Installing VO2 Analog Output Boards

Similar documents
System User Manual. AKC 55 Rack Controller

Installing and Setting Up the Components

REFRIGERATION AND AIR CONDITIONING. On Site Guide AK2-SC 255

ETM-2050/ETM-2051 Service Manual

Rev Cutler-Hammer Smart Breaker Panel Control Manual

Custom Controller Installation Instructions

Hardware Installation. Tracer MP581 Programmable Controller CNT-SVN01C-EN

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

ELECTRONIC CONTROLS & SENSORS. AK-SC255 Fact Sheet Version R Software Software version 02_085

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

PROLON INSTALLATION AND START UP GUIDE

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

clarity 3 Programmable Controller

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

Manual FC 3500 DC Fan Control

PumpDrive. Self -cooling, motor-independent frequency inverter. Brief Instructions

Quick Start Guide. SEB-710 I/O Expansion board. Introduction

Measure & Control Temperature & CO2 levels with analog & digital I/O

M1000 INTELLIGENT ZONE CONTROL SYSTEM

ETM-2040 Service Manual

RТTH DUAL ROOM SWITCH

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

SLX Series. Application Specific Controllers (SLX-ASC-FCU-L, SLX-ASC-HPU-L, SLX-ASC-RTU-L, SLX-ASC-UV-L)

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

TOXALERT MODEL AIR 2000

Rev MultiFlex I/O Board Installation and Operation Manual

VAV Modular Assembly (VMA) 1410/1420

H704-42(H)(E), H704-42/1(H)(E)

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

MC CO MODBUS ADDRESSABLE SENSOR

H7625B; H7635B,C; H7655B Duct-Mount and Outdoor-Mount Humidity/Temperature Sensors

Installation & Operation Guide

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

ARCTIC AIR DC OLED. Digital Control Operations Manual

X47.CE Product Guide

Non-communicating room controllers

Analog Output Module Installation Instructions

Specification Sheet For electronically commutated motors

WOODINVILLE, WA SUPERSTEP 2100 SERIES SEQUENCING PROPORTIONAL LOAD CONTROLLERS INSTALLATION & OPERATING MANUAL. Models: SLC2102-SLC2112

Installation, Operation and Maintenance Manual

VAT series controller and transmitter. Manual

Products no longer available

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

INTELLI-HOOD TROUBLESHOOTING GUIDE

Overview These instructions are presented as a guideline for installing and setting up the LX Series Breaker Control Panel.

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

Dual Digital Module Technical Guide

Temperature controller Multi-zone ducted systems

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

Differential Liquid/Gas Pressure Transmitter

MX1 Reversible AC Motor Controller. Supplementary Wiring Examples

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Temperature controller Ducted systems

4-step Chiller and Heat Pump Controller

Andover ContinuumTM Infinet II

Product Manual SZ2141

Content. Product Description

SuperBus Hardwire Input Module (HIM) Document Number: Rev. C September 1998

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

THE CTB08D LIGHT CONTOLLER

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

H7625A, H7635A Humidity/Temperature Sensors

Economizer Controller Installation Guide

InBin-P Pressure switches from 5 Pa Pa

Sigma XT Ancillary Board (K588)

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

REMOTE CONTROL MYSYSTEM

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

BACnet Product Overview

BACnet. b3810 Series Local Controllers

DataNab it8: Intelligent Communicating Thermostat

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

Thermometer / Barometer System

CDD4 Duct Carbon Dioxide Transmitter

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

TT-NRM. Network Relay Module Installation Instructions WARNING:

Greentrol Automation, Inc.

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

InCos-P Pressure sensor 20 Pa Pa

RS-485 Modbus RTU Networking FCU Thermostats with 0(2)-10 VDC Fan Output

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet VAV Actuator

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

VMS Co., Ltd. VMS Reliability Systems - Korea

FX 2 Instruction Manual

RXTH DUAL ROOM SENSOR / SWITCH

NSGV Series "90DM3" Carbon Dioxide Detector

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

Installation Instructions

Transcription:

Chapter 3-6 VO2 Description and Identification Installing VO2 Analog Output Boards The VO2 Variable Output board provides an AKC 55 system with 2 variable outputs for control of loads like variable speed compressors and variable speed condenser fan motors. Each output can supply 0-10 VDC or 0-5 VDC. Both outputs can supply the same range or there can be one in each voltage range. Since they are nodes on the I/O network, VO2 boards communicate with a host AKC 55 over TP-78K twisted pair shielded cable. The board s name and version number are printed on the board as shown in the following illustration. Mounting The VO2 board is designed for 3" snaptrack mounting in either a Danfoss IO4R or IO12 enclosure, and OEM control panel, or other enclosed spaces. Snaptrack for I/O boards can be mounted on any flat surface where codes and good electrical practice permit. A Danfoss IOPS-series power supply must be used to provide operating voltage for I/O boards not mounted in a Danfoss IO4R or IO12 enclosure. Addressing a VO2 Each of the VO2 boards connected to an AKC 55 must have a unique address in the range 01-99. The address is set by the two rotary switches located side-by-side beneath the board s status and service LED s. Each switch has an arrow pointer which serves also as a screwdriver slot. Use a small screwdriver to rotate the arrowhead on each switch until the left arrowhead points to the first digit, and the right arrowhead to the second digit, of the correct address. AKCESS System Manual RC.IU.B1.22 4/99.1 3-25

Network Connections The VO2 board is connected to the I/O network at the terminal strip labeled NETWORK. When connecting from board to board (point-to-point or daisy-chain wiring), use only twisted-pair cable meeting the specifications given in the illustration below. There is no polarity to observe; connect the two signal wires to the terminals labeled A and B, and the cable shield to the terminal labeled shield. If it s the last board on a main I/O cable run, for Pete s sake terminate it!! Controlled Load Connections Each load to be controlled is connected to a variable output by wiring to one of the two pairs of Vout and GND terminals on terminal strip in the lower right corner of the board. VO2 Power Connections As with all I/O boards in the AKC 55 system, 12 VAC or 15 VDC from a Danfoss IOPS-series power supply is connected to a terminal strip labeled 12 VAC on the VO2 board. The power terminal strip is shown in the upper left corner of the illustration. Keep the wiring distance from the power supply to the I/O board under the limits given in the IOPSseries instruction sheet. There are copies of the instructions in Appendix B! 3-26 System Manual RC.IU.B1.22 4/99.1 AKCESS

Inspection of the Installed VO2 When a VO2 Variable Output Board is ready for operation, you should be able to observe the following, proceeding clockwise around the board from the power terminal strip: 1. Power (12 VAC or 15 VDC) has been connected to the 12 VAC terminal strip. 2. The status LED should be blinking. If the status LED is off, there is no power to the board (check the fuses). If the status LED is constantly on (not blinking), the board is not communicating with its AKC 55. Make sure the AKC 55 has been configured for this board; if configured, there will be information in at least one of the Board and Points screens; you can investigate, and supply configuration information, if necessary, by following the procedures described in Section IV of this manual. 3. The service LED will normally blink briefly when the network is scanned, but if the service LED remains steadily on, the VO2 board is defective and should be replaced. 4. The address switches have been set to a valid address. 5. Loads are connected to one or both of the pair of output terminals. 6. Connection has been made to the I/O network of an AKC 55 at the NETWORK terminal. 7. If this board is the last node on a run, make sure that it is terminated by using one of the terminators supplied with the AKC 55. AKCESS System Manual RC.IU.B1.22 4/99.1 3-27

Chapter 3-7 RTC Description Availability Capabilities and Capacities Capacity: Sensor Inputs Installing RTC Rooftop Controllers The RTC Rooftop Controller can operate in two modes: as a node in an AKCESS I/O Identification network, connected to an AKC 55, or as a stand-alone rooftop controller. The RTC communicates over the I/O network when it is a node in an AKCESS system. Like an AKCESS Smart Case Controller, the RTC is an intelligent controller. If communications are interrupted or lost, the RTC will continue to operate as a stand-alone controller with the same strategy and settings as selected during its configuration as part of the AKCESS network. The RTC is available from Danfoss in a rainproof enclosure or without enclosure for installation by original equipment manufacturers. There can be as many as 32 RTC rooftop controller nodes in an AKCESS system, as long as the total number of HVAC systems does not exceed 32. The RTC has one required and up to seven optional sensor inputs, which are pre-assigned for use as follows: Input Number Sensor 1 Zone Humidity 1 2 Zone Humidity 2 3 Outside Humidity 4 Zone Temperature 1 5 Zone Temperature 2 6 Outside Temperature 7 Supply Temperature 8 Return Temperature These sensor inputs need not be wired directly to the RTC board; they can be set up during configuration to be received from sensors connected to any SI board in the AKCESS system. Required Sensor Capacity: On/Off inputs At least one zone temperature sensor or the return temperature sensor must be connected in order for the RTC to function. There are up to four optional on/off inputs, pre-assigned for use as follwos: Input Number 1 Fan 2 Cooling 1 On/Off Input 3 Heating 1 OR Cooling 2 4 Smoke Detector OR Differential Pressure These on/off inputs can be wired directly to the RTC board or they can be received from any OI board on the AKCESS network. 3-28 System Manual RC.IU.B1.22 4/99.1 AKCESS

Capacity: Relay Outputs Relay outputs are provided for control of HVAC devices, and are pre-assigned for control as follows: Relay Output Number Controlled Device 1 Fan 2 Damper 3 Cooling, Stage 1 4 Cooling, Stage 2 5 Cooling, Stage 3 6 Heating, Stage 1 7 Heating, Stage 2 8 Heating, Stage 3 Mounting Addressing Using the pre-drilled holes, mount the RTC securely to a solid surface. Operating temperature must be in the range from 0 o F to 130 o F at 90% rh (non-condensing) or from 0 o F to 122 o F at 95% rh (noncondensing). The RTC is addressed by setting the two side-by-side rotary switches on the circuit board. Each RTC must have a unique address in the range 01-99. Each switch has an arrow pointer which serves also as a screwdriver slot. Use a small screwdriver to rotate the arrowhead on each switch until the left arrowhead points to the first digit, and the right arrowhead to the second digit of the correct address. AKCESS System Manual RC.IU.B1.22 4/99.1 3-29

Network Connections The RTC is connected to the I/O network at the terminal strip labeled NETWORK. When connecting from board to board (point-to-point or daisy-chain wiring), use only twisted- pair cable meeting the specifications given in the illustration below. There is no polarity to observe; connect the two signal wires to the terminals labeled A and B, and the cable shield to the terminal labeled shield. If your RTC is at the end of a main cable run, it has to be terminated!!. Sensor Connections Up to 8 sensors can be connected to an RTC board. The board has three sets of terminals for humidity sensors and five sets for temperature sensors. Each set of terminals is dedicated and labeled for a particular sensor. Although sensor leads can be up to 1000' long, when leads are over 100', take care to calibrate and offset sensor readings (see Chapter 5 section 2 and use the Sensor Adjustment screen selected from the appropriate Service menu). Connect temperature sensor to GND and SIG terminals as shown in the following illustration; there is no polarity requirement: 3-30 System Manual RC.IU.B1.22 4/99.1 AKCESS

Connectingg On/Off Inputs The RTC has four sets of terminals for on/off inputs. Each set of terminals is labeled with the name of the device for which the terminals are intended. Connecting Relay Outputs Controlled loads are connected to their RTC terminals by wiring to the common and either the normally open ( NO ) or normally closed ( NC ) screw terminals labeled for the particular load. RTC Power Connections Inspection of the Installed RTC Power connections (24 VAC, +10% / -15%) are made to the terminals labeled 24 VAC. When an RTC Rooftop Controller is ready for operation, you should be able to observe the following, proceeding clockwise around the board from the power terminal strip: 1. Power connections (24 VAC) have been made to the 24 VAC terminal. 2. Controlled loads are connected to the relay output terminal strips (labeled C, NO, and NC for Common, Normally Open, and Normally Closed) for Fan, Damper, Cool 1, etc. 3. Loads to be monitored are connected to the on/off input terminals (labeled N and L for Neutral and Line) for appropriate devices. 4. Connection has been made to the I/O network of an AKC 55 at the NETWORK terminals. 5. Sensor connections have been made to the terminal strips labeled for Zone Humidity, Outside Humidity, Zone Temperature, etc. For temperature sensors, only SIG and GND connections have been made, and for humidity sensors, 12V, SIG, and GND have been connected. 6. The Service LED will normally blink briefly when the network is scanned, but if the service LED remains steadily on, or blinks constantly, the RTC board is defective and should be replaced. 7. If this board is the last node on a run, make sure that it is terminated by using one of the terminators supplied with the AKC 55. AKCESS System Manual RC.IU.B1.22 4/99.1 3-31