Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni)

Similar documents
MACX MCR-EX-SD LP(-SP)

PHOENIX CONTACT - 12/2007

PI-EX-ME-2NAM/COC-24VDC

PI-EX-ME-2NAM/COC-120VAC

MACX MCR-EX-SL-NAM-R(-SP)

MACX MCR-EX-SL-NAM-2RO(-SP)

PHOENIX CONTACT - 02/2008

PHOENIX CONTACT - 05/2007

PHOENIX CONTACT - 01/2008

4 Remote I/O. Digital Output Module 8-Channel Version Type 9475/ from Rev. F

MINI MCR-SL-CVS NC

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

ETD-BL-1T-OFF-CC- 10S

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

MINI MCR-SL-PT100-UI-200

Operating instructions (Safety-related part ATEX and IECEx) Inductive NAMUR sensors NN504A NN505A NN506A NN507A /00 08/2015

Digital Output Module 8-Channel Version for Zone 1 Series 9475/

MACX MCR-EX-SL-2NAM-T(-SP)

MACX MCR-EX-SL-RPSSI-I(-SP)

Safety Barriers. CEAG safety barriers can be used for all kinds of instrumentation applications.

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

Digital Output Module 8-Channel Version for Zone 2 Series 9475/

MACX MCR-SL-(2)I-2)I-ILP(-SP)

MINI MCR-SL-MUX-V8-FLK 16

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

MACX MCR-EX-SL-RTD-I...

Digital Output Module 4-Channel Version for Zone 1 Series 9475/

Safety instructions VEGATOR 121, 122

MACX MCR-EX-SL-RPSS-2I-2I

ADAMCZEWSKI. Ordering data AD-STVEX 710 GVD Option: Factory-software configuration as per customer specifications.

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S

Interface and Supply module. IPC 3x0i / PSC 3x0i

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

Digital Output Module 8-Channel Version for Zone 2 Series 9475/

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

Operating Instructions

4 â Active barrier RN221N with optional HART diagnosis. Technical Information

4 Remote I/O. Digital Output Module 8-Channel Version Series 9475/ from Rev. F

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Termination Board FC-GPCS-SAI16-PF. Features. Assembly. Function. Connection. SAI-1620m HART 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.

5 Fieldbus Technology

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet.

Safety instructions. IECEx TUN Ex ia IIC T6 Gb

4 Remote I/O. Analog Output Module HART Ex i / I.S. Outputs, 8 Channels Series 9466/12

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

Operating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505

Operating instructions

Terminal Block Catalog Numbers 1719-TB6, 1719-TB6S, 1719-TB8, 1719-TB8S, 1719-TB8Sx2, 1719-TB8x2

MINI MCR-SL-PT100-UI(-SP)(-NC)

FLEX Ex Spring Clamp Terminal Base

Separating and protective. Separating and protective instruments. VEGATRENN 149AEx Separator type KFDO Barrier type Product Information

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection

MANUAL Surge Protectors

Termination Board FC-GPCS-RIO16-PF. Features. Assembly. Function. Connection USIO/UPIO 24 V DC (I), 24 V DC (II) Fault. Zone 0, 1, 2 Div.

How to calculate an Intrinsically Safe loop approval.

Digital Positioner 8049

Functional safety manual RB223

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

SAFETY MANUAL SIL Switch Amplifier

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Intrinsically Safe Barriers

Magnetic Field Sensor for pneumatic cylinders BIM-INT-Y1X-H1141

Intrinsically safe batch controller Batching Master 110i

Proline Prowirl 72, 73

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail

Magnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-EG08-Y1X

Assembly MAU. MUX 4 Channels 8 Channels Zone 1

Magnetic field sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X

Operating Manual / IEC. Explosion-Proofed Junction Boxes, Polyester. Wallücker Bahndamm 7 DE Kirchlengern

Assembly. Front view. LED yellow/red: Status output Ι/ Fault signal Function. Switch Power Rail

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

ACT20X-(2)HTI-(2)SAO Temperature/mA converter. Safety Manual

Inductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97

Barriers. EB3N Discrete Input Barrier with Redundant Output

QUINT-DC-UPS/24DC/40. Extract from the online catalog. Order No.:

Inductive sensor NI3-EG08K-Y1-H1341

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5

Termination Board. HiCTB08-SCT-44C-SC-RA. Features. Assembly. Function. Connection. 24 V DC (I), 24 V DC (II), Fault. Zone 0, 1, 2 Div.

Cerabar S PMC71, PMP71, PMP ma HART, PROFIBUS PA, FOUNDATION Fieldbus

Magnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X-H1141

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

Inductive sensor BI5-EM18-Y1X-H1141

Assembly MAU. MUX 4 Channels 8 Channels Zone 1

English. Operating Manual. Universal Isolating Amplifier TV125M / ST125M. Save for later reference. Companies / Brands of GHM

Inductive sensor BI1.5-EG08-Y1-H1341

Redundancy Module QUINT-DIODE/40

QUINT-PS/ 1AC/24DC/ 5

HART Temperature Transmitter for up to SIL 2 applications

Inductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

Inductive dual sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933

Safety manual. This safety manual is valid for the following product versions: Version No. V1R0

MINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:

SUBCON-PLUS-PROFIB...

PHOENIX CONTACT Pin. SUBCON-PLUS M ARCNET, MULTI/MININET (B&R), SYSTEM 2003 (B&R), P-NET SUCONET K1, K2 (EATON/Moeller),

Inductive sensor For rotary actuators NI4-DSU35TC-2Y1X2

Transcription:

Data sheet 302040_en MTP300i-SIL-K Loop-powered Transmitter for Thermocouple Type K (NiCr-Ni) Properties 2-wire temperature transmitter for DIN rails Galvanic isolated TC-input with cold-junction compensation Signal pass-through time: without Butterworth filter 3 ms with Butterworth filter 38 ms Installation in zone 1 or 2 permissible Intrinsic safety according to IEC/EN 60079-11 SIL 2 according to IEC/EN 61508:2010 Error indication according to NAMUR NE 43 LED status indication Description The 2-wire temperature transmitter MTP300i-SIL-K has been designed for the operation of intrinsically safe thermocouple circuits installed in the Ex area. The TC input is equipped with a Pt100 sensor for the cold-junction compensation. The TC transmitter must be intrinsically safe supplied by a repeater power supply or ZENER barrier. The thermocouple signal is galvanic isolated. The device can be installed in zone 1 or 2 with the n (IEC/EN 60079-15) protection type. The device is an intrinsically safe electrical equipment for intrinsically safe circuits. It is designed for use in zone 1 or 2, if specific conditions are observed. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. Observe also the safety regulations and installation notes on page 6. Mütec Instruments GmbH Tel.: +49 (0) 4185-80 83-0 E-Mail: muetec@muetec.de Bei den Kämpen 26 Fax: +49 (0) 4185-80 83-80 Web: www.muetec.de D-21220 Seevetal-Ramelsloh

Table of Content 1 TECHNICAL DATA... 2 2 SAFETY REGULATIONS AND INSTALLATION NOTES... 6 3 INSTALLATION... 7 4 COMPARISON OF SAFETY DATA... 7 5 PRINCIPLE OF FUNCTION:... 8 6 SAFETY FUNCTION:... 8 7 SAFETY APPLICATIONS FOR SIL 2... 10 8 PFD CALCULATIONS... 11 Certificate Ex certificate IECEx BVS 14.0073 X Ex ib [ia Ga] IIC T4 Gb Functional Safety (SIL) SIL 2 according to EN 61508 Safety data according to IECEx for intrinsically safe circuits Power supply - Ex ib IIC (terminals 1 and 4) Voltage Ui 28 Vdc Current Ii 95 ma Power Pi 655 mw Effective inner capacity Ci 26 nf Effective inner inductivity Li negligible Thermocouple input - Ex ia IIC and Ex ib IIC (terminals 5 and 8, 9 and 12) Voltage Uo 1 Vdc Current Io 1.8 ma Power Po 0.5 mw Permissible outer capacity Co 10 μf Permissible outer inductivity Lo 100 mh Input signal (terminals 5 and 8) Thermocouple type NiCr-Ni K fixed range (see nameplate) Cold-junction compensation with Pt100 sensor ( see Fig. 3) -10 +70 C Output signal (terminals 1 and 4) Current proportional to the temperature Io 4 20 ma Maximum current Io < 24 ma Behavior by failure (according to NE 43) Io 3.6 ma Status indicator for power supply respectively ma signal Green LED Behavior by failure luminosity corresponds to 4 20 ma off 2

General data Signal pass-through time Input to output without Butterworth filter Input to output with Butterworth filter Transmission error Typical Temperature coefficient Typical 3 ms 38 ms (default) < 0.05 % (of final value) < 0.05 %/10 K Pt100 sensor error Class B: t = +/- (0.3 C + 0.005 x t) < 0.23 C at 70 C Cold-junction compensation error Temperature range 0 C to +50 C < 0.4 C Temperature range -10 C to +70 C < 1.0 C Linearization error Typical < 0.1 C Measured value deviation Typical < 0.6 C at 20 C Electric isolation Tested according norms & rules EN 60079-11 Electromagnetic compatibility Tested according norms & rules EN 61326-3-2 Current loop supply Voltage range (RLoad = 70 Ω 800 Ω) Current range Power dissipation Minimum (12.5 V x 4 ma) Maximum (28 V x 20 ma) Ambient temperature Operation Storage/transport 12.5 28 V > 3.5 < 24 ma 50 mw 560 mw -10 C to +70 C -20 C to +80 C Humidity Permissible operation humidity (no condensation) 10 % 95 % Housing Material Color Degree of protection Width x length x height (with connection terminal blocks) Inflammability class according to UL 94 Housing type for mounting Weight with terminal blocks Polyamide light grey IP20 22.5 x 115 x 108 mm V0 35 mm DIN rails approx. 200 g Connection data Solid (minimum/maximum) 0.2 mm 2 /2.5 mm 2 Stranded wire (minimum/maximum) 0.2 mm 2 /2.5 mm 2 AWG/kcmil (minimum/maximum) 24/14 Stripping length 7 mm Connection method plugable screw connection Tightening torque 0.5 0.6 Nm Installation Safe area: Install the device in a clean and dry environment. Ex area (zone 1 or 2): Install the device in a suitable housing with a minimum of IP54 degree of protection. 3

Dimensions Fig. 1 ZERO and SPAN adjustment Fig. 2 Pt100 cold-junction compensation error Fig. 3 4

Mounting and removal: Mount the module on a 35 mm DIN rail according to EN 60715 Install the module in a suitable housing to meet the requirements for the protection class Mounting: Snap-on foot below (left part of drawing) Removal: With a screwdriver (right part of drawing) Before start up, check the correct wiring and labelling of the intrinsically safe circuits Fig. 4 Connecting the cables: Permissible cable cross-section are 0.2 mm 2 to 2.5 mm 2. Stranded wires provided with ferrules. Screw connection: Insert the wire into the corresponding connection terminal block and use a screwdriver to tighten the screw in the opening above the connection terminal block. 5

Follow the installation instructions: NOTE: Installation, operation, and maintenance may only be carried out by qualified specialist personnel. When installing and operating the device, the applicable safety directives (including national safety directives), accident prevention regulations, as well as general technical regulations, must be observed. NOTE: The circuits inside the device must not be accessed. Do not repair the device yourself, but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. NOTE: The device is suitable for IP20 degree of protection if: It is installed outside potentially explosive areas The environment is clean and dry Install the device in a suitable housing with a suitable degree of protection in accordance with IEC 60529 in order to protect it from mechanical and electrical damage. For the safety data, please refer to the operating instructions and certificates (EC examination certificate, other approvals, if necessary). Safety regulations for installation in potentially explosive areas and regulations for intrinsically safe circuits: When carrying out measurements on the intrinsically safe side, be sure to observe the relevant regulations regarding the connection of intrinsically safe equipment. Only use approved devices for use in intrinsically safe circuits. If the device has been used in non-intrinsically safe circuits, it must not be used again in intrinsically safe circuits. Clearly label the module as being non-intrinsically safe. Installation in zone 1 or 2: The device is an intrinsically safe equipment of the Ex-i protection type and suitable for installation in zone 1. Observe the specified conditions for use in potentially explosive areas. Install the device in a suitable housing with a minimum of IP54 degree of protection and in accordance with DIN EN 60529. Installation in areas with a danger of dust explosions: The device is not designed for installation in areas with a danger of dust explosions. Connection to the intrinsically safe circuit in areas with a danger of dust explosions (zones 20, 21, and 22) is only permitted if the equipment connected to this circuit is approved for this zone (e.g., category 1D, 2D or 3D). 6

NOTE: Electrostatic discharge The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. Basic circuit diagram for 1 TC with connection terminals: Fig. 5 Input (intrinsically safe): Thermocouple with connection to terminal 5/+ and 8/- Power supply/output signal (intrinsically safe): Repeater power supply with connection to terminal 1/+ and 4/- Compare the safety data before connecting a device located in the Ex-i area to the MTP300i-SIL-K. Safety data for MTP300i-SIL-K: U i, I i, P i, L i, C i Repeater power supply: U o, I o, P o, L o, C o For the values for U o, I o, P o, L o and C o please refer to Safety data according to ATEX for intrinsically safe circuits on page 2. Ex-i requirements (simple circuits) Ui Uo Ii Io Pi Po Li + Lc Lo Ci + Cc Co (Lc is depend on the cables/lines used) (Cc is depend on the cables/lines used) 7

Fig. 6 The MTP300i-SIL-K has two galvanic isolated temperature channels and two separate constant current sources. This structure supports at best the diagnosis and monitoring of temperature sensors with wires and temperature measuring circuits. All internal function blocks of the transmitter and the external circuits are subject of a continuous selftest. The failure information according to NE43 (NAMUR Recommendation) is a transmitter output signal < 3.6 ma. Activation of the Safety Function: I a 3.6 ma A deviation > 4 % between the two galvanic isolated temperature channels or an internal failure leads to a value reduction of the ma output (< 3.6 ma). The output signal (see Fig. 6) returns after a break of about 7 to 9 seconds and the self monitoring checks again, whether the failure still is present and thus the shutdown must be repeated. Only an external failure (Thermocouple or wire break) leads to a permanent reduction of the ma-value in the supply circuit (< 3.6 ma). Fig. 7 The MTP300i-SIL-K has two galvanic isolated temperature channels with two separate constant current sources. This structure supports at best the diagnosis and monitoring of temperature sensors with wires and temperature measuring circuits. All internal function blocks of the transmitter and the external circuits are subject of a continuous selftest. The failure information according to NE43 (NAMUR Recommendation) is a transmitter output signal < 3.6 ma. 8

Sensor or cable break The transmitter output signal is permanently limited < 3.6 ma. Short circuit The transmitter output signal corresponds to the Pt100 temperature value of the cold-junction compensation. Monitoring of the two measurement channels Exceeds the deviation the value of 0.4 ma, so the transmitter output signal jumps periodically to the value of < 3.6 ma. Monitoring of the internal supply voltage Exceeds the deviation the value of 5 %, so the transmitter output signal jumps periodically to the value of < 3.6 ma. Monitoring of the internal supply current Exceeds the deviation the value of 5 %, so the transmitter output signal jumps periodically to the value of < 3.6 ma. Monitoring of the clock frequency Exceeds the deviation of clock frequency the value of 10 %, so the transmitter output signal jumps periodically to the value of < 3.6 ma. 9

Safety integrity requirements (see also technical report 4.139.18/Risknowlogy) Failure rates of temperature measurement channels: Type A device (according to IEC/EN 61508-2), Safety Integrity Level (SIL 2) λsd λsu λdd λdu SFF 0 FIT 78.5 FIT 61.3 FIT 4.7 FIT 96.8 % λsu includes failure that not cause a spurious trip SFF = Safe Failure Fraction FIT = Failure In Time (1 FIT = 1 failure / 10 9 h) PFDAVG values of MTP300i-SIL-K without TC-sensor(s): The beta factor is 2 % and was derived from IEC/EN 61508-6, Annex D T [PROOF] 1 Year 2 Years 5 Years 10 Years 20 Years PFDAVG 5.63E-05 1.11E-04 2.77E-04 5.54E-04 1.11E-03 % SIL 2 0.56 % 1.11 % 2.77 % 5.54 % 11.07 % PFDAVG = Average value of the Probability of Failure on Demand T [PROOF] = Proof test interval The calculated PFDAVG values are within the allowed range for SIL 2 according to table 2 of IEC/EN 61508-1, and do fulfill the requirement to not cover more than 11.1% of this range after 20 years. PFSAVG for 1 Year: 2.63E-05 PFSAVG = Average value of the Probability of Fail Safe Failure limit: The operating mode is based on low demand mode. The proportion of MTP300i-SIL on the PFDAVG of safety chain shall be not more 15 %. Sensors (2xTC) 35 % MTP300i-SIL 15 % Repeater power supply 35 % Processing 15 % Conditions: The failure rates of the components used remain constant throughout the period of use. Propagation of errors by the device in the system is not taken into consideration. The repair time (= replacement) should be 72 hours. The average temperature at which the device is to be used is +40 C. This is based on standard industrial conditions. The failure rates given refer to an ambient temperature of +40 C. For an ambient temperature of +60 C, you will need to multiply the failure rates by a factor of 2.5. The factor is based on empirical values gathered. Proof test Carry out the appropriate steps to prevent incorrect use. Example for TC type K: An input signal of 0 16.395 mv corresponds to a temperature range of 0 to 400 C. The output must be set to 4.00 20.00 ma. Setting 3.6 ma or > 22 ma verifies that the subsequent processing can provide signals outside the range. In the event of an error, the device must be replaced by an equivalent device. Restore the safety circuit to full functionality. Return to normal operation. 10

Failure rate of TC sensor: TC sensor without extension wire TC sensor with extension wire s [FIT] d [FIT] DC SFF s [FIT] d [FIT] DC SFF Low Stress 40 9 95 % 81.63 % 381 95 95 % 80.04 % High Stress 787 173 95 % 81.98 % 7600 1900 95 % 80.00 % Failure rate of extension wire: Extension wire s [FIT] d [FIT] DC SFF Low Stress 341 86 95 % 79.86 % High Stress 6813 1727 95 % 79.96 % Failure rate of TC sensor with extension wire by high stress: T [PROOF] 1 Year 2 Years 5 Years 10 Years 20 Years tce 291 510 1167 2262 4452 PFDAVG Sensor + Wire 5.53E-04 9.69E-04 2.22E-03 4.30E-03 8.46E-03 PFD formula for TC sensor: PFD AVG Sensor 0.5 x λdu x T λdu = (1 - DC) x λd Failure rate of a transmitter with measuring circuit: T [PROOF] 1 Year 2 Years 5 Years 10 Years 20 Years PFDAVG Sensor+Wire 5.53E-04 9.69E-04 2.22E-03 4.30E-03 8.46E-03 PFDAVG MTP300i 5.63E-05 1.11E-04 2.77E-04 5.54E-04 1.11E-03 PFDAVG total 6.09E-04 1.08E-03 2.49E-03 4.85E-03 9.57E-03 % SIL 2 6.1 % 10.8 % 24.9 % 48.5 % 95.7 % PFD formula for transmitter with measuring circuit: PFD AVG total = PFD AVG Sensor + Wire + PFD AVG MTP300i 11