Install the DeviceNet Module using the following procedure:

Similar documents
Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

DeviceNet Module. User Manual. 1 Important User Information. 2 Installation

1. Installation DEVICENET INTERFACE. Install the DeviceNet Interface using the following procedure:

- 15G0078B120 - DEVICENET MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

MCD 200 Series. MCD 200 DEVICENET Module OPERATING INSTRUCTIONS. MCD 200 DEVICENET Module. Order Code: 175G9002. Adjustment.

Copyright: December 2017 Nidec Issue: E

- 15G0078B110 - PROFIBUS MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Ethernet/IP Module. User Manual. Contents

OPERATING INSTRUCTIONS MCD

Profinet Module. User Manual. Contents

1. Introduction. 2. Installation MODBUS INTERFACE

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Section 1.0 Description Section 2.0. Section 3.0. Section 4.0. MCD3000 DeviceNet Gateway. Contents

Copyright: December 2017 Nidec Issue: E

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Installation Guide EtherNet/IP Module

Instructions. Modbus RTU Card (WSIQ-COM-MB)

ETHERNET/IP & PROFINET MODULE

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

PROFINET MODULE. Communications module. User Guide. This manual is to be given to the end user en / a. Power. Error. Status.

1. Introduction. 2. Installation INSTALLATION INSTRUCTIONS: MCD USB MODULE

Installation Guide Modbus TCP Module

Installation Guide PROFINET Module

Installation Guide EtherNet/IP Module

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

ASTAT XB/XBm Remote Operator

Diagnostics (Physical)

1. Warnings Introduction Mechanical Installation Electrical Installation Application Examples...

Section 0.0 Warnings... 2 Section 1.0 Quick Set-up... 3 Section 2.0 Description Section 3.0. Section 4.0. Section 5.0. Section 6.0. Section 7.

Section 0.0 Warnings... 3 Section 1.0 Quick Set-up... 4 Section 2.0 Description Section 3.0. Section 4.0. Section 5.0. Section 6.0. Section 7.

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

Powered Roller Controller for DeviceNet

MICRO-SCREEN DIN Controllers with DeviceNet Trip Output

G3 Series DeviceNet TM Technical Manual

Elco BradControl DEVICENET ACTIVE 60mm Input/Output Interface Block May, 2008

DeviceNet Drive Profile CFW-09

MPCR Series DeviceNet Technical Manual

INTEGRATED MICROSTEPPING MOTOR DRIVER AND HIGH PERFORMANCE MACHINE/PROCESS CONTROLLER

FC 300 DeviceNet and Allen Bradley Control logix 5550

Section 1 Caution Statements... 3 Section 2 Introduction Section 3 Basic Setup Procedure... 5 Section 4 Installation... 6

2002 Series DeviceNet Technical Manual

USERS IMS2 SERIES SOFT STARTERS

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

CDN572-5 DEVICENET SPECIFICATIONS

CONTENTS IMS2 SERIES A. 2.1 Overview Feature List Part Number Format... 3

Diagnostics (Logical) Diagnostics (Physical)

01325T -- Robot Welder

Opal Pro to DeviceNet. Opal Pro MS6 SERIES. DeviceNet Interface Users Manual. Revision Page 1

GSE Scale Systems A div of SPX Corporation

Series SD6 with DeviceNet (Addendum)

Copyright December 2017 Nidec Issue: D

Allen-Bradley Automation

SE-330 SERIES (NEW REVISION) DEVICENET INTERFACE

Softstarters Type PSTX Fieldbus communication, Anybus CompactCom DeviceNet

CONTENTS. Basic Setup Procedure Section 1 Caution Statements Programming and Operation IMS2 SERIES H

DeviceNet for Capacitance Diaphragm Gauge

VLT 5000 DeviceNet and Allen Bradley Control logix 5550

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance.

Installation Instructions for DeviceNet E50 Limit Switches

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor Start-up Guide DeviceNet Adapter Module NDNA-02

VLT 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA. Instruction Manual DeviceNet. Drives Solutions.

MicroNode I/O TM DeviceNet AI User Manual

METTLER TOLEDO DNB User Manual

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET

ABB Drives. User s Manual DeviceNet Adapter Module RDNA-01

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

L5351 DeviceNet Communications Interface

SMART RELAY SRW 01 V4.0X

SE-330/SE-330AU/SE-330HV DEVICENET INTERFACE

DeviceNet Communication Manual

EL731 DEVICENET INTERFACE

Operation manual. HDOM-Profibus-V0. More options please visit;

Installation and maintenance instructions

ZoneLink 4-Zone Controller For use with ZL.S-DK101 and Microroller

Compact Multiprotocol I/O Module for Ethernet 16 Universal Digital Channels, Configurable as PNP Inputs or 2 A Outputs TBEN-L4-16DXP

1 Extended and Advanced Cascade Controller Option 3

1782-JDC DeviceNet/Serial Gateway User s Manual

DeviceNet - ODVA Conformance Test Results

Motors Automation Energy Transmission & Distribution Coatings. Profibus DP SRW 01. User s Manual

DeviceNet Conformance Test Result

Rotary Measuring Technology Absolute encoders, Multiturn, DeviceNet

DeviceNet System Installation manual rev. 3.0

MPS DEVICENET INTERFACE

VersaMax IP Input Module

MPU-32 DEVICENET INTERFACE

Introduction to Danfoss VLT series and DeviceNet... 2

POWR-GARD Motor Protection PGR-6200 SERIES Motor Protection System PGR-6200 DEVICENET INTERFACE

1 How to Read these Operating Instructions 3. 3 Introduction to MCF 106 A/ B in C Option Adaptor 7

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

1.5 axis motion controller

Installation Guide VLT DeviceNet MCA 104

Programming Guide VLT DeviceNet MCA 104

DeviceNet Motor Control

Transcription:

Installation INSTALLATION INSTRUCTIONS: MCD DEVICENET MODULE Order Code: 175G9002 1. Installation Install the DeviceNet Module using the following procedure: 1. Remove control power and mains supply from the soft starter. 2. Attach the DeviceNet Module to the soft starter as illustrated below. 3. Set the DeviceNet Module Node Address (MAC ID) and Data Rate. 4. Apply control power to the soft starter. 5. Insert the network connector into the module and power up the DeviceNet network. MCD 200 MCD 500 177HA368.11 177HA530.10 CAUTION Network designs must decrease the maximum allowable cumulative dropline length by 400 mm for every DeviceNet Module installed on the network. Failure to do so may result in network communication errors and decreased reliability. Example: ODVA specifies a maximum cumulative dropline length of 156 m on a network operating at 125 kb/s. If six DeviceNet Modules were installed on this network, the total cumulative dropline length would need to be decreased to 153.6 m. Remove the DeviceNet Module using the following procedure: 1. Take the module off-line and remove the DeviceNet connector. 2. Remove control power and mains supply from the soft starter. 3. Push a small flat-bladed screwdriver into the slots at the top and bottom of the module and depress the retaining clips. 4. Pull the module away from the soft starter. 177HA378.10 CAUTION Remove mains and control voltage from the soft starter before attaching or removing accessories. Failure to do so may damage the equipment. MG.17.H9.02 VLT is a registered Danfoss trademark 1

Configuration MCD DeviceNet Module 2. Configuration The DeviceNet Module is a Group 2 slave device, using a predefined master/slave connection set. I/O data is produced and consumed using polled I/O messaging. The soft starter must be added to the DeviceNet manager project using the EDS file and configuration/management software tool. This file is available on the supplied CD or can be downloaded from the website www.danfoss.com/drives. In order to operate successfully, the correct EDS file must be used. Product MCD 200 MCD 500 EDS Filename SSDM04_11.eds SSDM07_12_1.eds (serial number version xxxx03-xxx or earlier) SSDM07_13_1.eds (serial number version xxxx04-xxx) An on-screen graphics bitmap file (device.bmp) is available on the supplied CD or can be downloaded from the website www.danfoss.com/drives. 3. Adjustment The factory default settings for the rotary adjustment switches are: 500 kb 250 kb 125 kb DATA RATE PGM NODE ADDRESS ( 00-63, PGM ) 2 4 0 177HA372.11 PGM MSD 2 0 8 LSD 6 4 6 Changes to the rotary switch settings take effect when the DeviceNet network is next powered up. The Data Rate and Node Address (MAC ID) must be set locally on the module. These cannot be set using DeviceNet management software. When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on PGM position, the module uses the previously used valid on-line Data Rate and Node Address (MAC ID). 4. Connection For the DeviceNet Module to accept serial commands, a link must be fitted across terminals A1-N2 on MCD 200 starters. In order for the MCD 500 to accept commands from the serial network, the soft starter must be in Auto On mode and links must be fitted to terminals 17 and 25 to 18. In Hand On mode, the starter will not accept commands from the serial network but the starter's status can still be monitored. MG.17.H9.02 - VLT is a registered Danfoss trademark 2

Module and Network LEDs MCD 200 MCD 500 MCD 200 A1 N2 DEVICENET MODULE MCD500 (Auto On mode) 17 Stop 18 COM 25 Reset DEVICENET MODULE Rd Wh Bu Bk V + CAN_H Shield CAN_L V - 177HA367.11 Rd Wh Bu Bk V + CAN_H Shield CAN_L V - 177HA534.10 Standard connection onto DeviceNet bus Standard connection onto DeviceNet bus If parameter 3-2 Comms in Remote is set to Disable Comms in Remote, the starter will not accept start or stop commands from the serial network (the starter will still accept reset commands and allow status monitoring). 5. Module and Network LEDs The Module LED indicates the condition of the power supply and module operation. The Network LED indicates status of the communication link between the DeviceNet Module and the network Master. LED operation is as follows: Module LED Network LED 177HA366.11 LED State Description Module Off Network power off Green Normal operation Red Unrecoverable fault Red/Green flashing Self Test mode Network Off Duplicate MAC ID test has not been completed Green flashing Online but no connection with Master Green Online and allocated to a Master Red flashing One or more timed out I/O connections Red Failed communication between module and Master Red/Green flashing Communication faulted and received an Identity communication faulted request When a communications failure occurs, the soft starter may trip if the Communication Timeout parameter for the network is set greater than zero. When communication is restored, the soft starter must be reset. MG.17.H9.02 VLT is a registered Danfoss trademark 3

DeviceNet Polled I/O Structure MCD DeviceNet Module 6. DeviceNet Polled I/O Structure Once the EDS file has been loaded, the DeviceNet Module must be added to the scanner list with parameters shown in the following table: Parameter Value I/O connection type Polled Poll receive size 14 bytes Poll transmit size 2 bytes Once the soft starter, module and Master have been set up, configured and powered up, the Master will transmit 2 bytes of data to the module and receive 14 bytes of data from the module. Master > Slave polled I/O output data is as follows: Byte Bit Function 0 0 0 = Stop command 1 = Start command 1 0 = Enable Start or Stop command 1 = Quick Stop (i.e. coast to stop) and disable Start command 2 0 = Enable Start or Stop command 1 = Reset command and disable Start command 3 to 7 Reserved 1 0 to 1 1 0 = Use soft starter remote input to select motor set 1 = Use primary motor set when starting 2 2 = Use secondary motor set when starting 2 3 = Reserved 2 to 7 Reserved 1 Only available on MCD 500 soft starters. 2 Ensure that the programmable input is not set to Motor Set Select before using this function. Slave > Master polled I/O input data is as follows: Byte Bit Function Value 0 0 Trip 1 = Soft starter trip 1 1 Warning 1 = Soft starter warning 2 Running 0 = Unknown, not ready, ready to start or tripped 1 = Starting, running, stopping or jogging. 3 Reserved 4 Ready 0 = Start or stop command not acceptable 1 = Start or stop command acceptable 5 Control from Net 1 = Always except in Program mode 6 Reserved 7 At reference 1 = Running (full voltage at the motor) 1 0 to 7 Status 0 = Unknown (menu open) 1 2 = Starter not ready (restart delay, thermal delay or run simulation) 1 3 = Ready to start (including warning state 1 ) 4 = Starting or running 5 = Soft stopping 7 = Trip 8 = Jog forward 1 9 = Jog reverse 1 2 0 to 7 Trip/Warning code See trip code table below 3 0 Initialised 1 = Phase sequence bit is valid (bit 1) after 1 st start 1 Phase sequence 1 = Positive phase sequence detected MG.17.H9.02 - VLT is a registered Danfoss trademark 4

DeviceNet Polled I/O Structure 2 to 7 Reserved 4 2 0 to 7 Motor current (low byte) Current (A) 3 5 2 0 to 7 Motor current (high byte) 6 2 0 to 7 Current %FLC (low byte) Current as a percentage of soft starter FLC setting (%) 7 2 0 to 7 Current %FLC (high byte) 8 2 0 to 7 % Motor temperature Motor thermal model 9 0 to 7 Reserved 10 1 0 to 7 % Power factor Percentage power factor (100 = power factor of 1) 11 1 0 to 7 Power (low byte) Power low byte, scaled by power scale 12 1 0 to 3 Power (high nibble) Power high nibble, scaled by power scale 4 to 5 Power scale 0 = Multiply power by 10 to get W 1 = Multiply power by 100 to get W 2 = Power (kw) 3 = Multiply power by 10 to get kw 6 to 7 Reserved 13 0 to 7 Reserved 1 Only available on MCD 500 soft starters. 2 Only available on MCD 202 and MCD 500 soft starters. 3 For MCD 500 models MCD5-0068B and smaller this value will be 10 times greater than the value displayed on the LCP. MG.17.H9.02 VLT is a registered Danfoss trademark 5

DeviceNet Polled I/O Structure MCD DeviceNet Module 6.1. Trip Codes Code Trip Type MCD 201 MCD 202 MCD 500 0 No trip 11 Input A trip 20 Motor overload (thermal model) 21 Heatsink overtemperature 23 L1 phase loss 24 L2 phase loss 25 L3 phase loss 26 Current imbalance 28 Instantaneous overcurrent 29 Undercurrent 50 Power loss (Power circuit) 54 Phase sequence 55 Frequency (Mains Supply) 60 Unsupported option (not available in inside delta) 61 FLC too high (FLC out of range) 62 EEPROM fail 70 Miscellaneous 75 Motor thermistor 101 Excess start time 102 Motor connection 104 Internal fault 113 Starter communication (between module and soft starter) 114 Network communication (between module and network) 115 L1-T1 shorted 116 L2-T2 shorted 117 L3-T3 shorted 119 Time-overcurrent (Bypass overload) 121 Battery/Clock 122 Thermistor circuit MG.17.H9.02 - VLT is a registered Danfoss trademark 6

Parameter Object 7. Parameter Object The DeviceNet Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and downloaded (read) using DeviceNet management software. When the DeviceNet Module is powered up, it automatically obtains parameter information from the soft starter. Detail Value (Hex) Comment Class 0F Parameter object address Instance 1 ~ xxx xxx = maximum soft starter parameter number Attribute ID 01 Always 0x01 Get Service 0E Read single soft starter parameter value Set Service 10 Write single soft starter parameter value Only available on MCD 500 soft starters. For parameter details, see the soft starter User Manual. The numbering of parameter options via serial communications differs slightly from the numbering displayed on the LCP. Numbering via the DeviceNet Module starts at 0, so for Par. 2-1 Phase Sequence, the options are 1~3 on the LCP but 0~2 via the module. 8. Specifications Enclosure Dimensions... 35 mm (W) x 157 mm (H) x 90 mm (D) Weight... 250 g Protection... IP20 Mounting Spring-action plastic mounting clips (x 2) Connections Soft starter... 6-way pin assembly Network... 5-way male and unpluggable female connector (supplied) Maximum cable size... 2.5 mm 2 Contacts... Gold flash Settings Node address (MAC ID) Setting... Rotary switches Range... 0 to 63 (63, factory default) Data rate Setting... Rotary switch Options... 125 kb, 250 kb, 500 kb (125 kb, factory default) Power Consumption steady state... 19 ma at 25 VDC... 31 ma at 11 VDC in-rush (at 24 VDC)... 1.8 A maximum for 2 ms Galvanically isolated Certification C... IEC 60947-4-2 CE... IEC 60947-4-2 ODVA... DeviceNet Conformance Tested MG.17.H9.02 VLT is a registered Danfoss trademark 7