PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

Similar documents
PSR-PS21. SIL coupling relay. Data sheet. 1 Description

PSR UC/ESAM4/3X1/1X2/B

PSR DC/ESP4/2X1/1X2

PSR-PC20. SIL coupling relay. Data sheet. 1 Description

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Safety module - PSR-SCP- 24DC/TS/S

ETD-BL-1T-OFF-CC- 10S

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

MINI-PS AC/10-15DC/8

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

QUINT-BUFFER/24DC/24DC/40

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Safety relay emergency stop/protective door, 24VDC/AC, 4 enabling paths

TRIO-DIODE/12-24DC/2X10/1X20

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

PHOENIX CONTACT Features

IB IL 24/48 DOR 2/W-XC-PAC

MINI MCR-SL-CVS NC

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

ELR H3-IES-PT- 24DC/500AC-...

MACX MCR-EX-SD LP(-SP)

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

QUINT-PS-3x AC/24DC/10

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

QUINT-PS/ 1AC/24DC/ 5

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Redundancy Module QUINT-DIODE/40

Datasheet - SRB 402EM-24V

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

Safety relay emergency stop/protective door, 24VDC/AC, 3 enabling paths

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Safety relay emergency stop/protective door, 230VAC, 3 enabling paths

FL MC 2000E (SM40) LC

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-PS/ 1AC/24DC/20/CO

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

Safety relay emergency stop/protective door, 24V-230VDC/AC, 3 enabling paths

PHOENIX CONTACT - 05/2007

STEP-PS/1AC/24DC/1.75

MACX MCR-SL-(2)I-2)I-ILP(-SP)

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

MINI MCR-SL-PT100-UI-200

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet.

QUINT-PS AC/24DC/10

PI-EX-ME-2NAM/COC-24VDC

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

QUINT-PS/24DC/48DC/ 5

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

PI-EX-ME-2NAM/COC-120VAC

MINI MCR-2-U-I4(-PT) 3-way signal conditioner. Data sheet. 1 Description

PHOENIX CONTACT - 12/2007

Operating instructions. Speed monitor D / / 2014

MACX MCR-EX-SL-NAM-R(-SP)

RTU500 series Data Sheet Power Supply CP-E 24/2.5

MACX MCR-EX-SL-NAM-2RO(-SP)

ABL1REM24025 regulated SMPS - single phase V input - 24 V output - 60 W

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Original operating instructions Safety relay with relay outputs G1501S / / 2016

SECTION 16 LED DIAGNOSTIC FEATURES: EXPANSION UNITS: SCR-31P-i. SCR-73-i. SEU-31-i. SCR-31-42TD-i. SEU-31TD-i

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

Datasheet - SRB 301LC/B-24V

Power supply CP-C 24/5.0

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

Safety Technique. SAFEMASTER C Multifunction Safety Module BH 5910

Extract from the online catalog

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Original operating instructions Fail-safe inductive sensor GG711S

Original operating instructions Fail-safe inductive sensor GI712S

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

Operating instructions. Switching amplifier DN0210 DN / / 2015

ASI QUINT /2.4 EFD

Datasheet SRB301ST 24V (V.2)

1-Phase Power Supply, Primary Switch Mode for Use in Potentially Explosive Areas QUINT-PS AC/24DC/5/EX

Electronic timer CT-AHD.22

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

E-STOP relays, safety gate monitors

MINI MCR-SL-UI-REL(-SP)

Electronic timer CT-ERD.12

MINI MCR-SL-PT100-UI(-SP)(-NC)

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

Power Supply HARTING pcon

Electronic timer CT-ERS.21

PHOENIX CONTACT - 01/2007

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

PHOENIX CONTACT - 02/2008

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Redundancy unit CP-A RU

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

Transcription:

SILCL IEC 62061 Safety relay for emergency stop, safety door and light grid monitoring Data sheet 106171_en_01 PHOENIX CONTACT 2015-05-19 1 Description Intended Use The PSR-MS60 safety relay can be used to monitor twochannel signal generators, e.g., emergency stop buttons, safety door locking mechanisms, and light grids, as well as to control actuators. The safety relay is equipped with two single-channel enabling current paths that drop out without delay according to stop category 0 and EN 60204-1. The enabling current paths are controlled automatically once the sensor circuit has been closed. Features Safety relay for emergency stop, safety door, and light grid monitoring Suitable up to category 4, PL e (EN ISO 13849-1), SILCL 3 (EN 62061) 1 two-channel sensor circuit 2 undelayed single-channel enabling current paths Fixed screw connection 6.8 mm housing width WARNING: Risk of electric shock Observe the safety instructions in the corresponding section! Make sure you always use the latest documentation. It can be downloaded from the product at phoenixcontact.net/products. This data sheet meets the same requirements as the original operating instructions in terms of contents and is valid for all products listed on the following pages.

2 Table of contents 1 Description... 1 2 Table of contents... 2 3 Ordering data... 3 4 Technical data... 3 5 Safety notes... 6 6 Basic circuit diagram... 7 7 Derating... 7 7.1 Vertical or horizontal mounting position... 7 8 Load curve... 7 8.1 Ohmic load... 7 9 Function/time diagrams... 7 10 Operating and indication elements... 8 10.1 Connection versions... 8 10.2 Connection assignment... 8 11 Mounting and connection... 9 12 Startup... 9 13 Calculating the power dissipation... 10 14 Diagnostics... 11 14.1 General states... 11 14.2 Error Messages... 11 15 Application examples... 12 15.1 Light grid monitoring/automatic start... 12 15.2 Two-channel control via LPSDO module... 12 15.3 Single-channel control via failsafe controller... 12 16 Revision history... 13 106171_en_01 PHOENIX CONTACT 2

3 Ordering data Description Type Order No. Pcs. / Pkt. Safety relay for emergency stop, safety doors, and light grids up to SIL 3, SILCL 3, Cat. 4, PL e, 2-channel operation, automatic start, 2 enabling current paths (1-channel), U S = 24 V DC, fixed screw terminal block PSR-MS60-2NO-24DC-SC 2904958 1 4 Technical data Hardware/firmware version HW/FW 00/-- (The technical data and safety characteristics are valid as of the specified HW/FW version.) Input data Rated control supply voltage U S 24 V DC -15 % / +10 % Rated control supply current I S typ. 40 ma Typical inrush current 4.5 A ( t = 120 s at U s ) < 20 ma (with U s /I x to S12) < 20 ma (with U s /I x to S22) Current consumption < 5 ma (with U s /I x to S12) < 5 ma (with U s /I x to S22) Power consumption at U S typ. 0.96 W Voltage at input/start and feedback circuit 24 V DC -15 % / +10 % Filter time 1 ms (at in the event of voltage dips at U s ) max. 1.5 ms (Test pulse duration) min. 7.5 ms (Test pulse rate) Test pulse rate = 5 x Test pulse width Max. permissible overall conductor resistance 150 Ω (Input and reset circuit at U S ) Typical response time at U s < 175 ms Typical starting time with U s < 250 ms (when controlled via ) Typical release time with U s < 20 ms (when controlled via or S12 and S22.) Recovery time < 500 ms Maximum switching frequency 0.5 Hz Operating voltage display 1 x green LED Status display 2 x green LEDs Protective circuit Surge protection Suppressor diode Reverse polarity protection for rated control supply voltage Output data Contact type 2 enabling current paths Contact material AgSnO 2 Minimum switching voltage 10 V AC/DC Maximum switching voltage Limiting continuous current Maximum inrush current Inrush current, minimum Sq. Total current Switching capacity min. Mechanical service life Output fuse 250 V AC/DC 6 A (N/O contact) 6 A 3 ma 72 A 2 (see to derating) 30 mw 10 x 10 6 cycles 6 A gl/gg (N/O contact) 4 A gl/gg (for low-demand applications) 106171_en_01 PHOENIX CONTACT 3

General data Relay type Electromechanically forcibly guided, dust-proof relay. Nominal operating mode 100% operating factor Degree of protection IP20 Min. degree of protection of inst. location IP54 Mounting type DIN rail mounting Mounting position vertical or horizontal Assembly instructions See derating curve Dimensions (W/H/D) 6.8 x 93.1 x 102.5 mm Type of housing PBT yellow Clearances and creepage distances between the power circuits DIN EN 50178 Rated insulation voltage 250 V AC Rated surge voltage/insulation Safe isolation, reinforced insulation 6 kv between input circuit and enabling current path (13/14) and enabling current path (23/24) Basic insulation 4 kv between all current paths and housing Pollution degree 2 Surge voltage category III Connection data Connection method Screw connection Conductor cross section, solid 0.2 mm²... 2.5 mm² Conductor cross section, stranded 0.2 mm²... 2.5 mm² Conductor cross section AWG/kcmil 26... 12 Stripping length 12 mm Screw thread M3 Ambient conditions Ambient temperature (operation) -40 C... 55 C (observe derating) Ambient temperature (storage/transport) -40 C... 85 C Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing) Max. permissible humidity (storage/transport) Maximum altitude Shock Vibration (operation) Conformance / approvals Conformance CE-compliant Approvals $ Safety data Stop category according to IEC 60204 0 Safety parameters for IEC 61508 - High demand SIL 3 PFH d Demand rate Proof test interval Duration of use 75 % (on average, 85% infrequently, non-condensing) max. 2000 m (Above sea level) 15g 10 Hz...150 Hz, 2g 1.5 x 10-9 (4 A DC13; 5 A AC15; 8760 switching cycles/year) < 12 Months 240 Months 240 Months 106171_en_01 PHOENIX CONTACT 4

Safety parameters for IEC 61508 - Low demand SIL 3 PFD avg 1.47 x 10-4 Proof test interval 60 Months Duration of use 240 Months Safety parameters for EN 62061 SIL CL 3 Safety characteristic data according to EN ISO 13849 Category 4 Performance level e (4 A DC13; 5 A AC15; 8760 switching cycles/year) Duration of use 240 Months For applications in PL e, the required demand rate for the safety function is once per month. 106171_en_01 PHOENIX CONTACT 5

5 Safety notes WARNING: Risk of electric shock During operation, parts of electrical switching devices carry hazardous voltages. Before working on the switching device, disconnect the power. Please observe the safety regulations of electrical engineering and industrial safety and liability associations! Disregarding these safety regulations may result in death, serious personal injury or damage to equipment. Startup, mounting, modifications, and upgrades should only be carried out by a skilled electrical engineer! WARNING: Risk of automatic machine restart! For emergency stop applications, the machine must be prevented from restarting automatically by a higher-level control system. Protective covers must not be removed when operating electrical switching devices. WARNING: Danger due to faulty devices! The devices may be damaged following an error and correct operation can no longer be ensured. In the event of an error, replace the device immediately. Repairs to the device, especially if the housing must be opened, may only be carried out by the manufacturer or authorized persons. Otherwise the warranty is invalidated. WARNING: danger due to magnetic interference! Do not use the device in the vicinity of strong magnetic fields (e.g., caused by transformers or magnetic iron). The magnetic field strength of the environment must not exceed 30 A/m. NOTE: Risk of damage to equipment due to noise emissions When operating relay modules the operator must meet the requirements for noise emission for electrical and electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures. NOTE: Risk of damage to equipment due to noise emissions This is a Class A product. In a domestic environment it may cause radion inteference, in which case the user may be required to take adequate measures. Only use power supply units with safe isolation and SELV / PELV in accordance with EN 50178/VDE 0160 (SELV / PELV). NOTE: Electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 61340-5-1 and EN 61340-5-2. WARNING: Risk due to incorrect installation For reliable operation, the safety relay must be installed in housing protected from dust and humidity (IP54). Carry out wiring according to the application. Refer to the Application examples section for this. WARNING: Risk due to welded relay contacts A suitable and effective protective circuit is to be provided for inductive loads. This is to be implemented parallel to the load and not parallel to the switch contact. 106171_en_01 PHOENIX CONTACT 6

6 Basic circuit diagram 8 Load curve S22 S12 13 23 8.1 Ohmic load PSR-MS60 IN / 24V DC A2 Figure 1 Block diagram 14 24 Key: Designation Explanation +24 V power supply A2 0 V power supply S12 Input sensor circuit (channel 1) S22 Input sensor circuit (channel 2) 13/14 Enabling current path (channel 1), undelayed 23/24 Enabling current path (channel 2), undelayed 7 Derating 7.1 Vertical or horizontal mounting position I TH² [A ² ] 70 72 60 50 40 30 20 10 0 0 Figure 2 8 10 20 2830 40 50 55 60 70 T A [ C] Derating curve - vertical or horizontal mounting position with connected modules Figure 3 Relay load curve - ohmic load 9 Function/time diagrams /A2 S12 S22 13/14 23/24 Figure 4 Key: Time diagram Designation Explanation /A2 Power supply S12 Input sensor circuit (channel 1) S22 Input sensor circuit (channel 2) 13/14 Enabling current path (channel 1), undelayed 23/24 Enabling current path (channel 2), undelayed 106171_en_01 PHOENIX CONTACT 7

10 Operating and indication elements 10.1 Connection versions 1 Fixed screw connection 2 Snap-on foot for DIN rail mounting 1 The year the device was constructed can be found underneath the CE designation on the housing. APPROVALS HW/FW: 00/-- HW/FW: 00/-- Serial No. xxxxxxxxxx xxxxxxxxxx 2 Warning Warning -- Do not not seperate seperate when energized! AWG 26-12 0,2-2,5 mm 2 PHOENIX CONTACT GmbH & CO.KG Flachsmarktstrasse 8 32825 Blomberg, Germany 14 12 mm 0,5-0,6 Nm 5-7 lb In Figure 5 Connection versions Figure 6 Year of manufacture of the device 10.2 Connection assignment Figure Designation Explanation +24 V power supply A 1 A 2 S 22 S 12 A2 0 V power supply S22 Input sensor circuit (channel 2) S12 Input sensor circuit (channel 1) IN IN / Power LED (green) Status indicator sensor circuit; LED (green) Status indicator safety circuit; LED (green) MS 60 2 2 1 1 4 3 4 3 23/24 Enabling current path (channel 2), undelayed 13/14 Enabling current path (channel 1), undelayed 106171_en_01 PHOENIX CONTACT 8

11 Mounting and connection Mount the module on a 35 mm DIN rail according to EN 60715. 12 Startup Apply the rated control supply voltage (24 V DC) at terminal blocks /A2. The LED lights up. Close sensor circuit 24 V/S12 and 24 V/S22. The IN LED lights up. The / LED lights up. If the rated control supply voltage drops, the enabling current paths of the output circuits (13/14 and 23/24) open and the contacts enter the safe state. If a channel to the sensor circuit is opened (24 V/S12 or 24 V/S22) the corresponding enabling current path opens (13/14 or 23/24). Figure 7 Mounting and removing Connect the cables to the connection terminal blocks using a screwdriver. B The sensor circuits are assigned to the enabling current paths as follows: S12 to 13/14 and S22 to 23/24 (see block diagram). This means: If only sensor circuit S12 opens, only enabling current path 13/14 is opened. If sensor circuit S22 also opens, enabling current path 23/24 is also opened. AWG 26-12 0,2-2,5 mm 2 A 12 mm 0,5-0,6 Nm 5-7 lb In Figure 8 Connection of the cables For compliance with UL approval, use copper wire that is approved up to 60 C/75 C. 106171_en_01 PHOENIX CONTACT 9

13 Calculating the power dissipation The total power dissipation of the safety relay is based on the input power dissipation and the contact power dissipation for the same and for different load currents. Input power dissipation P Input = U ² B / (U S /I S ) Contact power dissipation With the same load currents: P Contact = n I ² L 25 mω With different load currents: P Contact = (I ² L1 + I ² L2 +... + I ² Ln ) 25 mω Total power dissipation P Total =P Input + P Contact therefore P Total = U ² B / (U S /I S ) + n I ² L 25 mω or P Total = U ² B / (U S /I S ) + (I ² L1 + I ² L2 +... + I ² Ln ) 25 mω Key: Designation P U B U S I S n I L Explanation Power dissipation in mw Applied operating voltage Rated control supply voltage Rated control supply current Number of enabling current paths used Contact load current 106171_en_01 PHOENIX CONTACT 10

14 Diagnostics The following section describes the LED indicators for general states and error messages as well as possible causes and remedies. Function test/proof test Use the function test to check the safety function. To do this, request the safety function once by pressing the emergency stop button, for example. Check whether the safety function is running correctly by switching the device on again via the sensor circuits. 14.1 General states LED IN LED / LED State ON OFF OFF All relays are not activated. The sensor circuit is off. ON ON ON The sensor circuit is active. All relays are picked up. Notes Possible error see error messages - 14.2 Error Messages LED IN LED / LED State Possible cause Remedy ON OFF OFF The sensor circuit is actively controlled, but no input LEDs are lit up. ON ON OFF The sensor circuit is active. The safety circuit ( and ) is not picking up. ON ON OFF The sensor circuit is active. The safety circuit ( and ) is not picking up. Interrupt in the sensor circuit or faulty signal generator. Internal error: 1. The diagnostic contact is not working correctly. 2. An N/O contact is welded. Error in the sensor circuit. OFF OFF OFF The sensor circuit is active. 1. No supply voltage at /A 2. Over- or undervoltage at Check the sensor circuit/signal generator. Then perform a function test. Internal error: perform a power down reset with subsequent function test. If the error occurs again after the function test, replace the device. Check the sensor circuit. Then perform a function test. If the error occurs again after the function test, replace the device. Check the supply voltage. 106171_en_01 PHOENIX CONTACT 11

15 Application examples Key: / = Contactors Applications with the PSR-MS60 15.2 Two-channel control via LPSDO module Two-channel control Cross-circuit detection by means of LPSDO module Automatic start Suitable up to category 4, PL e (EN ISO 13849-1), SILCL 3 (EN 62061) 24V L 15.1 Light grid monitoring/automatic start Two-channel light grid monitoring Automatic start Suitable up to category 4, PL e (EN ISO 13849-1), SILCL 3 (EN 62061) LPSDO 8 V2/V3 DO DO PSDI 8 V2/V3 DI 24V 0V Figure 9 PSR-MS60 A2 Light grid type 4 Transmitter Receiver S12 ( ) S22 ( ) EDM OSSD1 OSSD2 Light grid monitoring/automatic start L N 13 23 14 24 M 0V A2 Figure 10 Two-channel control via LPSDO module 15.3 Single-channel control via failsafe controller Single-channel control Automatic start Suitable up to category 4, PL e (EN ISO 13849-1), SILCL 3 (EN 62061) if the digital output of the safety-related controller meets PL e, SIL 3 and cross-circuits can be ruled out 24V PSR-MS60 S12 ( ) S22 ( ) N L 13 23 14 24 M FAIL-SAFE SPS/PLC DO DO DI PSR-MS60 A2 S12 ( ) S22 ( ) 13 23 14 24 M 0V Figure 11 N Single-channel control via failsafe PLC 106171_en_01 PHOENIX CONTACT 12

16 Revision history Version Date Contents 00 2014-12-03 First publication 01 2015-03-05 Reverse polarity protection extended; relay type extended; dimensions updated; load curve extended 01_c00 2015-05-19 Caption of figure 3 corrected (translation error) 106171_en_01 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 13 phoenixcontact.com