Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Similar documents
CDD4 Duct Carbon Dioxide Transmitter

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

CDD4 Series Room CO2 Transmitter Installation Instructions

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

CDD Carbon Dioxide Transmitter

Specifications - Installation and Operating Instructions. Duracell is a registered trademark of The Gillette Company.

Zone Pressure Touch Sensor - Standard Range

Zone Pressure Touch (ZPT) Sensor - Standard Range

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

Air Quality Solutions

PS-AULDP Series. Overview. Applications. Features & Benefits. Datasheet. Ultra Low Air Differential Pressure Transmitters

TPE 1464 Series Pressure Transducer

Carbon Monoxide Sensor - ModBus

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

MST2000 Loop Powered Multivariable SMARTFLOW Transmitter

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

MicroTrans EQ Signal Processor. Operation & Maintenance Manual

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz)

Installation, Operation and Maintenance Manual

MODELS PD230 AND PD1230 Installation Instructions

P216 Series Condenser Fan Speed Controller

DP DP2500 DP0250

Series ULT Ultrasonic Level Transmitter

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

Level-Lance Model 5400A

TOXALERT MODEL AIR 2000

MAXIMA+ Series Rotary Level Indicator

Installation, Operation and Maintenance Manual

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

AD-7830 Servo Amplifier

MAXIMA + Series ROTARY LEVEL CONTROL

Analyzer/Controller. ph/orp HART. Model 54e ph/orp ESSENTIAL INSTRUCTIONS WARNINGS RISK OF ELECTRICAL SHOCK

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

T7560A1036 Digital Wall Module

955 ebrik INSTALLATION MANUAL. Series ebrik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS LINEAR DISPLACEMENT TRANSDUCERS

Sidewinder Pumps Inc. AC C1D2 Timer/Controller

PV Rapid Shutdown device

SAVE THESE INSTRUCTIONS

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

EPWR Series. RoHS. Product Description. Available Products. Installation Instructions 01

Differential Liquid/Gas Pressure Transmitter

Model 675 DREXELBROOK. Shark Cage Submersible Level Transmitter DATA SHEET. Description. Features. Applications.

1. Installation. 2. Configuration - Operation. 3. Specifications. Safety

MODEL 245 / 345 High Range

OPERATION MANUAL MODEL TT-LP

ORB TM 4-20 ma Input Box Installation & Operation Manual

Configurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English

Operating Instructions Differential Pressure Transducer PS27

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter

TC22/23/24/25 Capacitance level transmitter - electronic preamplifi er

BA505C 2-wire 4/20mA manual setpoint station Issue 6

Operation Manual CX10 1/8 DIN Microcomputer Based Conductivity/Resistivity Controller

Resolver to Digital Expansion Board

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

PS/IO Circuit Board Retrofit

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

SP6R Level Controller Operation Manual

MODEL 692P TWO-WIRE ph TRANSMITTER. Manual No. 692P Revision 9-898

Installation and Operation Instructions I/CO 2, I/CO 2 -VDC, I/CO 2 -T

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157

OZONE SWITCH Model OS-6. OS-6 Features

Product Data. Model 675 Shark Cage Submersible Level Transmitter ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Net-Ritef Continuity and Wiremap Tester Trace-Ritef Tone Generator and Amplified Tone Tracer User's Guide.

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

Signet Pressure Transmitter

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

2 Table of Contents 1. TABLE OF CONTENTS. 1. Table of Contents Introduction Wiring Diagram Terminals Review...

Universal Safety Photo Eye UL MONITORED DEVICE

Druck DPI bar g. GE Infrastructure Sensing. Pressure Indicator User manual - K344

CLEVELAND CONTROLS MODEL 6650 DIGITAL MANOMETER INSTRUCTION MANUAL DM

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

OPERATOR S MANUAL 9000U ISOLATOR

Model 2657A-LIM-3 LO Interconnect Module

KOBOLD PDA Series Digital Pressure Transmitter

Type Quickstart (from device Version 2)

Carbon Monoxide (CO) Gas Detection and Control System

Airflow Pressure Sensor

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

Multi-Point Gas Detection and Control System

Smart Wireless THUM Adapter

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

A0-10 ANALOG OUTPUT. Instruction Manual April 2001 NALOG OUTPUT

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions

INSTRUCTIONS FOR MODEL 1000 DIGITAL PROCESS INDICATOR AND ALARM

Scanner 2000 microefm QuickStart. Installing the Scanner Remote Mount. Direct Mount NUFLO. Part No , Rev. A

3% VOLTAGE DROP. Installation Instructions for 100 Watt 24 Volt DC RGB DMX LED Power Supply SAVE THESE INSTRUCTIONS!

YT-870 / 875 Series. Rotork YTC Limited VERSION 1.06

Component identification

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application

MAN-652-OM1. 3 Oct 07 Revision G.R. G.A. 2 Jun 06 Revision A.G. G.A. 1 Feb 06 Revision A.G. G.A. Rev. Date DESCRIPTION Prepared Approved

Page 2 262/264 LaserMount User s Manual. Table of Contents

LAKEWOOD INSTRUMENTS MODEL 1575e WATER TREATMENT CONTROLLER

P2-04DA Analog Output. Removable Terminal Block Specifications

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

Transcription:

Document 476092 User and Service Manual Installation, Operation and Maintenance Manual Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Differential Pressure Controller Features: NEMA-4 and IP56 enclosure rating Factory calibrated 24 Vdc or 24 Vac input voltage Pressure ranges: 0-8.30 inches W.C. 0-22.4 inches W.C. 0-4.52 inches W.C. 0-83.04 inches W.C. 0-38.40 inches W.C. Selectable isolated output transmitter linear to differential pressure 4-20 ma 2-0 Vdc LCD display with user-friendly touch panel interface Temperature compensation Remote duct temperature sensor Programmable elevation English or metric readings Simple installation General Information This instruction manual provides installation, operating, maintenance, and parts information for Sure-Aire Series Differential Pressure Controllers. WARNING Improper installation, adjustment, alterations, service or maintenance can cause injury and property damage, as well as possible voiding of factory warranty. No person may install, operate, or maintain the Sure-Aire Differential Pressure Controller(s) and transmitters without first being fully trained and qualified in the installation, operation and maintenance, and carefully reading and understanding the contents of this manual. If you have any questions about these instructions, contact your local representative. CAUTION Risk of electrical shock! More than one disconnect switch may be required to de-energize the equipment before servicing. Table of Contents General Information.................. Differential Pressure Controller Features........ Installation....................... 2 Dimensions and Hole Mounting Patterns...... 2 Wiring and System Components.......... 2 Label and Order Information............ 2 Sure-Aire Controller Part Number.......... 2 Display Setting Options and Setup......... 3-4 4-20 ma Transmitter Calibration Procedure...... 5 2-0 Vdc Transmitter Calibration Procedure...... 6 Temperature Sensor.................. 7 Specifications..................... 7 Maintenance Log............... Backcover Our Commitment............... Backcover

Installation WARNING When wiring the instrument, you must follow industry standard practices for control and protection against electrostatic discharge (ESD). Failure to exercise good ESD practices may cause damage to the controller.. Mount the controller in the vertical plane using four #8-32 screws. Open the front cover by unscrewing the two captive thumb screws to gain access to the four mounting locations pictured at right. Note: Mount the Sure-Aire controller within 75 feet of the termination plate on the fan. 2. Use /4-inch nylon tubing to connect the corresponding high and low, /4-inch quick connect, pressure ports of the Sure-Aire controller to the high and low pressure ports of the termination plate on the fan. 3. Remove terminal block TB and perform wiring for the pins listed below. For liquid tight applications, use only /2-inch liquid tight conduit. Terminal Block TB: Input Power Pin = 24V, AC or DC (+ or -) Pin 2 = 24V, AC or DC (+ or -) Pin 3 = Earth Ground 4. Provide power to the controller to turn it on. 5. Select the desired Output Signal of the controller for the Building Automation System. Use the touch screen to select the 4-20 ma or 2-0 Vdc output signal via the controller s setup menu. (Refer to Display Setting Options and Setup section, Output Signal, pages 3 and 4). 6. Wire TB2 appropriately for the selected Output Signal in Step 5. Terminal Block TB2: Transmitter/Temperature Sensor Pin = 4-20 ma or 2-0 Vdc (+) (output) Note: 4 to 20 ma requires a load resistor 200-900 ohms Pin 2 = 4-20 ma or 2-0 Vdc (-) (output) Pin 3 = Shield Pin 4 = Remote Temperature Sensor (input) Pin 5 = Remote Temperature Sensor (input) Note: Signal isolator may be required when two or more output signals share a common connection at the PLC/controller. 7. If temperature compensation is desired, mount the provided temperature sensor in contact with the airstream. Wire the temperature sensor into TB2 and change Temperature Comp to Yes via the controller s setup menu. 8. When the above steps are completed, make sure the front cover is properly aligned to the housing and the two captive thumb screws are securely tightened. Dimensions and Hole Mounting Pattern 5-3/8 in. (36.5 mm) Label and Order Information The label providing details pertaining to the purchase order is located on the inside cover of the controller. Equipment for Measurement 4-5/32 in. (05.6 mm) 5 in. (27 mm) Wiring and System Components 24V, AC or DC 24V, AC or DC Earth Ground TB TB2 Description: CNTRL,SURE-AIRE,0-22.4 Fan Model: QEP Fan Size: 36 K Factor: 967 Elevation: 00 P/N: 384987 Sales Order: 6606573 Tag Mark: SF- 3-9/32 in. (83.3 mm) Reset Button High Pressure Port Low Pressure Port Temperature Sensor Shield 4-20 ma / 2-0 Vdc (-) 4-20 ma / 2-0 Vdc (+) TB 24 Volts AC or DC 2 6VA Max Input Power 3 Earth Ground TB2 Load Resistance 4 to 20 ma/ 2-0 Vdc (+) 200-900 Ohms 2 4 to 20 ma/ 2-0 Vdc (-) 3 Shield 4 Temperature 5 Sensor P.O.#0843 Date Code: 8/2 Schofield, WI 54476 U.S.A. Part Number Description 384986 CNTRL,SURE-AIRE,0-8.3 384987 CNTRL,SURE-AIRE, 0-22.4 384988 CNTRL,SURE-AIRE, 0-4.52 384989 CNTRL,SURE-AIRE, 0-83.04 384990 CNTRL,SURE-AIRE, 0-38.40 2

Display Setting Options and Setup Menu Options: Current settings are displayed in the main display area of the screen. To review current settings, press Up or Down to scroll through the various controller settings as outlined below. Press Home to return to the main screen. Elevation X-Mitter (output signal) Software Version K-Factor Sensor Installed Differential Pressure Measurement Sure-Air Controller Temperature Flow Temperature Flow Rate Measurement Air Density Measurement System:. Press Prev or Next to adjust, then press to store the value. English (default) Metric K Factor: Press Edit to change K Factor. Press Inc or Dec to adjust, then press to store the value. 200 to 30,000 0.000 CFM 3.96 ma Setup Up Down Home Sure-Aire Controller LCD Touch Display The following display setting options can be changed in the Setup menu of the controller: Measurement System: English K Factor: 200 Pressure Units: Press Edit to change pressure units. Press Prev or Next to adjust, then press to store the value. In WC (default) Ft WC mm WC cm WC PSI In Hg mm Hg mbar PA KPA - kilopascals (kpa = 000 Pa) HPA - hectopascals ( hpa = 00 Pa) Oz In. Air Flow Units: Press Edit to change Air Flow Units. Press Prev or Next to adjust, then press to store the value. CFM (default) m 3 /hr m 3 /min Main Display Value: Main Display Value. Press Prev or Next to adjust, then press to store the value. Flow (default) Pressure Temperature Air Density Output Signal None Secondary Display: Secondary Display. Press Prev or Next to adjust, then press to store the value. Flow Pressure Temperature Air Density Output Signal (default) None Pressure Unit: In WC Air Flow Unit: CFM Main Display Value: Flow Secondary Display Value: Output Signal 3

Display Brightness: brightness. Press Inc or Dec to adjust, then press to store the value. 0-00% (80% default) Display Brightness %: 80 Transmitter Min Value: Transmitter Min Value. Press Inc or Dec to adjust, then press to store the value. Transmitter Min Value: 827 NOTE: See Transmitter Calibration Elevation: Press Edit to change elevation. Press Inc or Dec to adjust, then press to store the value. 0-0,000 ft (0 ft default) Elevation: 800ft Transmitter Max Value: Transmitter Max Value. Press Inc or Dec to adjust, then press to store the value. NOTE: See Transmitter Calibration Transmitter Max Value: 720 Temperature Compensation: Press Edit to change Temperature Compensation. Press Prev or Next to adjust, then press to store the value. Yes (default) No Temperature Comp: Yes Note: If temperature compensation is set to No, the air density will be a function of standard temperature (70 F/2 C). Output Signal: Press Edit to change Output Signal type. Press Prev or Next to adjust, then press to store the value. 4-20 ma (default) 2-0 Vdc Note: Output signal is linear to differential pressure. The equation Output Signal: 4-20 ma provided on the Sure-Aire label adhered to the fan must be used to calculate volume. WARNING Due to load resistance change from product to product, it may be necessary to recalibrate the 4-20 ma transmitter. See 4-20 ma calibration procedure. 4

4-20 ma Transmitter Calibration Procedure WARNING Due to load resistance change from product to product, it may be necessary to recalibrate the 4-20 ma transmitter..0 Test Equipment. Digital Multimeter. Set multimeter to read ma DC.2 Load resistor. Select a series Load Resistor between 200 and 900 ohms. 2.0 Interconnect Wiring TB 24 Volts AC or DC 2 6VA Max Input Power 3 Earth Ground TB2 Load Resistance 4 to 20 ma/ 2-0 Vdc (+) 200-900 Ohms 2 4 to 20 ma/ 2-0 Vdc (-) 3 Shield 4 Temperature 5 Sensor 0.000 CFM 3.96 ma Setup Up Down Home Sure-Aire Controller LCD Touch Display 2.3 Transmitter Max Value. Transmitter Max Value: 720 2.4 Press Edit, then Inc or Dec until the digital multimeter reads exactly 20.00 ma. 2.5 Press to store the new value. 2.6 Press Exit to return to the main screen. 2.7 4-20 ma transmitter calibration completed. NOTE Apply a vacuum to the High Port and the 4-20 ma transmitter will track the span of the pressure range. i.e. The Sure-Aire controller with a pressure sensor of 0-4.5 in. W.C. installed, 4.00 ma = 0 in. W.C., 20.00 ma = 4.52 in. W.C. 2. Validate the controller is setup for 4-20 ma output signal. 2.2 Validate the power is off on the DC power supply and the Sure-Aire controller. 2.3 Validate the multimeter is set to read ma DC. 2.4 Select a series Load Resistor between 200 and 900 ohms and install one end to TB2-. 2.5 Interconnect the multimeter (+) probe to the other end of the load resistor. 2.6 Interconnect the multimeter (-) probe to TB2-2 to complete the current loop. 2.7 Apply power to the Sure-Aire controller. 2.8 Press the Setup button on the Touch Panel interface. 2.9 Keep pressing Next button until you reach the Transmitter Min Value screen. 2.0 Press Edit, then Inc or Dec until the digital multimeter reads exactly 4.00 ma. Transmitter Min Value: 827 2. Press to store the new value. 2.2 Press Next. 5

2-0 Vdc Output Signal Transmitter Calibration Procedure.0 Test Equipment. Digital multimeter. Set multimeter to read DC voltage..2 Make sure Output Signal type is set to 2-0 Vdc. 2.0 Interconnect Wiring TB 24 Volts AC or DC 2 6VA Max Input Power 3 Earth Ground 2.2 Press Edit, then Inc or Dec until the digital multimeter reads exactly 0.00 Vdc. 2.3 Press to store the new value. 2.4 Press Exit to return to the main screen 2.5 2-0 Vdc transmitter calibration completed. NOTE Apply a vacuum to the High Port and the 2-0 Vdc transmitter will track the span of the pressure range. i.e. The Sure-Aire controller with a pressure sensor of 0-4.5 in. W.C. installed, 2.00 Vdc = 0 in. W.C., 0.00 Vdc = 4.52 in. W.C. TB2 4 to 20 ma/ 2-0 Vdc (+) 2 4 to 20 ma/ 2-0 Vdc (-) 3 Shield 4 Temperature 5 Sensor Output Signal: 2-0v Edit Sure-Aire Controller LCD Touch Display 2. Validate the power is off on the DC power supply and the Sure-Aire controller. 2.2 Validate the multimeter is set to read DC voltage. 2.3 Interconnect the multimeter (+) probe to TB2 pin. 2.4 Interconnect the multimeter (-) probe to TB2 pin 2. 2.5 Apply power to the Sure-Aire controller. 2.6 Press the Setup button on the Touch Panel Interface. 2.7 Keep pressing the Next button until you reach the Transmitter Min Value screen. 2.8 Press Edit, then Inc or Dec until the digital multimeter reads exactly 2.00 Vdc Transmitter Min Value: 827 2.9 Press to store the new value. 2.0 Press Next. 2. Transmitter Max Value. Transmitter Max Value: 720 6

Temperature Sensor Interconnect the remote temperature sensor by connecting the temperature sensor to pins 4 and 5 of TB2. The Remote Temperature Sensor will adjust the air density value in the controller based on the sensor measurement when Temperature Compensation is set to Yes. This density compensation will affect the flow rate accordingly. If Temperature Compensation is set to No, the air density value will be a function of standard air (70 F/2 C). Specifications Service: Air and non-combustible, compatible gases Enclosure Rating: NEMA-4 and IP56 Dimensions: 5 x 5-3/8 x 2-/2 inches (27 x 36.5 x 63.5 mm) Mounting: Mount unit in vertical plane with #8-32 screws (4 hole locations) Accuracy: ±0.5% full pressure scale at 77 F (25 C) Thermal Effects: 0.05% / F (0.027% / C) from -3 thru 85 F (25 thru 85 C) Stability: < ±% per year Max. Pressure Limit: 72 psi (993 inches W.C.) Temperature Limits: 32 to 40 F (0 to 60 C) Power Requirements: 24 Vdc or 24 Vac input voltage Power Consumption: Power = 6VA Output Signal: User selectable. 4-20 ma (900 ohms max.) or 2-0 Vdc Connections: Euro-type removable terminal blocks with /2 inch watertight conduit fittings. Pressure Connections: /4 inch quick connect Weight:.5 lbs. Agency Approvals: ETL #392905 7

Maintenance Log Our Commitment As a result of our commitment to continuous improvement, reserves the right to change specifications without notice. Specific product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. s catalog provides additional information describing the equipment, fan performance, available accessories, and specification data. AMCA Publication 40-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org. Phone: (75) 359-67 Fax: (75) 355-2399 E-mail: gfcinfo@greenheck.com Website: www.greenheck.com 8 476092 Sure-Aire User and Service Manual, Rev. 4, August 203 Copyright 203 Fan Corporation