Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Similar documents
Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Residual overvoltage relay

Synchro-check relay. Application

Feeder protection relay SPAA 341 C. Product Guide

Feeder protection relay

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

High impedance protection relay

Arc protection relay. Features Three-phase overcurrent function. Application

SPAA 341 C Feeder protection relay

Arc protection relay. Features Three-phase overcurrent function. Application

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

Feeder Protection Relay REF 610. Product Guide

Motor Protection Relay REM 610. Product Guide

Relion 611 series. 611 series Type Test Certificate

SPA-ZC 302. Profibus-DPV1/SPA Gateway. Product Guide. spa-zc302_rightco300

Communication Gateway COM 610. Product Guide

Overcurrent and Earth-Fault Relay REJ 525. Technical Reference Manual

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Protection Relays PHASE & RESIDUAL OVERCURRENT

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

General characteristics of C-type relay modules

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

SPA-ZC 17. Bus connection module SPA-ZC 17. User s manual and Technical description. Tx SC Rx BB BM MB MM SPA / RS 485 POWER SLAVE 1 MASTER 0

SPA-ZC 200/SPA-ZC 202 IEC /SPA-gateway Modules. Installation Manual

Data communication and reporting unit

Relion 610 series. Feeder Protection REF610 Product Guide

Protection and control. Sepam range Sepam 100 RT. Merlin Gerin Square D Telemecanique

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Data communication and reporting unit

For Transmission, Distribution and Machinery protection.

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

LON bus communication devices 1MRS MBG Page 1 Issued: April 1999 Status: New Data subject to change without notice

Contact protection relay

GRD130 - FEATURES APPLICATION

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Relion 610 series. Voltage Protection REU610 Product Guide

SREDU Double Connection Option Card for Lon Star Coupler RER 111

RT4B-110V/12A RECTIFIER

RT4F-48V/50A-WAC RECTIFIER

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Feeder Protection REF615. Product Guide

Technical specifications

RT4F-120V/20A-WAC RECTIFIER

FL MC 2000E (SM40) LC

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Binary output and supervision 520CSD01 Data sheet

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

DRTS 66. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Relays for Various Protection Applications / 7SV600

RER 123 Bus Connection Module. Technical Description

MiCOM P122C Time-Overcurrent Protection

RT12-240V/2.4kW Rectifier Specification

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

RT4F-110V/25A RECTIFIER

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

Model Number Structure

Electronic timer CT-ARS.11

Solid-state Timer H3YN

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

DRTS 33. The new generation of advanced three phase relay test set

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

Electronic timer CT-ERS.21

Switching relay CT-IRE with 1 c/o (SPDT) contact

Electronic timer CT-ERD.12

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

MIN II. Complete numerical ground directional protection. Digital Energy Multilin. Protection and Control. Monitoring and Metering.

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

Type VRLTC tap changer

Power Products. Station Automation COM600 Product Guide

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

Multifunction Transducer MT440

DRTS 64. The new generation of advanced test equipment for Relays, Energy meters, Transducers and Power quality meters.

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

DIAC/DIFC/DSFC. Single Phase Digital O/C. Single phase or ground overcurrent protection for industrial and utility power systems.

Analog output 520AOD01 Data sheet

Electronic timer CT-AHD.22

RT7-48V/6kW Specification

Switching Power Supply S82J. Ordering Information. Open-Frame, Covered-Frame, or Enclosed-Frame Type with Capacity Up to 600 W

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

Transcription:

Combined Overcurrent and Earth-fault Product Guide

Issued: April 1999 Status: Updated Version: C/18.04.2006 Data subject to change without notice Features Three-phase, low-set phase overcurrent unit with definite time or inverse definite minimum time (IDMT) characteristic Three-phase, high-set phase overcurrent unit with instantaneous or definite time operation Low-set earth-fault unit with definite time or inverse definite minimum time (IDMT) characteristic High-set earth-fault unit with instantaneous or definite time operation Built-in circuit-breaker failure protection Two heavy-duty and four signal output relays Output relay matrix allowing start or trip signals from the protection stages to be routed to the desired output relay Local display of measured and set values and data recorded at the moment of a fault Reading and writing of setting values either via local display and front panel push-buttons or from higher-level systems over the serial interface and the fibre-optic bus Self-supervision system continuously monitoring the operation of the electronics and the microprocessor Powerful software support for parameterization of the relay, for reading measured and recorded values, events, etc., and for storing readings Member of the SPACOM product family and ABB s Distribution Automation system CE marking according to the EC directive for EMC Application The combined overcurrent and earth-fault relay is intended to be used for the selective short-circuit and earth-fault protection of radial feeders in solidly earthed, resistance earthed or impedance earthed power systems. The integrated protection relay includes an overcurrent unit and an earth-fault unit with flexible tripping and signalling facilities. The overcurrent and earthfault relays can also be used for other applications requiring single-, two-, or three-phase overcurrent protection. The combined overcurrent and earth-fault relay includes a circuit-breaker failure protection unit. The combined overcurrent and earth-fault relay is part of ABB s Distribution Automation concept, the complete ABB solution for the control and management of electric power systems. 3

Design The combined overcurrent and earth-fault relay is a secondary relay to be connected to the current transformers of the object to be protected. The three-phase overcurrent unit and the earth-fault unit continuously measure the phase currents and the neutral current of the object. On detection of a fault the relay starts, trips the circuit breaker, provides an alarm signal, records fault data, etc., in accordance with the requirements of the application and the relay configuration. When the phase current exceeds the set start current of the low-set stage I>, the overcurrent unit starts and, after a preset start time, it delivers a start signal. When the set operate time, at definite time operation, or the calculated operate time, at inverse time operation, elapses, the overcurrent unit operates. In the same way, the high-set stage I>> of the overcurrent unit starts when the set start current is exceeded and delivers a start signal after the preset (~40 ms) start time. When the set operate time has elapsed, the overcurrent unit operates. When the earth-fault current exceeds the set start current of the low-set stage I 0 >, the earth-fault unit starts and, after a preset start time, it delivers a start signal. When the set operate time, at definite time operation, or the calculated operate time, at inverse time operation, elapses, the earth-fault unit operates. In the same way, the high-set stage I 0 >> of the earth-fault unit starts, when the set start current is exceeded, and delivers a start signal after the preset (~50 ms) start time. Once the set operate time has elapsed, the earth-fault unit operates. The low-set stage of the overcurrent unit and the low-set stage of the earth-fault unit may be given definite time or inverse definite minimum time (IDMT) characteristic. The IDMT characteristic includes six time/current curve sets. Four of the curve sets comply with the BS 142 and IEC 255 and are named Normal inverse, Very inverse, Extremely inverse and Long-time inverse. The two additional inverse time curve sets comply with ABB standards and are called RI and RXIDG. By appropriate configuration of the output relay matrix, the start signals of the overcurrent and earth-fault units are obtained as contact functions. The start signals can be used for blocking co-operating protection relays, and for signalling. The relay includes one external binary input, which is controlled by an external control voltage. The function of the control input is determined by a selector switch in the protection relay module. The control input can be used for blocking the operation of one or more protection stages, for resetting a latched output relay in the manual reset mode or for switching between main and second setting banks. Data communication The relay is provided with a serial interface on the rear panel. By means of a bus connection module type SPA-ZC 17 or SPA-ZC 21 the relay can be connected to the fibre-optic SPA bus. The bus connection module type SPA-ZC 21 is powered from the host relay, whereas the bus connection module SPA- ZC 17 is provided with a built-in power unit, which can be fed from an external secured power source. The relay communicates with higher-level data acquisition and control systems over the SPA bus. Self-supervision The relay incorporates a sophisticated selfsupervision system with auto-diagnosis, which increases the availability of the relay and the reliability of the system. The selfsupervision system continuously monitors the hardware and the software of the relay. The system also supervises the operation of the auxiliary supply module and the voltages generated by the module. When a permanent internal relay fault is detected, the IRF indicator on the relay front panel is lit. At the same time the output relay of the self-supervision system operates and a fault message is transmitted to the higherlevel system over the serial bus. Further, in most fault situations, a fault code is shown in the display of the protection relay module. The fault code indicates the type of the fault that has been detected. Auxiliary supply voltage The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module versions are available: type SPTU 240R1 for the supply voltage range 80 265 V ac/dc and type SPTU 48R1 for the supply voltage range 18 80 V dc. The power supply module forms the internal voltages required by the protection relay and the I/O module. 4

Technical data Table 1: Energizing inputs, overcurrent unit Terminals 1-3, 4-6, 7-9 1-2, 4-5, 7-8 Rated current I n 1 A 5 A Thermal withstand continuously 4 A 20 A capability for 10 s 25 A 100 A for 1 s 100 A 500 A Dynamic current Half-wave value 250 A 1250 A withstand capability Input impedance <100 mω <20 mω Rated frequency f n, according to order 50 Hz or 60 Hz Table 2: Energizing inputs, earth-fault unit Terminals 25-26 25-27 Rated current I n 1 A 5 A Thermal withstand continuously 4 A 20 A capability for 10 s 25 A 100 A for 1 s 100 A 500 A Dynamic current Half-wave value 250 A 1250 A withstand capability Input impedance <100 mω <20 mω Rated frequency f n, according to order 50 Hz or 60 Hz Table 3: Output contact ratings Type of contact Tripping Signalling Terminals 65-66, 74-75 70-71-72, 68-69, 77-78, 80-81 Rated voltage 250 V ac/dc Continuous carry 5 A 5 A Make and carry for 0.5 s 30 A 10 A Make and carry for 3 s 15 A 8 A Breaking capacity for dc, 220 V dc 1 A 0.15 A when the 110 V dc 3 A 0.25 A control/signalling circuit time constant L/R 40 ms, at the control voltages 48 V dc 5 A 1 A 5

Technical data (cont d) Table 4: Control input, communication and power supply External control input Terminals 10-11 Control voltage level 18 265 V dc or 80 265 V ac Current drain at activated input 2 20 ma Data communication Transmission mode Fibre-optic serial bus Data code ASCII Selectable data transfer rates 4800 or 9600 Bd Bus connection module, for plastic core cables SPA-ZC 21BB powered from the host for glass fibre cables SPA-ZC 21MM relay Bus connection module, for plastic core cables SPA-ZC 17BB powered from the host for glass fibre cables SPA-ZC 17MM relay or from an external power source Auxiliary supply modules Power supply and I/O modules, rated voltages and operative range SPTU 240R1 110/120/230/240 V ac, 110/125/220 V dc, 80 265 V ac/dc SPTU 48R1 24/48/60 V dc, 18 80 V dc Power consumption under quiescent ~4 W conditions under operating conditions ~6 W Table 5: module SPCJ 4D29, overcurrent unit Features Stage I> Stage I>> Start current at definite time 0.5 5.0 I n 0.5 40.0 I n and at inverse time 0.5 2.5 I n Start time, typically 50 ms 40 ms Operate time at definite time characteristic 0.05 300 s 0.04 300 s Time/current characteristic at inverse mode Extremely inverse Very inverse Normal inverse Long-time inverse RI type inverse RXIDG type inverse Time multiplier k 0.05 1.0 Reset time, typically 40 ms 40 ms Retardation time <30 ms Reset ratio, typically 0.96 Operate time accuracy at definite time mode ±2% of set value or ±25 ms Accuracy class index E at inverse time mode 5 Operation accuracy ±3% of set value ±3% of set value 6

Technical data (cont d) Table 6: module SPCJ 4D29, earth-fault unit Features Stage I 0 > Stage I 0 >> Start current 0.1 0.8 I n 0.1 10.0 I n and Start time, typically 60 ms 40 ms Operate time at definite time characteristic 0.05 300 s 0.05 300 s Time/current characteristic at inverse time mode Extremely inverse Very inverse Normal inverse Long-time inverse RI type inverse RXIDG type inverse Time multiplier k 0.05 1.0 Reset time, typically 40 ms 40 ms Retardation time <30 ms Reset ratio, typically 0.96 0.96 Operate time accuracy at definite time mode ±2% of set value or ±25 ms Accuracy class index E at inverse time mode 5 Operation accuracy ±3% of set value ±3% of set value Table 7: Tests and standards Test voltages Interference tests Power supply test, power supply variation Dielectric test voltage (IEC 60255-5) Impulse test voltage (IEC 60255-5) Insulation resistance (IEC 60255-5) High-frequency (1 MHz) disturbance test (IEC 60255-22- 1), common mode High-frequency (1 MHz) disturbance test (IEC 60255-22- 1), differential mode Fast transients (IEC 60255-22-4, class III and IEC 61000-4-4), power supply inputs Fast transients (IEC 60255-22-4, class III and IEC 61000-4-4), other inputs Electrostatic discharge (IEC 60255-22-2 and IEC 61000-4-2), air discharge Electrostatic discharge (IEC 60255-22-2 and IEC61000-4-2), contact discharge RF electromagnetic field test (IEC 61000-4-3 and ENV 50140) Conducted RF disturbance test (IEC 61000-4-6 and ENV 50141) Variation voltage Interruption 80 V - 50% Interruption 80 V - 100% Interruption 255 V - 100% 2.0 kv, 50 Hz, 1 min 5 kv, 1.2/50 µs, 0.5 J >100 MΩ, 500 V dc 2.5 kv 1.0 kv 4 kv, 5/50 ns 2 kv, 5/50 ns 8 kv 6 kv 10 V/m, f = 80 1000 MHz 10 V, f = 150 khz 80 MHz 68 265 V 0 200 ms 0 30 ms 0 160 ms 7

Table 7: Tests and standards Mechanical test Seismic test (ANSI/IEEE C37.98-1987), operating basis earth-quake test Seismic test (ANSI/IEEE C37.98-1987), safe shut down earth-quake test Vibration test Shock/bump test (IEC 60255-21-2) Corrosion test 0.5 5.25 g 0.5 7.5 g 2 13.2 Hz, ±1.0 mm 13.2 100 Hz, ±0.7 g 20 g, 1000 bumps/direction Battelle test Environmental conditions Service temperature range -10 55 C Transport and storage temperature range (IEC 60068-2-8) -40 70 C Damp heat test (IEC 60068-2-3) Degree of protection by enclosure when panel mounted Weight <95%, 40 C, 96 h IP 54 ~3.5 kg 8

Block diagram 63 1 23 4 5 6 7 89 25 26 27 L1 L2 L3 0 I 0 (~) - (~) U aux IRF START 1 START 2 SIGNAL 1 SIGNAL 2 TRIP 11 10 62 61 70 71 72 74 75 77 78 80 81 68 69 65 66 F E D C B A U2 - TS1 SS1 SS2 SS3 TS2 1 1 1 1 LATCHING 1 SGB/6 SGB/7 SGB/1 U1 3I> IRF T1 SGB/2 3I>> T3 SGB/3 Io> T5 SGB/4 Io>> T7 SGB/5 RC SETTINGS I/O SGB/8 SGF/4 RESET T9 0.1...1s T2 T4 T6 T8 - I - 1 A 5 A SGR1/2 SGR1/4 SGR1/6 SGR1/8 SGR2/8 U3 R Rx Tx SERIAL PORT TRIP U1 1 A 5 A 1 A 5 A 1 A 5 A SGR3/1 SGR3/2 SGR3/3 SGR3/4 SGR3/5 SGR3/6 SGR3/7 SGR3/8 SGR1/1 SGR1/3 SGR1/5 SGR1/7 SGR2/1 SGR2/3 SGR2/5 SGR2/7 SGR2/2 SGR2/4 SGR2/6 SPA-ZC_ EXTERNAL CONTROL ~ Fig. 8 Block diagram and sample connection diagram BSPAJ140 9

Mounting and dimensions Flush mounting 142 30 250 216 186 34 129 ±1 162 136 139 ±1 Panel cutout dim100 Fig. 1 Flush-mounting relay case (dimensions in mm) Semi-flush mounting a b Raising frame SPA-ZX 111 SPA-ZX 112 SPA-ZX 113 a 176 136 96 b 74 114 154 SFM100_1 Fig. 2 Semi-flush mounting relay case (dimensions in mm) Mounting in 19 inch cabinets and frames An ancillary mounting plate, height 4U (~177 mm), is recommended to be used when the protection relays are to be mounted in 19 inch frames or cabinets. The ancillary mounting plate type SPA-ZX 104 accommodates three relays, type SPA-ZX 105 two relays and type SPA-ZX 106 one relay. Projecting mounting When projecting mounting is preferred, a relay case type SPA-ZX 110 is used. The relay case for projecting mounting is provided with front connectors. SPA-ZX104 SPA-ZX105 SPA-ZX106 0,4 482,6 0 (19") SPA-ZX110 SPA-ZX115 10 158 115 ø6 263 312 292 101,6 21,5 7 0,4 177 0 (4U) 115 6 98 104_6_10 Fig. 3 Mounting cabinets and frames as well as projecting mounting (dimensions in mm) 10

Ordering When ordering, please specify: Ordering information Ordering example 1. Type designation and quantity, 5 pieces 2. Order number RS 611 006-AA 3. Rated values I n =5 A, f n =50 Hz 4. Auxiliary voltage U aux =110 V dc 5. Accessories - 6. Special requirements - Order numbers Combined overcurrent and earth-fault relay without test adapter Combined overcurrent and earth-fault relay including test adapter RTXP 18 The last two letters of the order number indicate the rated frequency f n and the auxiliary voltage U aux of the relay as follows: RS 611 006-AA, CA, DA, FA RS 611 206-AA, CA, DA, FA AA equals f n = 50 Hz and U aux = 80 265 V ac/dc CA equals f n = 50 Hz and U aux = 18 80 V dc DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc References Additional information User s manual and technical description Combined overcurrent and earth-fault relay 1MRS 750629-MUM EN 11

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 www.abb.com/substationautomation