ecounit : Room operating unit with EnOcean wireless technology

Similar documents
EY-RU : Room operating unit with EnOcean wireless technology, ecounit

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-RU 355: Room operating unit, ecounit355

EY-SU 358: Push-button unit for room operating unit, ecounit358

I/O module, analogue outputs and universal inputs

EYE 200: DDC single-room controller, ecos200

modu : Local override and indicating units

I/O module, digital and universal inputs, modu530

I/O module, digital outputs (relays), modu550

I/O module, universal, digital, S0 inputs, modu533

I/O module, digital outputs (open collector), modu551

modunet292: novanet-ethernet interface

EY-IO 534: I/O module, analogue inputs with galvanic isolation, modu534

EY-EM : Remote I/O module, ecolink

EY-RC 500: Room automation station, ecos500

Content. Product Description

Weekday / weekend room temperature controller

7-day room temperature controller

7-day room temperature controller

EY-RC 208, 209: Room automation stations, ecos208, 209

Sauter Systems

Room unit with PPS2 interface

UCU Room Display. Operation Modes. Features. Applications DATASHEET

24-hour room temperature controller

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

STRA-17 Room controller. Installation and maintenance manual. Content

Master room unit for RRV controllers

Room unit with PPS2 interface

Room unit with PPS2 interface

EY-WS 500: Web server for moduweb Vision and moduweb500 BACnet networks

ERF910. RF Repeater. Synco living

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

Wireless Small Actuator MAC-WSA

EY-RC 311: Programmable controller, ecos311

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Getting Started V1.5

Room Temperature Controller

PRESENCE DETECTOR, CONSTANT LIGHT CONTROLLER PD00D01KNX. Product Handbook

Semi flush-mounted room temperature controllers with LCD

Product and Application Description

Room unit with PPS2 interface

Room Temperature Controller

AVM 321, 322: Valve actuator

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

Network node WTT56.. A6V _en--_c Building Technologies

252F 5WG FB_1 DELTA

AVF 125S: SUT valve actuator with spring return

RNN5-STD NETWORK NODE FOR AMR SYTEMS

Room Temperature Controller with 7-Day Time Switch, LCD and opt. Remote Temperature Sensor

Heating Circuit Controller

The network node works extremely well in more complex building environments (e.g. where fire doors/glass walls are installed).

T7270B2009 WIRELESS WALL MODULE

User Manual EDK 350 Developer Kit EDK 352 Thermo Developer Kit (EDK 350 upgrade) EPK 350 Programmer Kit (ESK 300 upgrade)

Semi flush-mounted room temperature controllers with LCD

Super universal modules

testo 184 Data logger Instruction manual

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

7-day room temperature controller

Weekday / weekend room temperature controller

Product and functional description

EY-AS 521: Compact automation station, modu521

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

Status display unit with P-bus connection

Room Temperature Controllers

User Manual. EDK 400J EnOcean Developer Kit

Digital input modules

902 MHz Wireless Relays Application Manual Bulletin B1867

Pre-programmed room controller with display and communication

902 MHz Wireless Relays Application Manual Bulletin B1867

Application description

Manual operation and local visualisation. with SAUTER EY-modulo.

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

ABB i-bus KNX KNX/EnOcean Gateway EG/A , 2CDG R0011

ProcessCalibrator Model CPH6000

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

CMC III Universal Sensor

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

Semi Flush-mount Room Temperature Controllers with LCD

GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26

EDK MHz EDK 350U 902 MHz EDK 400J 928 MHz. EnOcean Developer Kits USER MANUAL. Observe precautions! Electrostatic sensitive devices!

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

Power Load Controller F series INSTALLATION GUIDE

Heating Circuit Controller

Product and Applications Description. Application programs. instabus EIB Technical Product Information. February 2012

Use of the application program

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001

Data sheet. Function description. Benefits

B. AVM321S/AVM322S: 1000N Actuator with analog SUT positioner

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

Eco Climate Control. Intelligent comfort for radio control of surface heating and cooling systems.

LRA1750, LRM1763, LCC172x Datasheet OccuSwitch Wireless System

Product and Function Description

Transcription:

SAUTER EY-modulo 5 PDS 94.010 en Product Data Sheet EY-RU110...146 ecounit110...146: Room operating unit with EnOcean wireless technology How energy efficiency is improved Individual setting of occupancy and absence, plus room setpoint correction and control of lighting and window blinds in order to optimise the use of energy in the room. Areas of application Operating unit to control and ensure maximum indoor comfort. Temperature measurement and control for rooms with various types of equipment thanks to room automation stations with an EnOcean interface. Features Part of the SAUTER EY-modulo 5 system family Can be extended with the EY-SU106 switching unit Room operating unit with a wide range of different functions, designs and colours Device insert with transparent front, fits into frame with 55 55 mm aperture Frame can be ordered as an accessory Indoor climate can be adapted individually Operating mode is set for room occupancy and control of a three-speed fan Lamp control, on/off/dimming Window blind control Window control Display with extensive status information on room conditions Technical description Power supply from integrated solar panel Optional battery operation EnOcean wireless protocol Approx. 30 m range depending on type of building Products Type EY-RU110F001 EY-RU141F001 EY-RU144F001 EY-RU146F001 NTC sensor Operating unit with LCD, NTC, dxs setpoint correction, 2 buttons Operating unit with LCD, NTC, dxs setpoint correction, fan, occupancy, 4 buttons Operating unit with LCD, NTC, dxs setpoint correction, fan, occupancy, window blinds/lights, 6 buttons Technical data Electrical supply Permitted ambient conditions Power supply from integrated solar panel Operating temperature 0 45 C (optional battery operation) Storage and transport temperature 25 70 C Min. illuminance 250 Lux, 5 h Humidity 5 85% rh, no condensation Power reserve without lighting typically 60 h Installation Specifications Fitting Recessed/surface-mounted Sensors: (see list of accessories) Measuring range 0 40 C Dimensions W H D (mm) 59.5 59.5 25 Resolution 0.1 K Weight (kg) 0.1 Time constant approx. 7 min Error: room temperature typically 0.5 K in the range 5 35 C Standards, guidelines and directives Functionality: Degree of protection IP 30 (EN 60529) Setpoint correction adjustable Protection class III (EN 630-1) Room occupancy (presence) 3 modes, LCD display Environmental class 3K3 (IEC 621) Fan speed 5 functions, LCD display CE conformity as per EMC Directive 2004/108/EC EN 61000-6-1, EN 61000-6-2 Connection to ecos 5: no wiring required, connection to SLC EN 61000-6-3, EN 61000-6-4 via wireless interface EY-EM580 Radio directive R&TTE 1999/5/EC EN 50371, EN 300489-1 (V1.8.1) Technology EnOcean, STM 300 EN 300489-3 (1.4.1) Transmission frequency 868.3 MHz EN 300220-1 (V2.1.1) Range approx. 30 m depending on type EN 300200-2 (V2.1.2) of building EnOcean Equipment Profile (EEP V2.0) EEP: 2D-00-01* Additional information (in bi-directional mode) Fitting instructions EPP: -10-01** EY-RU141 146 MV P100002468 (in uni-directional mode) EY-RU110 MV P100002471 EEP: 05-03-01** Operating instructions BA P1000833 (buttons 3, 4, 7 12 Material declaration MD 94.010 Dimension drawing M11452 * ecounit141 146 Wiring diagram A10647 ** ecounit110 146 A10648 www.sauter-controls.com 1/9

Accessories Type Operation EY-SU106F001 Switching unit with solar panel, 6 buttons, without frame Installation 0949360002 4-pin plug-in connector for ecos room operating unit (10 pcs) 0949241301 Transparent single cover (10 pcs) 0940240*** For frames, fixing plates and adaptors for third-party frames, see product data sheet PDS 94.055 Energy supply in permanently darkened room 0949570001 Battery pack, 10 pcs Front view and labelling inserts Various labelling inserts are included, depending on the device type. These enable the device to be adapted to room conditions. Labelling inserts EY-RU110 EY-RU141 EY-RU144 EY-RU146 2/9 www.sauter-controls.com

of function The ecounit 1 wireless room operating units EY-RU 110...146 record the room temperature and have buttons for setpoint correction, to select the occupancy mode and the fan speed and up to two freely allocatable buttons. The devices are wireless and communicate via EnOcean wireless protocol. Energy is supplied by the integrated solar cell, meaning that no battery is required. The devices can be operated using wireless interfaces from other manufacturers if they comply with the EnOcean standard. In conjunction with the ecomod580 wireless interface, the devices can be used with ecos 5 room controllers. The bi-directional function means that the room controller can affect the content of the LCD. More information about EnOcean wireless technology and the positioning of the wireless interface and the room operating units is available in the "Project engineering using EnOcean wireless technology" manual (7010084001). Engineering notes Installation EY-RU110 146 room operating units are suitable for various types of mounting. Product data sheet PDS 94.055 shows the mounting options and the accessory material required. Fitting notes As a general rule, the use of non-sauter frames should be checked in advance. EY-RU141 146 room operating units can be extended by 6 pushbutton functions by means of the EY-SU106 switching unit. The EY-SU106 is always connected to an EY-RU110 146 via a fourcore cable and can be used only in conjunction with this device. The EY-SU106 switching unit can also be installed at a distance of up to 1 m (total line length) from the EY-RU1. For information on choosing the right location with regard to the radio properties and the power supply from solar energy, please refer to the application notes for the ecomod580 wireless interface with ecounit110 146. Connection to ecos 5 The room operating unit exchanges information with the ecomod580 wireless interface (send/receive). The wireless interface is connected to the SLC interface of the ecos 5 via a fourcore cable. The wireless interface must be connected to the ecos 5 while the equipment is dead (no voltage). Up to four ecounit 1 can be assigned to one wireless interface. For more information on the wireless interface, see PDS 94.015. Minimum illuminance in relation to time Minimum illuminance Light conditions at fitting location 125 lx min. 10 h per day 250 lx min. 5 h per day 500 lx min. 2.5 h per day The minimum illuminance applies to artificial light; daylight may produce better values. The minimum illuminance is sufficient for a maximum of 20 keystrokes per day and a measuring cycle of 180 s (as delivered ex works). Shorter measuring cycles or a greater number of keystrokes require more energy and, therefore, a higher illuminance. For comparison, the Workplace Ordinance requires a minimum illuminance of 500 lx for office workplaces. Recesses in rooms that are not adequately lit throughout the day should be avoided. It is preferable to fit the sensor with the solar panel side facing towards a window, but direct sunlight should be avoided. Direct sunlight would falsify the measured temperature values. The fitting location should also be chosen with the subsequent use of the room in mind, so as to avoid shadows cast by users due to storage areas or movable objects etc. Rooms with insufficient daylight A battery pack can be used as an accessory to provide the power supply for devices in rooms with insufficient daylight. The battery pack is connected via terminals and is stowed on the back of the device. The device has to be configured for battery mode. Alternatively, a second solar panel can be wired in. This is combined with the EY-SU106 switching unit. Summary of functions and button assignment The following data are transmitted from the room operating unit to the wireless interface: Temperature Setpoint adjuster Occupancy function (3-stage: comfort, reduced, lowered) Fan speed (5-speed: AUTO, 0, 1, 2, 3) Switching functions for lights and window blinds. A Send command is issued when the button is pressed and released. Address of the operating unit The room operating unit transmits its data on the basis of the EnOcean standard. Each operating unit has one single and unique address, based on the EnOcean wireless module that is used. This address is stored in the wireless interface during the initial learning process. Power supply and choice of fitting location The power supply is provided from the integrated solar panel; for this purpose, the solar energy is stored in a high-capacity condenser ('super cap'). Operation of this super cap must be started by connecting ports 01 and 02 with the activation plug that is included in delivery. When selecting the fitting location, the following points (especially the light conditions) should be borne in mind: www.sauter-controls.com 3/9

EY-RU14x with EY-SU106: button assignment Transmission of fan speed ecounit 1 transmits the fan speed as an absolute value to the ecomod580, which sends pulses to the ecos 5 until the ecos feedback equates to the fan speed requested. Transmission of presence mode The procedure is similar to the Transmission of fan speed above. Display Seven-segment display Key Button Function 1 Occupancy function 2 Decrease setpoint ( ) 3 Freely assignable 4 Freely assignable 5 Increase setpoint (+) 6 Fan speed Buttons 7 to 12 on the switching unit can be assigned freely. Display functions and communication in general To ensure optimal availability of the ecounit 1 operating unit even under poor light conditions, the display on the ecounit 1 is switched off on completion of a user action. Depending on the transmission parameters that have been set, the actual temperature value will be transmitted at intervals. The display of the ecounit 1 is activated by pressing one of the buttons (1-6). This also synchronises the data between the gateway and the wireless room operating unit. The display shows the current values from the ecos 5. If you press button 3 or 4 or any of the buttons between 7 and 12, the button status is immediately transmitted to the ecos 5 by means of a PTM telegram. Operating the switching unit does not activate the display (in order to save energy). The values for setpoint correction, occupancy mode and fan speed are shown first on the room operating unit via the integrated cyclical circuit, and are then sent to the ecos 5. Data are sent only after a period of approximately 3 s during which no button is pressed. After transmission, the room operating unit synchronises itself with the ecos 5 user programme, which is co-ordinated with the cyclical circuit in the room operating unit. Once the display for occupancy mode or fan speed has been deactivated, normal push-button operation is transmitted by the wireless room operating unit. The display is used for various functions: Function Actual value/setpoint display in C Actual value/setpoint display in F Shown as 3-digit, last digit is 'C' Measuring range 0 40 C, resolution 0.1 K 3-digit, last digit is 'F' Measuring range 32 99.9 F Resolution 0.2 K Setpoint correction C/ F Digit 1: ± Digits 2, 3: 0 9.9 K Digit 4: C/ F Possible only in bi-directional mode Date display DD:MM or MM:DD (can be selected) Time display HH:SS Humidity rh Digits 1 and 2 as value (00-99) Digit 3: r Digit 4: H The '%' symbol is shown in addition. Illuminance lx 0 9999 lx % 0 0.9999: Display: 0...99.99% 1 : display: 100% ppm Bi-directional mode 0 0.009999: display: 0 9999 ppm The ecounit 1 room operating units work with ecos 5 in bidirectional mode, i.e. information is transmitted in both directions. 4/9 www.sauter-controls.com

Uni-directional mode In uni-directional mode, the ecounit 1 can be connected to various third-party receivers (such as heating valves). In this case, the display shows the last data sent by the ecounit 1 to the receiver. It is possible to configure the ecounit 1 to run in uni-directional mode. If the ecounit 1 is operating with an 'alien' receiver (e.g. EYmodulo ecos 4), the temperature display can be either C or F if configured accordingly. The value for the temperature display comes directly from the in-built sensor (and not as feedback from the ecos 5 to the ecounit 1 via ecomod580). Configuration display 1 2 digit 1: Configuration identifier digit 2: Prefixed sign (-) digits 3 and 4: Settings 6 5 3 4 Note ecounit110 does not have a display, so it cannot be re-configured manually. This means, therefore: The ecounit110 works only in bidirectional mode (EEP: -10-01). For ecounit 1, only the default settings (shown below) apply. Configuration of ecounit 1 Configuration identifier (digit 1) Denotes Values (digits 3 and 4) 0 Access to configuration 00 = Manual + Service Tool (default) 01 = via Service Tool only Note This mode can be changed only with the Service Tool. 1 Measuring cycle (digit 3) 00 = No measurement (operation only) 01 60: 10 600 s Default 18: 180 s 2 Mandatory cycle 00: Send on every measuring cycle 01 : send once every 5 35 measuring cycles Default 01: every 5 measuring cycles 3 Measured value hysteresis for spontaneous transmission, i.e. if the hysteresis threshold is exceeded, the measured value is transmitted immediately, regardless of the mandatory cycle. Note If the time for the mandatory cycle > 120 min, this parameter is reset to a lower value. 00 15 as a multiple of 0.2 K Examples: 00: 0 K 05: 1 K 10: 2 K Default for 01: 0.2 K 4 Normal mode or battery mode 0: Normal (default) 1: Battery 5 Select or lock function(s) for button 1 or 6 (EY-RU144 and EY-RU146 only) The identifiers 6, 7, 8 and 9 are valid for uni-directional mode only: 6 Select display for actual value: C or F 00 = C ( default) 01 = F 7 Display and setting range for setpoint correction (max. ± 9.9 K) Shown without C or F ( 9.9 +9.9 ) 00 (bi-directional mode) default EY-RU14x uni-directional mode: 01 dxs only, default for EY-RU14x 02 dxs + occupancy function 03 dxs + fan function 04 dxs + occupancy + fan 00 99: ±0,0K ±9.9 K 20: 2.0 0.0 2.0 (default) www.sauter-controls.com 5/9

Configuration of ecounit 1 (continue) Configuration identifier (digit 1) Denotes Values (digits 3 and 4) 8 Resolution of setpoint correction range 00 99 (number of steps based on 0 max. value) Transmission of setpoint correction: as a number between 0 255, without mathematical sign. The set resolution affects the change in value each time a button is pressed as follows: Value = 255/ (2 resolution) 9 Correction value: Calibrate displayed value (Xi); the correction value (with the correct prefixed sign) is added to the measured actual value. The device sends Xi plus the measured correction value. F Version of firmware for room operating units. Default 04: 255/ (2 04) = 32 Example of default setting (Configuration identifiers 7 and 8) Display range 20: -2.0 2.0 Resolution 04: the range 0 2.0 C is split into four steps Display: 2 / 1.5 / 1/ 0.5 / 0 / 0.5 / 1 / 1.5 / 2 Value transmitted: 0/32/64/96/128/160/192/224/225 00 99: 0.0 9.9 K Digit 2 = prefixed sign ( ) Default 0: 0 K Setpoint correction display When buttons 2 ( ) or 5 (+) are pressed, the last valid setpoint correction value is shown and changed according to the definition. For a change of occupancy via button 1, the setpoint correction is reset to 0. Bi-directional mode: The range and steps are derived from the entry in the ecos 5 ROOM_UNIT firmware module. Uni-directional mode: range and steps as per configuration identifiers 7 and 8 in the ecounit 1 (see the table, Configuration of ecounit 1). Changing a configuration Step 1 Switch to configuration mode Press button 6 for at least 7 10 s without releasing it; this will trigger a switch to configuration mode. During this time, the display is turned on for approx. 5 s, and then it remains off for 2 5 s before the switch to configuration mode. The first 3 digits are shown (digit 1 = configuration identifier, digits 2 and 3 = set value). Starting from now, button 1 or 6 must be pressed within 10 s, otherwise the device will automatically switch back to operating mode. 2 You can now select the configuration identifier that you want with button 6 = increment and button 1 = decrement; you must press the buttons for more than 1 s to do this. After the highest configuration identifier is reached, the display switches back automatically to identifier 0. If identifier 0 is shown and you switch back to the preceding identifier, the highest identifier is shown. Select a configuration 3 Change the setting You can change the current value with button 6 = increment and button 1 = decrement; to do this, press the buttons briefly, i.e. for less than 1 s. Press button 1 or 6 for more than one second to switch to the next or previous configuration identifier. 4 Save the configuration and exit from configuration mode Press button 1 for approx. 5 s; the previous configuration identifier will now be shown briefly (for approx. 2 s). The display is switched off after this. The data have now been saved and you can release the button. 5 Exit from configuration mode without saving data If no button is pressed for approx. 10 s, the system switches automatically to operating mode (and changed data are not saved). 6/9 www.sauter-controls.com

EnOcean transmission standards ecounit 1 transmits its data in two modes. Control functions (buttons 1, 2, 5, 6) in the STM profile: Bi-directional mode: EEP: 2D-00-01 for use with ecomod580 wireless receiver Uni-directional mode: EEP: -10-01 Switching functions (buttons 3, 4, 7 to 12) in the PTM profile via RPS telegrams: EEP: 05-03-01 of EEP wireless telegram: -10-01 DATA BYTES: TYPE = 01 Temperature sensor; setpoint, fan speed and occupancy mode Data byte Content Value range DB_3 Fan Auto speed 210 255 Speed 0 190 209 Speed 1 165 189 Speed 2 145 164 Speed 3 0 144 DB_2 Setpoint min. max. +, linear n = 0 255 DB_1 Temperature 0 40 C, linear n = 255 0 DB_0.BIT_3 Learn button 0 = Teach-in telegram 1 = Data telegram DB_0.BIT_0 Occupancy button 0 = Button pressed of EEP wireless telegram: 05-03-01 DATA BYTES Buttons 3, 4, 7 12 N-MESSAGE STATUS FIELD: T21 = 0; NU = 1 DB_3 if button is pressed Button 3 0 10 Button 4 0 30 Button 7 0 50 Button 8 0 90 Button 9 0 D0 Button 10 0 F0 Button 11 0 B0 Button 12 0 70 DB_3 if button is released Button 3 0 00 Button 4 0 20 Button 7 0 40 Button 8 0 80 Button 9 0 C0 Button 10 0 E0 Button 11 0 A0 Button 12 0 60 DB_3.BIT_4 'Energy Bow' released 0b0 'Energy Bow' pressed 0b1 Learning and addressing Learning and/or addressing are carried out in the ecounit 1's operating mode. Press button 1 for at least 5 s and the ecounit 1 will send a learning telegram; this also forces the temperature to be sent immediately. As a general principle, the receiver (e.g. ecomod580) is switched to learning mode first (the learning procedure depends on the receiver used); after this, the operating unit is manually induced to send a learning telegram. If the receiver is not in learning mode, no operating unit can be assigned. If a learning telegram is sent, it will have no effect. General notes on the learning function The snowflake symbol denotes that the learning process was successful. If, the snowflake symbol does not appear after the learn button has been pressed for at least 5 s, it can be assumed that the learning process was unsuccessful. If, in addition to the snowflake, a colon appears in the lower line, this denotes that the learning process has already been carried out successfully on this RU (on either the current or another gateway). Similarly, the learning process was successful when the snowflake and the colon appear. If, during the learning process, the learn button is released before the snowflake (or an error message) appears, the operator must wait until the display has been deleted before pressing the learn button again. Only then can a new learning process be started. If the learning process was unsuccessful, the INFO symbol appears with an error message (Err2 ErrC). If an error message is shown, the learning process must be repeated. www.sauter-controls.com 7/9

List of error messages and their meaning Error message Meaning Err2 No communication to the gateway. Cause: Not learnt; outside the radio range, interference prevents communication. Err3 Err4 Err5 Err6 Err7 Err8 Err9 ErrA ErrB ErrC Internal error. Cause: Device is defective LEARN OUT message received. Cause: Learning was not successful, repeat the learning process. Invalid EnOcean telegram received (CHOICE): repeat the learning process/query. Mailbox not available. Cause: Learning was not completed; repeat the learning process. Mailbox empty. Cause: Gateway was unable to answer the query in time; repeat the query by pressing the button again. N.B.: If the message remains, repeat the learning process. Internal error EEP EnOcean profile invalid. Cause: Interference prevents correct communication or device is defective. Postmaster full (no more post boxes possible): maximum number of post boxes has been reached on the postmaster. Cause: Internal error in gateway. Solution: Delete all transmitters and memory locations in the gateway, then 'teach in' the transmitters again. Controller full (no more post boxes possible): maximum number of post boxes has been reached on the controller. Cause: Internal error in gateway. Solution: Delete all transmitters and memory locations in the gateway, then 'teach in' the transmitters again. Radio signal to gateway is too weak. Cause: Outside the radio range, interference prevents communication. Solution: Change the position of the gateway or the transmitter in order to obtain a reliable wireless connection. See also the application notes on ecomod580 wireless interface with ecounit110 146 Invalid telegram: The received telegram was faulty, so it was rejected. Cause: Interference prevents reliable communication. Solution: Repeat query press button again. If the problem recurs, remove the source of interference. The error messages Err2, Err5, Err6, Err7 and ErrC may also during normal operation. All other error messages may appear during the learning process. Dimension drawing 25 59,5 15,5 M11452 59,5 8/9 www.sauter-controls.com

Wiring diagram Connection with switching unit, without battery EY-SU106 EY-RU1.. + GND + GND 04 05 06 04 05 06 01 02 03 Terminal 04, 05 Solar panel 06, Key function Connection with switching unit and battery EY-SU106 EY-RU1.. 04 05 06 04 05 06 Terminal 01 NC CR2032 02 (GND) 03 + (typically 3 V) Fr. Sauter AG Im Surinam 55 CH-4016 Basle Tel. +41 61-695 55 55 Fax +41 61-695 55 10 www.sauter-controls.com info@sauter-controls.com Printed in Switzerland www.sauter-controls.com 71940100039/9