Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

Similar documents
This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

Vision OPLC. General Description. Standard Kit Contents. Installation Guide Vision120. This guide provides basic information for Unitronics Vision120.

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

Installation Guide V1210-T20BJ This guide provides basic information for Unitronics controllers V1210-T20BJ.

Failure to comply with appropriate safety guidelines can cause severe injury or property damage.

This guide provides basic information for Unitronics Models V230/260/280/290 (Non-color Screens).

Vision OPLC. General Description.

EX-RC1 Remote I/O Adapter

This guide provides basic information for Unitronics controllers V C30B and V T40B.

Screen 2.4" 3.5" Color Touch 4.3" Color Touch. RS232/485 Yes Yes Yes Yes Yes* USB device, mini-b Com Ports, separate order, user-installed

Vision OPLC. General Description. Installation Guide V T34.

Vision OPLC V TR20

UniStream HMI Panel. CPU-for-Panel

UniStream CPU-for-Panel

EX-RC1 Remote I/O Adapter

Vision OPLC V TR20/V350-J-TR20

Installation Guide V1210-T20BJ This guide provides basic information for Unitronics controllers V1210-T20BJ.

Failure to comply with appropriate safety guidelines can cause severe injury or property damage.

V E5B Snap-in I/O Module

V E62B Snap-in I/O Module

This guide provides basic information for Unitronics controller model V T2.

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Vision OPLC. V T38 Installation Guide. General Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Component identification

IO-DI8-RO8, IO-DI8-RO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

EX-RC1 Remote I/O Adapter

The identified danger could cause physical and property damage.

Vision OPLC V TR6/V350-J-TR6

22 Digital Inputs, including 2 Analog, 2 HSC/Shaft-encoder inputs 16 Transistor Outputs

IO-DI16, IO-DI16-L I/O Expansion Modules

OPLC Installation Guide

High Speed Remote I/O Module

Vision OPLC V TR20

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

General Description V TR34/V130-J-TR34 V TR34/V350-J-TR34 V430J-R34 V R34/V130-J-R34 V R34/V350-J-R34

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

V TU24 V350-J-TU24

IO-DI8-RO4, IO-DI8-RO4-L I/O Expansion Modules 8 Inputs, 4 Outputs

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Unitronics Devices and RS485 Table Of Contents

Screen 2.4" 3.5" Color Touch 4.3" Color Touch. RS232/485 Yes Yes Yes* Yes* Yes* USB device, mini-b Com Ports, separate order, user-installed

High Speed Remote I/O Module

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

V E1B Snap-in I/O Module

V E2B Snap-in I/O Module

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

Micro-OPLC Installation Guide

IO-PT4. Component identification. User safety and equipment protection guidelines. Unitronics Industrial Automation Systems 1

UniStream. Built-in. Installation Guide: US7-B5-B1, US7-B10-B1, US7-B5-TR22, US7-B10-TR22, US7-B5-T24, US7-B10-T24

IO-DI8-TO8, IO-DI8-TO8-L I/O Expansion Modules 8 Inputs, 8 Outputs

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

V E2B Snap-in I/O Module

Vision OPLC. Technical Specifications. V T34 Technical Specifications

User safety and equipment protection guidelines

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

V E3XB Snap-in I/O Module

V E1B Snap-in I/O Module

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

20.4VDC to 28.8VDC with less than 10% ripple Max. current consumption See Note 1 npn inputs

Using your PC to access a remote M90 via GSM

Vision OPLC. V TR6 Technical Specifications. Technical Specifications.

IO-LC1, IO-LC3 I/O Expansion Modules 1-3 Loadcell Inputs, 1 Digital In, 2 Out

3 Digital, 3 Digital/Analog, 3 PT1000/NI1000 Inputs, 5 Relay, 1 pnp/npn Outputs

V350-RA22 V350J-RA22.

V E4XB Snap-in I/O Module

V E6B Snap-in I/O Module

V E3XBW Snap-in I/O Module

V E3XB Snap-in I/O Module

LIMANDA Handheld Enclosures Product Drawings Last Updated 6/5/2008

Smart Portal SP5000SERIES

Replacing the Power Supply

DINALOG A 96 x 24. Programmable quasi-analogue bar graph meters. Technical characteristics DINALOG A 96 x 24

Package Contents. GP Options (Made by Digital)

Accessories - cable tie bases

1. Safety Precautions (Read these precautions before use.)

F1000 User's Manual. (Version: V1.01)

UDS-Universal Docking Stations Product Drawings Last Updated 4/22/2008

VENTILATION. Short catalogue VENTILATION COMMON FEATURES.

CARLO GAVAZZI. Automation Components. The quick-fit energy metering solutions

Hardware Installation. In this chapter... Custom Labels EMI Noise Filter Installation Mounting DIN Clip Mounting Connections and Wiring

BreezeMAX Wi² and BreezeACCESS Wi² Quick Installation Guide

Installing the Cisco 2524 and Cisco 2525 Routers

FX1N-4EX-BD Input Expansion Board

Characteristics. High impact with draw wire (ICTA 3422) Use. Accessories for conduits (p. 754)

InView Marquee Message Display

Medium Voltage Solutions For Water and Wastewater Treatment

M215 (M215-60) Safety

FiberINTER. FiberINTERF. FiberINTERFACES.

MCS IsoTM Busbar Modules for maximal safety. Finger proof even when load feeders removed MCS Standard Busbar Modules the economic solution Features

M215-Z Safety Information (M LL-IG-ZC)

FX1N-2EYT-BD Output Expansion Board

VP-1231-CE7 Quick Start

Transcription:

Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable logic controllers that comprise an integral operating panel. Operating panel features differ according to model. The V290-19-C30B and V290-19-T40B offer a color touchscreen, which displays a virtual keyboard when the application requires the operator to enter data. Communications 2 isolated RS232/RS485 ports and a CANbus port. I/O Options Programming The user can order and install an additional port. Available port types are: RS232/RS485, and Ethernet. V290 (Color Screens) Touchscreen only Vision supports up to 171 digital, high-speed, and analog I/Os via modules. Number of I/Os and types vary according to module. Snap-in I/O Modules Plug into the back of the controller to provide an on-board I/O configuration. I/O Expansion Modules Via adapter, use up to 8 I/O Expansion Modules comprising up to 128 additional I/Os. Write both the HMI and Ladder control application using VisiLogic freeware. The Vision User Guide and the product s technical specification sheet contain additional information. These documents are located on the Unitronics Setup CD. They may also be downloaded from the Technical Library at www.unitronics.com. Standard Kit Contents Vision controller Programming cable + RS232 adapter Mounting brackets (x4) Grounding hardware 3 pin power supply connector Rubber seal 5-pin CANbus connector Unitronics Setup CD CANbus network termination resistor Danger Symbols When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Danger The identified danger causes physical and property damage. Warning The identified danger could cause physical and property damage. Caution Caution Use caution. Unitronics 1

Vision OPLC V290-19-C30B, V290-19-T40B Before using this product, the user must read and understand this document. All examples and diagrams are intended to aid understanding, and do not guarantee operation. Unitronics accepts no responsibility for actual use of this product based on these examples. Please dispose of this product according to local and national standards and regulations. Only qualified service personnel should open this device or carry out repairs. Failure to comply with appropriate safety guidelines can cause severe injury or property damage. Do not attempt to use this device with parameters that exceed permissible levels. To avoid damaging the system, do not connect/disconnect the device when power is on. Environmental Considerations Do not install in areas with: excessive or conductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact shocks or excessive vibration, in accordance with the standards given in the product s technical specification sheet. Ventilation: 10mm space required between controller s top/bottom edges & enclosure walls. Do not place in water or let water leak onto the unit. Do not allow debris to fall inside the unit during installation. Install at maximum distance from high-voltage cables and power equipment. Mounting Dimensions 2 Unitronics

Installation Guide Panel mounting Before you begin, note that: The mounting panel cannot be more than 5 mm thick. To minimize electromagnetic interference, mount the controller on a metal panel and earth the power supply according to the details in step 2 below. 1. Make a panel cut-out according to the dimensions shown below. Cut-out Dimensions 2. If you mount the controller on a metal panel, earth the power supply: a. Bore a hole to suit the NC6-32 screw supplied with the kit. b. Scrape panel paint away from the contact area to ensure a conductive connection. c. Drive the screw into the hole. d. Place the following hardware screw s shank, in the order shown in the accompanying figure: washer, ring cable shoe, second washer, spring, and nut. Note: The wire used to earth the power supply must not exceed 10 cm in length. If your conditions do not permit this, do not earth the power supply. Unitronics 3

Vision OPLC V290-19-C30B, V290-19-T40B 3. Slide the controller into the cut-out, ensuring that the rubber seal is in place. 4. Push the 4 mounting brackets into their slots on the sides of the controller as shown in the figure to the right. 5. Tighten the bracket screws against the panel. Hold the bracket securely against the unit while tightening the screw. 6. When properly mounted, the controller is squarely situated in the panel cut-out as shown in the figure to the right. I/O Modules I/Os are integrated into the system via Snap-in Modules and I/O Expansion Modules. Installation instructions and other data may be found in the module s technical specification sheet. Wiring: General Do not touch live wires. Unused pins should not be connected. Ignoring this directive may damage the device. Caution To avoid damaging the wire, do not exceed a maximum torque of 0.5 N m (5 kgf cm). Do not use tin, solder, or any substance on stripped wire that might cause the wire strand to break. Use crimp terminals for wiring; use 26-14 AWG wire (0.13 mm 2 2.08 mm 2 ). 1. Strip the wire to a length of 7±0.5mm (0.250 0.300 ). 2. Unscrew the terminal to its widest position before inserting a wire. 3. Insert the wire completely into the terminal to ensure a proper connection. 4. Tighten enough to keep the wire from pulling free. 4 Unitronics

Installation Guide Power Supply The controller requires an external 24VDC power supply. The permissible input voltage range is 20.4-28.8VDC, with less than 10% ripple. A non-isolated power supply can be used if a 0V signal is connected to the chassis. You must use an external circuit protection device. Install an external circuit breaker. Guard against short-circuiting in external wiring. Double-check all wiring before turning on the power supply. Do not connect either the Neutral or Line signal of the 110/220VAC to device s 0V pin. In the event of voltage fluctuations or non-conformity to voltage power supply specifications, connect the device to a regulated power supply. To avoid electromagnetic interference, earth the power supply as described on page 3. Communication Ports This series comprises 2 RS232/RS485 serial ports and a CANbus port. Caution Turn off power before making communications connections. Signals are related to the controller s 0V; the same 0V is used by the power supply. Always use the appropriate port adapters. Serial Communications The serial ports are type RJ-11 and may be set to either RS232 or RS485 via DIP switches, in accordance with to the table shown on page 7. Use RS232 to download programs from a PC, and to communicate with serial devices and applications, such as SCADA. Use RS485 to create a multi-drop network containing up to 32 devices. Caution The serial ports are isolated. If the controller is used with a non-isolated external device, avoid potential voltage that exceeds ± 10V. Pinouts The pinouts below show the signals between the adapter and port. RS232 RS485** Controller Port Pin # Description Pin # Description 1* DTR signal 1 A signal (+) 2 0V reference 2 (RS232 signal) 3 TXD signal 3 (RS232 signal) Pin #1 4 RXD signal 4 (RS232 signal) 5 0V reference 5 (RS232 signal) 6* DSR signal 6 B signal (-) *Standard programming cables do not provide connection points for pins 1 and 6. **When a port is adapted to RS485, Pin 1 (DTR) is used for signal A, and Pin 6 (DSR) signal is used for signal B. Unitronics 5

Vision OPLC V290-19-C30B, V290-19-T40B RS232 to RS485: Changing DIP Switch Settings The ports are set to RS232 by factory default. To access the DIP switches, first remove the Snap-in I/O Module, if one is installed, and then remove the back of the controller. Before removing a Snap-in I/O Module or opening the controller, you must turn off the power. Removing a Snap-in I/O Module 1. Locate the four buttons on the sides of the controller, two on either side. 2. Press the buttons and hold them down to open the locking mechanism. 3. Gently rock the module from side to side, easing the module from the controller. Opening and Closing the Controller 1. Locate the slots on the sides of the controller. 2. Open the controller by inserting a flat-bladed screwdriver into the slots located on the side of the controller, then carefully prying off the rear panel. 3. Locate the DIP switches, and then change the settings as required. Settings are shown on page 7. 4. Close the controller by snapping the plastic cover back in its place. 6 Unitronics

Installation Guide Re-installing a Snap-in I/O Module 1. Line the circular guidelines on the controller up with the guidelines on the Snap-in I/O Module as shown below. 2 Apply even pressure on all 4 corners until you hear a distinct click. The module is now installed. Check that all sides and corners are correctly aligned. RS232/RS485: DIP Switch Settings Switch Settings 1 2 3 4 5 6 RS232* ON ON ON OFF ON OFF RS485 OFF OFF OFF ON OFF ON RS485 with termination** ON ON OFF ON OFF ON *Default factory setting **Causes the unit to function as an end unit in an RS485 network Unitronics 7

Vision OPLC V290-19-C30B, V290-19-T40B CANbus These controllers comprise a CANbus port. Use this to create a decentralized control network of up to 63 controllers, using either Unitronics proprietary CANbus protocol or CANopen. The CANbus port is galvanically isolated. CANbus Wiring -V L - 24V Power Supply + Circuit protection device 121 terminating resistor Use twisted-pair cable. DeviceNet thick shielded twisted pair cable is recommended. PE H +V Network terminators: These are supplied with the controller. Place terminators at each end of the CANbus network. Resistance must be set to 1%, 121Ω, 1/4W. -V Connect ground signal to the earth at only one point, near the power supply. L PE H +V The network power supply need not be at the end of the network CANbus Connector -V L PE H +V 121 terminating resistor Helsinki tel. +358 9 540 4940 automation@klinkmann.fi St. Petersburg tel. +7 812 327 3752 klinkmann@klinkmann.spb.ru Moscow tel. +7 495 641 1616 moscow@klinkmann.spb.ru Yekaterinburg tel. +7 343 287 19 19 yekaterinburg@klinkmann.spb.ru Samara tel. +7 846 273 95 85 samara@klinkmann.spb.ru Кiev tel. +38 044 495 33 40 klinkmann@klinkmann.kiev.ua Riga tel. +371 6738 1617 klinkmann@klinkmann.lv Vilnius tel. +370 5 215 1646 post@klinkmann.lt Tallinn tel. +372 668 4500 klinkmann.est@klinkmann.ee Мinsk tel. +375 17 200 0876 minsk@klinkmann.com