Carbon Monoxide Sensor - ModBus

Similar documents
Carbon Monoxide Transmitter

CDD ModBus Carbon Dioxide Detector

Installation Guide. Section 1 - Room... pg 03. Section 2 - Duct... pg 23. I-CDD3_Modbus Installation. Modbus Gas Transmitters I-CDD3 Series

CDD Carbon Dioxide Transmitter

CDD4 Duct Carbon Dioxide Transmitter

CDD4 Series Room CO2 Transmitter Installation Instructions

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

Differential Liquid/Gas Pressure Transmitter

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

H704-42(H)(E), H704-42/1(H)(E)

TPE 1464 Series Pressure Transducer

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

sensor, which compensates for ageing effects, is highly insensitive to pollution and offers outstanding long term stability.

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

RTD-W Installation Instructions

CDD3 Duct Carbon Dioxide Detector with BACnet

RTD-NET Installation Instructions

CDD3 Space Carbon Dioxide Detector with BACnet

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

RS-FS-N01 Wind speed transmitter user's Guide (485type)

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

P3-SCM. General Specifications

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

RXTP ROOM TEMPERATURE

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

Carbon Monoxide (CO) Gas Detection and Control System

RS-FX-N01 wind transmitter user's Guide (485type)

EX-RC1 Remote I/O Adapter

General Specifications. P2-SCM Serial Communications

ASTAT XB/XBm Remote Operator

EX-RC1 Remote I/O Adapter

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL

asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

RS485 MODBUS Module 8AO

VAT series controller and transmitter. Manual

RTD-RA. realtime. Installation Instructions. English A B. Installation Instructions Control Systems LEDS ALL DIMENSIONS IN MM

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

USER MANUAL. Modbus IHP24-A IHP24-AF IHP24-B IHP24-BF IHP24-F IHP24-I 1/26

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions

EX-RC1 Remote I/O Adapter

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

USER GUIDE PEL / PEL-M

INSTALLATION INSTRUCTIONS

Sidewinder Pumps Inc. AC C1D2 Timer/Controller

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

ASI Systems ML5740A Series

ASI Systems ML5720A Series

MU110-6U. Analog output module 6 channel. User guide

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

RXTH DUAL ROOM SENSOR / SWITCH

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

PowerLogic High Density Metering System 1-Meter Enclosure

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

Micro Motion MVD Direct Connect Meters

MODBUS MANUAL For the AccUView UV Transmission Monitor

H7625A, H7635A Humidity/Temperature Sensors

KCD-HP. KCD-HP200x, 300X. [Figures] Top : 1% Sensor probe Bottom left : 10% / 20% Sensor probe Bottom right : Holding bracket(optional) Measurement

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

EE160 - Humidity and Temperature Transmitter for HVAC Applications

Tango. alpha nea. Thermometers and controllers with digital communication - Series AM

Installation and Operation Manual. INTEGRA BTU Meter System

Screen 2.4" 3.5" Color Touch 4.3" Color Touch. RS232/485 Yes Yes Yes Yes Yes* USB device, mini-b Com Ports, separate order, user-installed

USER GUIDE PEL 8K / PEL 8K-M

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

INSTALLATION INSTRUCTIONS

MX200 SERIES Modbus Card 50P GE Zenith Controls. Operation and Maintenance Manual 50R-2200B 12/00

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120.

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE

MANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.

V E62B Snap-in I/O Module

MDP200 Series. Differential Pressure Sensor FEATURES APPLICATIONS DESCRIPTION

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

Analog Voltage Combination Module

Dual Module VCT. 5. Lexan Enclosure is Water & Corrosion Proof Contaminants will not affect the module as long as terminal strip is not immersed.

TOXALERT MODEL AIR 2000

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

205 CPU NETWORK ADAPTER F2-UNICON

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

485DRCI. Industrial RS-232 to RS-422/485 Converter B&B ELECTRONICS PRODUCT INFORMATION. Specifications Serial Technology

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

General Description V TR34/V130-J-TR34 V TR34/V350-J-TR34 V430J-R34 V R34/V130-J-R34 V R34/V350-J-R34

Communicative controller for VAV systems

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

Transcription:

Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read these instructions carefully before installing and commissioning the CO Sensor. Failure to follow these instructions may result in product damage. Do not use in an explosive or hazardous environment, with combustible or flammable gases, as a safety or emergency stop device or in any other application where failure of the product could result in personal injury. Take electrostatic discharge precautions during installation and do not exceed the device ratings. Mounting The CO enclosure should be mounted on a flat surface three to five feet from the floor of the area to be controlled. Do not mount the sensor near doors, opening windows, supply air diffusers or other known air disturbances. Avoid areas with vibrations or rapid temperature changes. Wiring Use 22 AWG shielded wire for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as motors. Disconnect the power supply before making any connections to prevent electrical shock or equipment damage. Make all connections in accordance with national and local codes. This device has a half-wave type power supply so use caution when wiring multiple devices so that the circuit ground point is the same on all devices and the controller. This device is reverse voltage protected and will not operate if the power supply is connected backwards. Connect the RS-485 network with twisted shielded pair to the terminals marked A-, B+ and SHIELD. The positive wire connects to B(+) and the negative wire connects to A(-) and the cable shield must be connected to the SHIELD terminal on each device. If the device is installed at either end of the network, an end-of-line (EOL) termination resistor (121 ohm) Mar 6, 2013 IN-CMD5B1000MOD-01-01 Page 1

should be installed in parallel to the A(-) and B(+) terminals. This device includes a network termination jumper and will connect the resistor correctly on the pcb. Simply move the pcb jumper to the EOL position and no external resistor is required. The ground wire of the shielded pair should be connected to earth ground at the end of the network and the master is not grounded. Do not run bus wiring in the same conduit as line voltage wiring. A network segment is a single shielded wire loop run between several devices (nodes) in a daisy chain configuration. The total segment length should be less than 4000 feet (1220 meters) and the maximum number of nodes on one segment is 255 for ModBus. Nodes are any device connected to the loop and include controllers, repeaters and sensors such as the CO Sensor but does not include the EOL terminators. To install more devices, or to increase the network length, repeaters will be required for proper communication. The maximum daisy chain length (segment) depends on transmission speed (baud rate), wire size and number of nodes. If communication is slow or unreliable, it may be necessary to wire two daisy chains to the controller with a repeater for each segment. Network Communication Each device must have a unique ModBus address for startup and it must be set before connection to the network. The local DIP switch is used to set the ModBus device address (1-255). The factory default baud rate is 9600. Other ModBus parameter settings can be found in the Specifications section. The CO Sensor operates as a slave. It will not communicate unless a master is connected to the network and sends a request for information, then the slave will answer. If the device does not communicate properly, first check that the communication wires are not reversed. Then check that the slave address, baud rate, transmission mode, parity bit, stop bit and RTU mode polynomial are correct. Set the device address as shown below. Each device on the network must have a unique address. DIP Switch Position ModBus 128 64 32 16 8 4 2 1 Address OFF OFF OFF OFF OFF OFF OFF ON 1 OFF OFF OFF OFF OFF OFF ON OFF 2 OFF OFF OFF OFF OFF OFF ON ON 3 OFF OFF OFF OFF OFF ON OFF OFF 4 ON ON ON ON ON ON ON OFF 254 ON ON ON ON ON ON ON ON 255 Mar 6, 2013 IN-CMD5B1000MOD-01-01 Page 2

ModBus Protocol This section describes the implementation of the Modbus protocol used in the CO Sensor. It is intended to assist control system programmers who may need to add support to their systems to communicate with this device. The CO Sensor communicates on a standard Modbus network using RTU mode transmission. It operates as a slave device (address from 01 to 255) and expects a Modbus master device to transmit queries, which it will answer. The network parameters (except for the device address) are fixed at the factory to the most common application. For custom parameters (such as a different baud rate or ASCII transmission mode) contact the factory. RTU Message Format Modbus Framing Data Bits Baud Rate 9600 Duplex 8 bit binary start bits --- 1 data bits --- 8 parity bits --- none stop bits --- 1 Half duplex Error Checking Latency Cyclical Redundancy Check () -16 reverse 0xA001 More than 3.5 characters --- minimum Framing Support and Bit Sequences RTU Mode Start 1 2 3 4 5 6 7 8 Stop Modbus Register Addressing Modbus Typical Units Address Offset Data Type Access 40001 +0 Word Read Notes Unsigned 16-bit integer 0x0000 = CO in normal status, 0x0001 = in abnormal status 40002 +1 PPM Word Read Unsigned 16-bit integer, CO value Mar 6, 2013 IN-CMD5B1000MOD-01-01 Page 3

Codes (RTU mode) 0x03 --- Read holding registers Query code (0x03) Starting address Starting address Quantity of registers Quantity of registers * Starting address = 0x0000 to 0xFFFF, Quantity of registers = 0x0000 to 0x007D Response code (0x03) Byte count 2N Register value Register value * N= Quantity of registers Exception response code + 0x80 Exception code 0x01, 0x02 or 0x03 * An exception response is only returned if the is correct Exception code 01 --- illegal function, 02 --- illegal address, 03 --- illegal data value The RTU function codes supported by the CO Sensor are shown below. 0x03 --- Read CO Status Query 0x03 0x00 0x00 0x00 0x01 Response 0x03 0x02 0x00 * = 0x0000 in normal status, 0x0001 in abnormal status 0x03 --- Read CO PPM Query 0x03 0x00 0x01 0x00 0x01 Response 0x03 0x02 (PPM) (PPM) * = 0x0000 to 0x01F4, corresponding to 0 to 500 ppm Exception response code + 0x80 Exception code * 0x01, 0x02 or 0x03 * An exception response is only returned if the is correct Exception code 01 --- illegal function, 02 --- illegal address, 03 --- illegal data value Mar 6, 2013 IN-CMD5B1000MOD-01-01 Page 4

Calibration The CO Sensor features a simple snap-mount sensor pcb that is pre-calibrated. This means that the entire sensor pcb can simply be replaced with a new calibrated pcb if desired without having to remove the enclosure. This sensor swap requires no tools and can be completed in seconds. Simply disconnect the device wiring, remove the old sensor pcb, snap in the new pcb and reconnect the device power. There is no need to make any adjustments or apply gas to the device using the sensor swap method. The device may also be calibrated or verified with CO gas if required. This requires a field calibration kit consisting of a bottle of gas (250 ppm CO in air for example), a tank pressure regulator with flow restrictor and the necessary tubing with a calibration cap to cover to the sensor. Calibration can be done at 20-27 C. Verification with gas can be done without removing the device cover. Simply apply gas using the calibration cap attached directly to the port on the cover and monitor the output value. Remove the device cover to perform an actual calibration. In this case, the gas calibration cap attaches to the sensor fixture inside the enclosure. The sensor must be continuously powered for at least 1/2 hour prior to calibration. Calibrate the sensor first in clean air with no CO gas present. Simply adjust the ZERO pot on the sensor board until a 0 ppm output is obtained. Then attach the gas supply. Turn the regulator on/off knob fully off and attach it to the 250 ppm gas bottle and firmly tighten it by hand. Moisten the sponge and squeeze out any excess water. Place the sponge in the cap so that it will not touch the sensor but does not plug the hole in the side of the cap. Attach the cap to the fixture over the sensor. Slowly turn the valve knob on the regulator to let the gas begin flowing. The regulator will restrict the flow rate to the specified 200 ml/min and the sponge will ensure the gas is in the right humidity range. Wait for 5 minutes and then adjust the SPAN pot on the sensor board until the output value reads 250 ppm. Close the valve on the tank and take the cap off from the sensor. Calibration is complete. If the gas cap is too loose on the fixtures, simply place a wrap of electrical tape around the cap to tighten it up. Verify With Cover In Place Calibrate With Cover Removed Mar 6, 2013 IN-CMD5B1000MOD-01-01 Page 5

Specifications Measurement................. Electrochemical Sample Method............... Diffusion Measurement Range........... 0-500 ppm Accuracy.................... 5 ppm or 5% of reading (whichever is greater) 0-50 C (32-122 F), 15-90 %RH Agency Approvals............ Sensor is UL Recognized for ANSI/UL-2034 and UL-2075, E240671 Operating Conditions.......... -20-50 C (-4-122 F), 15-90 %RH, 0.9-1.1 atm Stability..................... < 5% signal loss/year Response Time............... < 35 seconds for 90 % step change Typical Area Coverage......... 700 m 2 (7500 ft 2 ) or 15 m (50 ft) radius Power Supply................ 24 Vdc ± 20% Consumption................. 35 ma max ModBus Hardware................ 2-wire RS-485 Software................ Native ModBus MS/TP protocol (RTU) Baud Rate............... 9600 Slave Address Range....... Locally set to 1-255 Parity................... None Stop Bits................ 1................... A001 (-16 reverse) Wiring Connections........... Screw terminal block (14 to 22 AWG) Enclosure................... 2.8 w x 4.1 h x 1.9 d (71 x 104 x 48 mm) * Note - ModBus parameters may be factory customized Mar 6, 2013 IN-CMD5B1000MOD-01-01 Page 6