Supplementary Components WirelessHART products

Similar documents
Siemens AG Network transitions. 8/2 Transition from Industrial Ethernet to WirelessHART 8/2 IE/WSN-PA LINK

Supplementary Components WirelessHART products

Communication and Software

1 Overview. Pressure Measurement Transmitters with WirelessHART. 1/36 Siemens FI US Edition. SITRANS P280 for gauge and absolute pressure

General Specifications

SITRANS T measuring instruments for temperature

Supplementary Components Network transitions

SITRANS P measuring instruments for pressure

PAS 300, PROFIBUS Slave Interface Module

ABB ME ASURE ME NT & AN AL YT ICS D AT A SHE ET. WirelessHART components Gateway and accessories

SIMATIC S Central processing units

IE/WSN-PA Link SIMATIC NET. Industrial Ethernet / Wireless HART IE/WSN-PA Link. Preface. Product description. Setting up network structures

Model R-1420 Wireless Gateway

3420 Fieldbus Interface Module (FIM) Contents

SIMOTION P PC-based SIMOTION P350-3

MGate 5102-PBM-PN Series

Siemens AG ES AH02-0AE0 6ES BH02-0AE0 6ES CH02-0AE0

Siemens AG Continuous level measurement - Radar transmitters. Configuration. Mounting on a nozzle. Installation min.

CP ADVANCED. Function

TIM 3V- IE ADVANCED. Function

CPU module for zone 2 Series 9442/35

WIRELESS GATEWAY. Features. Model R-1420

6GK6091-0AT Automation Technology > Industrial Communication > Industrial Ethernet > RUGGEDCOM Serial Device Servers > RUGGEDCOM RS910 managed

PROFIBUS. Connectors Repeaters FO Wireless system Communication

Technical Information WirelessHART Fieldgate SWG70

6GK6041-6AT Automation Technology > Industrial Communication > Industrial Ethernet > RUGGEDCOM Serial Device Servers > RUGGEDCOM RS416 managed

1420 Wireless Gateway

WirelessHART Adapter SWA70

SITOP in the SIMATIC Design

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

OnCell G3150A-LTE Series

Continuous level measurement Radar transmitters

Rosemount 248 Wireless Temperature Transmitter

Ethernet CPU Module & Power Module for Zone 1 / Div. 1 Series 9441/12 and 9444/12

CP BACNET Function

RAD-WHG/WLAN-XD. WirelessHART gateway with integrated WLAN (802.11b/g) INTERFACE Data Sheet 2720_en_C. 2 Features. 1 Description

General Specifications

Technical Information Field Xpert SMT70

AC 800M for Compact Product Suite Outline of all modules

General. Remote I/O A4/1.

Features and Benefits. Certifications

MGate 5105-MB-EIP Series

Technical Information WirelessHART Adapter SWA70. Smart WirelessHART interface module with power supply for field devices. Products Solutions Services

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Technical Information WirelessHART Adapter SWA70. Smart WirelessHART interface module with power supply for field devices. Products Solutions Services

FLEX Ex Spring Clamp Terminal Base

SITOP 3-phase 24 V DC, 20 to 40 A

NETL ink gateways. Ethernet gateways WLAN gateways High-speed USB gateways

Honeywell OneWireless Network and Multinode Specifications EP November 2007

Bridge: The 702-W will operate in Layer 2 without network segmentation. Router: The 702-W offers Layer 3 routing to allow network segmentation.

Smart Wireless Gateway

Smart Wireless Gateway

Technical Information Promonitor NRF560

Smart Wireless THUM Adapter

PSI-MOS-RS422/FO 850 T

Features and Benefits. Certifications

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL.

Digital Output Module 8-Channel Version for Zone 2 Series 9475/

XPSMCMCO0000EM Modbus TCPIP diagnostic expansion module with screw term

Segment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.

SCALANCE X-200 SIMATIC NET. Industrial Ethernet Switches SCALANCE X-200. Preface. Functions. Description of the device.

General Specifications

The iwap107 supports 100/1000Base-T, offering a significant increase in speed over the older fast Ethernet standard.

6GK6096-8AS Automation Technology > Industrial Communication > Industrial Ethernet > RUGGEDCOM Ethernet Switches > RUGGEDCOM RS900 managed

SIMATIC NET. SCALANCE Industrial Ethernet SCALANCE X- 100 and SCALANCE X-200 Product Line. Preface. Introduction. Network Topologies

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

Programming unit VIATOR HART modems Model PU-H

Smart Wireless Gateway

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

Segment Protector for Cabinet Installation R2-SP-IC* Features. Assembly. Function. Connection. Trunk, Ex na non-arcing. Spur.

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage

MGate 4101-MB-PBS Series

6GK6093-0AD Transmission rate. Interfaces. remark. for network components and terminal equipment maximum 6. Signal-Inputs/outputs

IE/PB LINK PN IO. PROFINET applications

PSI-MOS-PROFIB/FO 850 T

Pro. LCN1840/05 Wireless gateway. Specification sheet. Connected lighting. Find out more about Interact

Technical Information Fieldgate SFG500

General information. Display. Supply voltage

General information. Display. Supply voltage. Input current

MODEL: WL40EW2F. Wireless I/O WL40F Series

Digital Output Module 8-Channel Version for Zone 2 Series 9475/

SITOP PSU8600 power supply system

PHOENIX CONTACT - 05/2007

PSI-MOS-PROFIB/FO 850 T

RFID systems for the HF frequency range

General Specifications

General information. Display. Supply voltage. Input current

Madrid, 25 y 26 de mayo de 2015 ABB Automation Days Wireless Instrumentation

General information. Display. Supply voltage

FL MC 10/100BASE-T/FO-660

Digital Output Module 8-Channel Version for Zone 1 Series 9475/

Operating Instructions 12/2010 MN Z-EN XV-152 MICRO PANEL

Operator panels Advanced HMI Panel-based Mobile Panels

4 Remote I/O. Analog Output Module HART Ex i / I.S. Outputs, 8 Channels Series 9466/12

Power Supplies & Logic Modules

DTM Distributed Transmitter Monitor

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)

6GK6096-8MS Automation Technology > Industrial Communication > Industrial Ethernet > RUGGEDCOM Ethernet Switches > RUGGEDCOM RS900 managed

Transcription:

Overview Application The connects wireless HART field devices by radio to the Ethernet. On the radio side, the supports the WirelessHART standard and on the Ethernet side the TCP/IP and Modbus TCP communication. The thus enables wireless diagnostics, maintenance and process monitoring. Monitoring WirelessHART is particularly suitable for use in plant sections that are to be included in monitoring, but which do not have any existing MSR cabling, e.g. external tank stores or other installations where high cabling costs are anticipated. Data for the visualization can be retrieved from the IE/WSN-PA link via Industrial Ethernet or Modbus TCP. The is a network transition for the connection of WirelessHART field devices (HART V.1) to, as an alternative or supplement to the wired connection. Connection of up to 100 WirelessHART devices Approved for operation in hazardous areas in Zone 2 Open TCP/IP communication and Modbus TCP via the Ethernet interface Can be used with HART-OPC servers of the HART Communication Foundation Note: A general introduction to WirelessHART and information on the WirelessHART adapter and the WirelessHART field devices can be found in Catalog FI 01 or on the Internet at http://www.siemens.com/wirelesshart Benefits Extended possible solutions for connecting process industry field devices by means of alternative or supplementary WirelessHART communication Reliable data transmission using intermeshed network technology; the self-organizing network with alternative paths enables radio obstacles to be bypassed Reduction of cabling costs under difficult installation conditions, e.g. if the field devices are located on inaccessible plant components or are only required temporarily To improve process monitoring and for maintenance tasks, sensors can be retrofitted Existing transmitters can be integrated wirelessly into maintenance and diagnostics systems by means of WirelessHART adapters Without additional software, restricted monitoring is possible via web services and the integrated web server of the IE/WSN- PA. ES OS MS Wireless HART IE/WSN- PA Monitoring of process states via WirelessHART SIMATIC system SIMATIC ET 200 with HART support DP/PA Retrofitting for diagnostics and maintenance For this application, wireless adapters are looped into the 4-20 ma interface or screwed directly onto the HART device. The acyclic HART message frames are transmitted by radio between and a wireless adapter. Without affecting the operation of the plant, the wireless adapter modulates the acyclic HART message frames to the 4-20 ma interface or extracts them from the 4-20 ma interface. The collects the data of all wireless adapters and transfers it via to the diagnostics and maintenance station. If greater distances between the and the monitoring station are to be spanned without cabling, this can be implemented by means of Industrial Wireless LAN with the access points and client modules of the SCALANCE W family. PROFIBUS PROFIBUS PA /34 Siemens FI 01 2015

MDS IEEE 802.11 IE/WSN- PA Industrial Ethernet Wireless HART Controller without HART support Remote I/O station w/o HART support Retrofitting of plants for diagnostics and maintenance Design 2 x 10/100/1 000 Mbit/s RJ45 ports, electrical (no integral switch; interfaces can be used, for example, for continuous connection to the plant network as well as the temporary connection of a PC) 1 x screw terminal for connection to Modbus RTU via RS 485 1 x screw terminal for the 24 V DC connection Rugged metal enclosure with IP65 protection for use outdoors, also in hazardous zone 2 Mounting: wall or mast mounting (vertical); U-bolts for mast mounting are included in the scope of delivery. Product versions With integral, non-detachable antenna Redundancy function and with N connector for connection of an external antenna OS PROFIBUS Function WirelessHART The establishes on the radio side an intermeshed wireless sensor network for communication with wireless field devices (e.g. transmitters). The data from the wireless field devices is received by the and transmitted via to the connected systems. The supported wireless network is an open wireless network specified by the HART Communication Foundation (HCF) in accordance with the WirelessHART (HART V.1) standard. On the field device side, the requires field devices that support WirelessHART (HART). Existing field devices can be integrated by means of wireless adapters into the WirelessHART communication. To this end, the adapters are looped into the 4-20 ma interface. In addition, as many as four standard HART field devices with external power supply can be connected to the adapter in multidrop mode. Individually connected devices can be operated with the battery of the adapter. The adapter wirelessly transmits all data and process values of the connected devices. The advantage of this solution is that tried and tested devices can continue to be used. Via the Ethernet interface the supports the use of the HART OPC server and the Modbus TCP protocol. Configuration The configuration is web-based, without additional software, and performed from the PC. By means of the web user interface it is also possible to display the device states and measured values of the WirelessHART devices. Increased availability of WirelessHART application due to redundancy mode For increased availability requirements, the link can be used redundantly. The redundancy function is only available for the device variant with a connection for an external antenna. Two links are connected to the same Ethernet subnet via a switch to provide the redundancy. The two links are connected to each other via an Ethernet cable (management coupling). One of the two links is configured as the active device. It carries out the communication between the control center and the WirelessHART wireless network under normal conditions. The second link is configured identically. It is used as a standby device. In a redundancy scenario, the standby device becomes the active device. Control center IE/WSN-PA P1 P2 IE/WSN-PA WirelessHart P2 SCALANCE X208 P1 WirelessHART Wireless connection Management Coupling between redundant gateways G_IK10_XX_30298 WirelessHART network operated with a redundant gateway Siemens FI 01 2015 /35

Integration Integration into automation systems Technical specifications 6GK1411-6GK1411-6CA40-0AA0 6CA40-0BA0 The can be integrated into automation systems via Ethernet or Modbus TCP. Communication modules Product type designation (CP 343-1 or CP 443-1) are required to connect the IE/WSN-PA Transfer rate to SIMATIC S-300/400. Function blocks and technical at the interface 1 10 100 Mbit/s support can be found at: at the interface 2 10 100 Mbit/s www.siemens.com/simatic-net/ik-info at the interface 3 9.6to5.6kbit/s Integration in PCS For integration of the into PCS you can obtain function blocks and technical support at: Interfaces Number of electrical connections at interface 1 in accordance with 1 at interface 2 in accordance with 1 www.siemens.com/simatic-net/ik-info at interface 3 in accordance with 1 RS 485 For power supply 1 Design of electrical connection at interface 1 in accordance with RJ 45 port at interface 2 in accordance with RJ 45 port at interface 3 in accordance with 2-pin terminal strip RS 485 For power supply 3-pin terminal strip Interfaces wireless Number of radio cards permanently 1 1 installed Number of internal antennas 1 0 Number of electrical connections for external antenna(s) 0 1 Design of electrical connection for - N-Connector external antenna(s) Supply voltage, current consumption, power loss Type of power supply DC Supply voltage, external 24 V Minimum 20 V Maximum 28 V Current consumed from external 0.5 A power supply at 24 V DC, maximum Active power loss, maximum 12 W Permitted ambient conditions Ambient temperature During operating -40 +0 C During storage -40 +85 C During transport -40 +85 C Relative humidity at 25 C without 90 % condensation during operating phase, maximum Protection class IP IP 65 Design, dimensions and weights Width of the housing 229 mm Height of the enclosure Without antenna 306 mm With antenna 354 mm Depth of the housing 89 mm Net weight 4.54 kg Mounting type Wall mounting Mast mounting Mounting type Material for mast mounting included in scope of delivery /36 Siemens FI 01 2015

Wireless frequencies Radio frequency with WirelessHART in the 2.4 GHz frequency band Initial value End value Performance data WirelessHART Number of WirelessHART devices which can be operated Network latency For 100 field devices and WirelessHART network maximum For 50 field devices and WirelessHART network maximum Transmission link between two devices with WirelessHART network Maximum Note Protocol is supported HART Product properties, functions, components general Protocol is supported Address Resolution Protocol (ARP) HTTP HTTPS Modbus TCP Modbus TCP secure Modbus RTU 2.4 GHz 2.5 GHz 100 10 s 5 s 100 m Values may vary in the case of radio obstacles s management, configuration Web-based management DHCP client s Diagnosis Web-based diagnostics WirelessHART diagnostics via Modbus s Redundancy device redundancy No s Security Password protection - multilevel WirelessHART join key ACL - MAC-based WirelessHART network ID Protocol is supported SSL Principle of encryption AES 128 bit s Time Protocol is supported NTP Standards, specifications, approvals Standard for WirelessHART HART V.1 Standard for wireless communication IEEE 802.15.4 Certificate of suitability CE mark Concerning CSA CSA Division 2 & Dust Ignition-proof for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II, Groups E, F, and G / Suitable for Class III Hazardous Locations. / Install per Siemens drawing A5E0246236A. Temperature Code: T4 (-40 C < Ta < 60 C) CSA Enclosure Type 4X Concerning FM FM Division 2, Non-Incendive for Class I, Division 2, Groups A, B, C, and D. Dust Ignition-proof for Class II, III, Division 1, Groups E, F, and G / Indoor and outdoor locations / NEMA Type 4X Temperature Code: T4 (-40 C < Ta < 60 C) Concerning ATEX ATEX type n, see note: Certificate number: Baseefa10ATEX0044X, ATEX marking: Ex II 3 G, Ex na nl IIC T4 (-40 C <= Ta <= 60 C), rated voltage: 28 V, ATEX Dust Ignition-proof: Certificate number: Baseefa10ATEX0045X, ATEX marking: II 3 D, Ex td A22 IP66 T135 (-40 C <= Ta <= 60 C), rated voltage: 28 V. Note on type n: Conditions for safe handling during installation: The device does not pass the 500 V insulation test in accordance with paragraph 6.8.1 of EN 6009-15:2005. This must be taken into account when installing the device. Regarding IECEx IECEx type n, see note: Certificate number: IECEx BAS 10.0014X, Ex na nl IIC T4 (-40 C <= Ta <= 60 C), rated voltage: 28 V, IECEx Dust Ignition-proof, see note: Certificate number: IECEx BAS 10.0015X, Ex td A22 IP66 T135 (-40 C <= Ta <= 60 C), rated voltage: 28 V. Note on type n: Conditions for safe handling during installation: The device does not pass the 500 V insulation test in accordance with paragraph 6.8.1 of EN 6009-15:2005. This must be taken into account when installing the device. Regarding NEMA - - Wireless approval FCC and IC IC approval approval Siemens FI 01 2015 /3

Selection and Ordering data Gateway between WirelessHART and ; transmission frequency: 2.4 GHz With integral, non-detachable 6GK1411-6CA40-0AA0 antenna N connector for connection of 6GK1411-6CA40-0BA0 external antennas Antennas Antennas with omni-directional characteristics; country permits, compact instructions (hard copy), German/English Wall or mast-mounting Antenna ANT92-6MN 6GK592-6MN00-0AA6 Antenna gain including N-Connect connector 6 dbi, 2.4 GHz Roof mounting ANT95-6MN antenna 6GK595-6MN00-0AA6 Antenna gain incl. N-Connect connector 6/8 dbi, 2.4/5 GHz Antenna mounting tool 6GK595-6MN01-0AA6 (ANT95-6MN) Mounting tool for installation of ANT95-6MN under a roof LP98-1N Lightning Protector 6GK598-2LP00-2AA6 Lightning protector with N/N female/female connector, IP65 (-40 +100 C) Antenna cables IWLAN N-Connect male/male flexible connection cable Flexible connecting cable for connecting an external antenna; assembled with two N-Connect male connectors 1 m 6XV185-5AH10 2 m 6XV185-5AH20 5 m 6XV185-5AH50 10 m 6XV185-5AN10 HF coupling 6GK598-0CP00-1AA0 N-Connect male/male connector for connecting the LP98-1N lightning protector Accessories IE FC M12 Plug PRO M12 plug-in connector suitable for on-site assembly (D-coded, IP65/IP6), metal housing, Fast- Connect connection system, for connecting HARTING adapter cables to the 1 unit 6GK1901-0DB20-6AA0 IE FC TP Standard Cable GP 2 x 6XV1840-2AH10 2 (Type A) 4-core, shielded TP installation cable for connection to IE FC Outlet RJ45/IE FC RJ45 Plug; PROFINET-compatible; with UL approval; sold by the meter; max. length 1000 m, minimum order quantity 20 m IE FC Stripping Tool Preadjusted stripping tool for fast stripping of the FC cables Network components for IWLAN HARTING adapter cable 1) M12 female NPT 1/2 thread to RJ45 11cm, (minimum order quantity: 10); The adapter is provided for easy connection of the link to the ; SITOP compact 24 V/ 0.6 A 1-phase power supply with widerange input 85 264 V AC/110 300 V DC, stabilized output voltage 24 V, rated output current value 0.6 A, slim design 1) 6GK1901-1GA00 see "Industrial Wireless Communication" 21036836420 Not included in the scope of delivery of the IE/WSN-PA link; You can find ordering information on the Internet at: http://www.harting.com 6EP1331-5BA00 When using the Harting adapter cable for the Ethernet connection, the requirements for intrinsic safety approval are not applicable. When used in an application relevant to intrinsic safety guidelines, it requires acceptance by the appropriate approval agency. More information Current approvals can be found on the Internet at: http://support.automation.siemens.com/ww/view/en/463434 /38 Siemens FI 01 2015