubleshooting Guide

Version 7.6x Release Notes

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

g GE Power Management UR - The Universal Relay

SIL-A. Overcurrent and Earth Fault Relay for Primary and Secondary Distribution. Main characteristics

SDR recloser. A PH Fault B PH Fault C PH Fault. Ground Fault. SGF Lockout Aux Power OK. Recloser OK

PQM4000 and PQM4000 PQM4000RGW. Class A DIN 192x144 power quality analyzer for CTs. Class A certified in compliance with IEC/EN :2015 Ed.

UR Plus Series. Revision 1.73 Release Notes. GE Digital Energy. Overview. GE Publication Number: GER Summary. Copyright 2013 GE Multilin Inc.

SIA-C. Overcurrent and Earth Fault Protection Relay for Secondary Distribution. Dual & Self Powered. Main characteristics

MiCOM P122C Time-Overcurrent Protection

MiCOM P521. Fast Feeder Differential Protection

EPM Multilin ADVANCED POWER QUALITY METER. High Performance Power Quality and Transient Recorder Meter KEY BENEFITS APPLICATIONS FEATURES

Current Fault Signatures and Analysis Auto-calibrating metrology means the meter maintains its accuracy over temperature and time

M60 Motor Relay. UR Series Instruction Manual. GE Industrial Systems. Title Page. M60 Revision: 3.4x

Protection Relays PHASE & RESIDUAL OVERCURRENT

Content REF615 Technical Presentation

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

FP5000. Refer to for the latest information on this constantly evolving product

Accessing the AXM-WEB at Admin level

Recloser Controller for feeder protection and automation siemens.com/distribution-automation

MiCOM P123R. Overcurrent Relays P123R/EN AD/A11. Upgrade Documentation

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

N60 Network Stability and Synchrophasor Measurement System

PowerXL DG1 Firmware Release Note

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

PQM4000 and PQM4000RGW

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

Firmware Revision History and Upgrade Instructions

SE-MON330 SOFTWARE MANUAL

Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation

IEC OBJECT MODELS OF MULTIFUNCTIONAL PROTECTION RELAYS

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

B30 Bus Differential Relay

F650 Feeder Management Relay & Bay Control

A low-cost, economical solution for distribution feeder protection

INSTALLATION & COMMISIONING GUIDE

REL52001 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, 2 x RJ-45

MIVII. GE Consumer & Industrial Multilin. Digital Voltage and Frequency Relay Instruction manual GEK E. Copyright 2007 GE Multilin

FP-5000 Feeder Protection

Substation Automation Products. Line differential protection RED670 Relion 670 series

SE-330 SERIES (NEW REVISION) MODBUS/TCP INTERFACE

Electrical Integration with Smart Communication

N60 Network Stability and Security Relay

Grid Automation Controller COM600 How it fits into the Smart Grid?

SACE Emax 2 Specification guide

C30. Controller System. Instruction Manual AF2. GE Grid Solutions. Product version: 7.6x GE publication code: AF2 (GEK A)

Generator Management Relay COMMUNICATIONS GUIDE

with Backlight Graphic LCD Screen

B30 Bus Differential Relay

Advanced distribution feeder solution with integrated protection, monitoring, and control

Digital multimeters DMG

UMG 511. Class A EN UMG 511 Class A power quality analyzer. according to EN50160, IEEE 519, ITIC, IEC Areas of application

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

NPW800R RETROFITTING. Power and Volatge Protection Relay

SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.

MIN II. Complete numerical ground directional protection. Digital Energy Multilin. Protection and Control. Monitoring and Metering.

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Protect induction and synchronous motors with one relay

Relion 615 series Transformer Protection and Control RET615 Ver. 2.0 Technical Presentation

TRAINING GUIDE LEVEL 3 MODBUS WRITE IMPORT COMMAND

7SR242 Duobias Multi-Function 2-Winding Transformer Protection Relay

CPU 412H. Function. Parameterizable properties

SCADAPack ES. Smart RTU

SIA C. Self-powered overcurrent relay USER MANUAL

DCU 305 R2. Communication Manual. Auto-Maskin AS. Page 1 of 25

Communications guide. Line Distance Protection System * F1* GE Digital Energy. Title page

Multilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications

PQM - Power Quality Monitoring

SCADAPack ES. Smart RTU

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

Transcription:

1.00 2.00 First version of the product (Basic Model F1G0) Full protection scheme F650BABF1G0HI August 30 th 2002 1.11 2.00 New model F2G0 (inputs and outputs board type 2) F650BABF2G0HI October 14 th 2002 1.13 2.20 Snapshot Events included (New and All) Oscillography up to 4 records. Maximum 70 cycles at 64 samples per cycle, trip programmable via PLC. Broken Conductor protection function included. Boot program updated through F650PC program December 20 th 2002 1.14 2.20 DNP 3.0 Level 2 protocol included, over TCP/IP and UDP/IP IRIG_B synchronization January 22 nd 1.20 2.25 Programmable Graphical display Calibration included to improve measurement accuracy January 28 th 1.30 2.25 Sensitive ground directional unit Isolated Ground directional unit (in 5 th current transformer) Energy measurements March 31 st 1.31 2.25 Enhancements in 60 Hz measurements Extended Settings Range in Negative Sequence Overcurrent function (46) April 9 th 1.33 2.30 1.44 2.30 Forward Power function (32FP) Demand 51PL function included (besides existing 51PH) Control Events Alarms Modbus over TCP/IP May 9 th July 24 th 1.48 2.30 Changes in 67 units in reverse mode Modbus TCP/IP enhancement September 5th 1

1.50 2.30 1.61 2.35 The following operation curves have been added to F650 functionality: IEC Long-Time Inverse IEC Short-Time Inverse ANSI Extremely Inverse ANSI Very Inverse ANSI Normally Inverse ANSI Moderately Inverse Rectifier Curve User Curve A/B/C/D - Flex Curve Note: User Curves allow the user to program any non-standard curve type by selecting, point by point, the Operation time. HARDWARE Voltage Range:Voltage Metering Range expanded from (2 to 200 Volts) to (2 to 275V) CIO Module: For those applications requiring a high number of inputs and outputs, F650 units can be connected to a CIO module (Remote CAN Bus I/O module) for using up to 2 additional boards. ModBus Protocol: Modbus User Map Virtual Inputs (control over internal logic variables, which can be used in the configurable logic). DNP 3.0 Protocol New Metering scale factors Switchgear bits mapped to binary points Possibility of restricting the binary points map by setting HMI Configurable Main Screen: The main screen offers the possibility to select the initial logo, a simplified Metering screen showing primary values, or both. Snapshot Events: Possibility of viewing snapshot events from the relay display in models without graphical display. Configuration: LED Reset by communications using the configurable logic Monitoring of phasor measurements in module and argument Snapshot Events: Possibility of reading the Snapshot events in Binary and ASCII format via Modbus Oscillography: The oscillography function has been improved to offer the possibility of creating up to a maximum of 20 oscillography records, with possibility to create concatenated oscillographies. Oscillography records can be obtained via communications using serial messaging (ModBus) or Ethernet (TCP/IP or TFTP). Fault Report: This version incorporates the tool to visualize and store the information from October 31 st April 30 th 2004 2

1.62 2.35 1.70 2.35 1.72 2.35 1.80 2.35 the last ten faults produced. This report can be shown on the relay display. The fault report will be available on the relay display and via communications, either on ModBus (serial) or TCP/IP. Data Logger: It allows registering 16 channels among all the available analog measures in the relay. The information provided by the data logger can be obtained via TCP/IP. Fault Report screen on HMI: Fault report information on display, selectable by setting WEB SERVER Web server tool has been upgraded to provide visualization of: Snapshot Events Control Events Alarms Oscillography Fault report Data Logger Metering Internal file management enhancement. IP Address maintenance after firmware upgrading. Latched Virtual Inputs maintenance after powering off and on the relay. Multilingual relay (French and English available) Multimaster DNP (3 masters) Measurement enhacement Sensitive Directional Power unit is included (32) Snapshot Events: Possibility to be enabled and disabled by setting. HMI: Enhanced HMI meeting Enervista F650 Setup structure. Multilingual Option available: The relay can be ordered in languages different from English, the relay always has English as default Languages Available now: French/English (F in ordering code request) English/English (former ordering code) Multilingual unit (French and English available). WEB SERVER Multilingual visualization of snapshot events, control events, oscillography, fault recorder, data logger, metering. HMI: New languages available: Russian/English (P in ordering code, basic display only) Spanish/English (S in ordering code) June 24 th 2004 F650BABF1G0HIF F650MFDF2G1LOF F650MFCF1G1LOF August 5 th 2004 December 1 st 2004 March 1 st 2005 3

2.00 3.00 1.82 4.00 2.20 4.00 New languages available: Russian and Spanish. Passwords included in EnerVista F650 Setup. WEB SERVER Multilingual visualization of snapshot events, control events, oscillography, fault recorder, data logger, metering. New languages available: Russian and Spanish. Modbus TCP communications enhacement. External CAN interruptions management enhancement. Decimal point included in PT and CT ratios. Power Factor measurement enhancement. Function 48 included. I2/I1 setting to select the minimum I1 inhibition current level of the unit. TOC operation level at 1.03 times the pickup (1.05 in previous releases). Neutral units measures management enhancement. Startup Enhancement. (product notification 1.72) Time Stamp for switchgear control events enhancement. HARDWARE New options for Rear Serial Comm. Board 1 C: cable remote CAN bus I/O M: RS485 + cable remote CAN bus I/O New options for Rear Ethernet Comm. Board 2 E: Redundant 10/100 Base TX New options for I/O Boards (available for slot G and CIO modules) 4: 32 digital inputs 5: 16 digital inputs + 8 analog inputs Protocol IEC 61850 GSSE Client/server implementation SNTP Synchronization (Clock time obtained over an Ethernet network). File system management enhancement in boot code 4.00 Measurements enhancement in 1.82 firmware version Data Logger visualization changes. File name available in Config file converter tool. DNP Scale factor correction. IRIGB synchronization: Date and time synchronization available. 980 ms delay correction. INPUTS/OUTPUTS Inputs Activation/Deactivation correction. June 30 th 2005 All models, excepting: Options 4 and 5 for inputs outputs boards. Option 6 for IEC61850 protocol 5. All models with hardware version 00 (See Note 1) Models not included: - Options 4 and 5 for inputs outputs boards - Option 6 for IEC61850 protocol. October 17 th 2005 November 25 TH 2005 4

3.00 4.00 Voltage threshold setting range from 20 to 230 Vdc. Debounce time settings: Timestamp before debounce time Setting range from 1 to 50 ms. Power calculations using ARON method. New measurements provided when using Delta connection and VN as auxiliary voltage input: Neutral voltage available. Phase to ground voltages available. Single phase power measurements available. Neutral, ground and sensitive ground directional units available with delta connection and VN as auxiliary voltage input. Minor changes in Forward Power elements. Ground current available in Fault report. Corrected 150 ms delay in Snapshot events measurements. Data Logger visualization changes. File name available in Config file converter tool. INPUTS/OUTPUTS Inputs Activation/Deactivation correction. Voltage threshold setting range from 20 to 230 Vdc. Debounce time settings: Timestamp before debounce time Setting range from 1 to 50 ms. Power calculations using ARON method. New measurements provided when using Delta connection and VN as auxiliary voltage input: Neutral voltage available. Phase to ground voltages available. Single phase power measurements available. Neutral, ground and sensitive ground directional units available with delta connection and VN as auxiliary voltage input. Minor changes in Forward Power elements. Ground current available in Fault report. Corrected 150 ms delay in Snapshot events measurements. DNP 3.0 Protocol: DNP Scale factor correction. IEC 61850 Protocol: New GSSE Control block added in LLN0 logical node. Unbuffered Reports (besides buffered reports available in former 2.00 version) New Data Set for contact inputs and report control blocks. All models with hardware version 01 (See Note 1) December 23rd 2005 5

3.20 4.10 IMPROVEMENTS IN REPORT CONTROL BLOCKS: The minimum value for the TrgOps parameter of Report control blocks have been reduced from 5000 to 500. Element BufTm naming modified (from BufTim to BufTm). The length of the OptFlds element has been resized from 9 to 10 bits. Flag BufOvfl correctly erased after PurgeBuf. Same entry times for all report segments. Buffered Reports are only sent if some bit is set in TrgOps (if IntgPd is set in BRCB) OTHER IMPROVEMENTS IN REPORT CONTROL BLOCKS: Buffer size reduction from 100 Kbytes to 50 Kbytes for Buffered Reports. Appropriate error codes returned for error messages. Minor changes in TCP/IP timed out connections. Minor changes in icd file for parse purposes and communication part addition. MMXU Logical node enhancement in measurements reading. Changes in commands execution for XCBR logical node. CODE Changes in the startup process for COM2 in 4.10 boot code version. ENERVISTA 650 SETUP IEC symbols in graphical display supported (N in ordering code). Config file converter tool improvement for CIO settings and configuration. Operating system upgrading process improvement. Settings files printing mode enhancement. Improved configuration in HMI for: Switchgear AR Status, AR Lockout, AR block and Fault type data. Confirmation request for saving files. Off line communication status enhancement. Texts Management in Configuration files for Chinese Language HMI IEC symbols in graphical display (N in ordering code). HMI management: Local/ remote /off by communications Switch off/on backlight by communications Red Leds lighting improvement. Available now configurable keys in chinese language. Two new measurements available in the synchrocheck module: Voltage difference ( V). Frequency difference ( f). Enhanced Offset Calibration mode. AND CONTROL All models with hardware version 01 and 02. N option (IEC Symbols) only available for hardware version 02. (See Note 1) April 21st 2006 6

Frequency rate of change function available (up to 3 units). Load Encroachment function available (up to 3 units) Maximum number of starts function available (1 unit) Analog Comparators available (up to 20). AR BLOCK mode enhancement. Syncrocheck settings enhancement. Pulse Counters available (up to 8). Changes in the naming of Energy frozen values. Fault report and oscillography trigger date accuracy enhancement. DNP 3.0 Protocol: Last fault data available.. IEC 61850 Protocol: Goose messages implementation. New Data Set for metering. Integrity report. Analog reports improvement. Virtual inputs Self-Reset management improvement. Writing procedure enhancement. XCBR and RREC operations enhancement. Note (1): Hardware Version: HW: 00 incorporates standard CPU board. HW: 01 incorporates enhanced CPU board. HW: 02 incorporates enhanced CPU board and enhanced HMI supporting IEC symbols for graphical display option. (N in ordering code) The hardware version of the relay can be verified in the identification label or in the bottom bar of EnerVista 650 Setup software version 3.00 or later when communicating with the relay. Note (2): Boot code 4.10 and firmware 3.20 must be upgraded from former versions using EnerVista 650 Setup 3.20 or later. 7