Compact Series Unitary Equipment Controller

Similar documents
TC Compact Series Unitary Equipment Controller

PXC Modular Series. Features. Description. Technical Specification Sheet Document No July 24, 2012

TC Modular Series for BACnet Networks

TC Compact Series for BACnet Networks

TC Compact Series for BACnet Networks

PXC Modular Series. Features. Description. Technical Specification Sheet Document No Rev. 1.1, May 2007

PXC Modular Series for BACnet Networks

TC Modular Series. Features. Description. Technical Specification Sheet Document No Rev. 1, July 31, 2008

PXC Modular Series for BACnet Networks

Power Modular Equipment Controller

Unitary Controller. Features. Description. Technical Specification Sheet Rev. 6, March, 2000

Modular Building Controller

TX-I/O Product Range. Description. Technical Specification Sheet Document No February 20, 2018

PXC Compact Series Configuration and Sizing Guidelines

TX-I/O Product Range. Description. Technical Specification Sheet Document No July 18, 2013

TALON Network Manager- 2 & 6 Express

PXC Compact Unitary Equipment Controller (UEC)

TALON System Configuration and Sizing Guidelines

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

Siemens BACnet Programmable TEC Unit Conditioner Controller

PXC Compact Series Technical Reference Manual

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Siemens BACnet Programmable TEC Unit Vent Controller

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

TX-I/O Product Range. Features. Description. Technical Specification Sheet Document No January 24, 2007

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

BT300 HVAC Drives Electronic Bypass (E-Bypass) Options

BACnet. b3810 Series Local Controllers

Andover ContinuumTM. b3850 Series Terminal Controllers

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

BACnet Terminal Box (VAV) Controller

TC Compact Series Owner's Manual

TAC Xenta 301. Controller, Freely Programmable

Dual Duct Controller - One Air Velocity

PXC Compact Series Owner's Manual

Siemens BACnet VAV Actuator

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Andover ContinuumTM Infinet II

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Johnson Controls N2 Master Driver on the PXC Series Platform

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

FX-PCX Expansion Input/Output Modules Catalog Page Code No. LIT Issued April 17, 2015

BACnet. b3867 Terminal Controllers

TX-I/O Product Range. Features. Description. Document No January 24, 2007

oom Pressurization Con

IQ21x Series Controllers

Andover ContinuumTM Infinet II

BACnet Driver on the TC Series Platform

Onboard Inputs and Outputs. Remote User Interface. Integral LCD User Interface

BACnet Controller for General-purpose Building Applications

PXC Compact Series for BACnet Networks

FX Input/Output (I/O) Modules XM07 and XM14

Specification Sheet For electronically commutated motors

Power Open Processor/Open Processor

Power Modular Equipment Controller for BACnet Networks

FEC - FAC. Metasys controllers. Complex BAS Programmable controllers. Catalog Page. Field Equipment Controllers

clarity 3 Programmable Controller

ECB-300 Series BACnet B-AAC 18-Point Programmable Controllers

BT300 HVAC Drives. Designed for HVAC. Description. Technical Specification Sheet Document No March 4, 2013

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

SED2 VFD NEMA Type 3R Bypass/Air Conditioner

BACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

Input/Output Module (IOM) Series Catalog Page

Siemens TEC Extended I/O Controller

DX-9100 Digital Controller, Version 2

DS October MAXIM 1010 Controller

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Datasheet. ECB-600 and ECx-400 Series. ECB-600 & ECx-400. Overview. Applications. Features & Benefits.

Modbus 250 Driver on the PXC Series Platform

NAE. Metasys. BAS network automation Supervisory controllers. Network Automation Engine

PEAK TM. PEAK TM controllers. Mid-Market BAS Smart equipment controllers. HVAC/R controllers

TEC Heat Pump Multi-Stage Controller. Control Applications. Accessories. Product Description. Product Numbers. Warning/Caution Notation

Network Control Engine Catalog Page

DS Type: MAXIM III Controller

MS/TP Point Pickup Module Owner's Manual

DS December Omni BEMS Controller

Web server. Simplified.

TEC Unit Conditioner Controller

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

Master Panel. Specifications. Document No. TS-2010 February 15, Product Description. Sample Specification

Smart Equipment Controls (SEC)

lighting control. Each controller switches up to 48 high voltage, 20-amp lighting circuits, using

Advanced Application Field Equipment Controller (FAC) Catalog Page

Andover ContinuumTM Infinet II

BACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation

BACnet/IP Web Interface

APOGEE Insight Advanced Workstation

ECB-203 Series BACnet B-ASC 14-Point Programmable Controllers

FX14 Field Controller

AIR HANDLING UNIT CONTROLS

VZ7000 Series. BACnet Commercial Zoning System

Datasheet. ECB-300 Series. 1/6. BACnet B-AAC 18-Point Programmable Controllers. Overview

TAC Xenta 121-FC Programmable Fan Coil Application

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

EXOcompact. Third generation freely programmable controllers

TM172PBG42R Modicon M172 Performance Blind 42 I/Os, Ethernet, Modbus

NIEx9. Metasys. BAS network automation Supervisory controllers. Network Integration Engine

Transcription:

Technical Specification Sheet Document No. 149-837 February 20, 2018 Compact Series Unitary Equipment Controller Figure 1. PXC Compact Series Unitary Equipment Controllers (PXC UEC-16/24). The PXC Compact Series Unitary Equipment Controller (Programmable Controller Compact) for BACnet networks is a high-performance Direct Digital Control (DDC) equipment controller, which is an integral part of the APOGEE Automation System. The controllers are classified as a BACnet Advanced Application Controller (B-AAC) with support for BACnet MS/TP protocol. The PXC Compact UEC Series offers integrated I/O based on state-of-the-art TX-I/O Technology, which provides superior flexibility of point and signal types, and makes it an optimal solution for Air Handling Unit (AHU) control. The Unitary Equipment Controller communicates with other field panels or workstations on a peer-to-peer Automation Level Network (ALN), or on the Field Level Network (FLN), and supports the following communication options: Native BACnet MS/TP on RS-485 Features BACnet Testing Laboratories (BTL) certified Classified as BACnet Advanced Application Controllers (B-AAC) using the BACnet MS/TP protocol for specific models. Sophisticated Adaptive Control, a closed loop control algorithm that auto-adjusts to compensate for load/seasonal changes. Message control for terminals, printers, pagers, and workstations. HMI RS-232 and USB port, which provides laptop connectivity for local operation and engineering. Extended battery backup of Real Time Clock. Auto Save and persistent database backup and restore within the controller. PXM10T and PXM10S support: Optional LCD Local user interface with HOA (Hand-off-auto) capability and point commanding and monitoring features. An extended temperature range for the control of rooftop devices. Compact Series Unitary Equipment Controller The PXC Unitary Equipment Controller (UEC) is an MS/TP device, that can be configured as a programmable, stand-alone device or as a networked device on the BACnet MS/TP ALN (Automation Level Network) or FLN (Field Level Network) device. Siemens Industry, Inc. Page 1 of 6

PXC UEC-16 The PXC UEC-16 provides control for 16 points, including 8 software-configurable universal points. Point count includes: 3 Universal Input (UI), 5 Universal I/O (U), 2 Digital Input (DI), 3 Analog Output (AOV), and 3 Digital Output (DO). PXC UEC-24 The PXC UEC-24 provides control for 24 points, including 16 software-configurable universal points. Point count includes: 3 Universal Input (UI), 9 Universal I/O (U), 4 Super Universal I/O (X), 3 Analog Output (AOV), 5 Digital Output (DO). Extended Temperature Operation The PXC Compact UEC "R" models support extended temperature operation, allowing for rooftop installations. Hardware The PXC Compact Series consists of the following major components: Input/Output Points Power Supply Controller Processor Input/Output Points The PXC Compact input/output points perform A/D or D/A conversion, signal processing, point command output, and communication with the controller processor. The terminal blocks are removable for easy termination of field wiring. The Universal and Super Universal points leverage TX-I/O Technology from Siemens Building Technologies to configure an extensive variety of point types. Universal Input (UI) and Universal Input/Output (U) points are software-selectable to be: 0-10V input 4-20 ma input Digital Input Pulse Accumulator inputs 1K Ni RTD @ 32 F (Siemens, Johnson Controls, DIN Standard) 1K Pt RTD (375 or 385 alpha) @ 32 F 10K NTC Thermistor (Type 2 and Type 3) @ 77 F 100K NTC Thermistor (Type 2) @ 77 F 0-10V Analog Output (Universal Input/Output (U) points only) Super Universal (X) points are softwareselectable to be: 0-10V input 4-20 ma input Digital Input Pulse Accumulator inputs 1K Ni RTD @ 32 F (Siemens, Johnson Controls, DIN Standard) 1K Pt RTD (375 or 385 alpha) @ 32 F 10K NTC Thermistor (Type 2 and Type 3) @ 77 F 100K NTC Thermistor (Type 2) @ 77 F 0-10V Analog Output 4-20 ma Analog Output Digital Output (using external relay) Digital Output (DO) points are 110/220V 4 Amp (resistive) Form C relays; LEDs indicate the status of each point. All PXC Compact Series models support 0-10 Vdc Analog Output circuits. The Super Universal points may be defined as either 0-10 Vdc or 4-20 ma Analog Output circuits. Power Supply The 24 volt DC power supply provides regulated power to the input/output points and active sensors. The power supply is internal to the PXC Compact housing, eliminating the need for external power supply and simplifying installation and troubleshooting. The power supply works with the processor to ensure smooth power up and power down sequences for the equipment controlled by the I/O points, even through brownout conditions. Controller Processor The Unitary Equipment Controller includes a microprocessor-based multi-tasking platform for program execution and communications with the I/O points and with other UECs and field panels. Page 2 of 6 Siemens Industry, Inc.

A Human Machine Interface (HMI) port, with a quick-connect phone jack (RJ-45), uses RS-232 protocol to support operator devices (such as a local user interface or simple CRT terminal), and a phone modem for dial-in service capability. A USB Device port supports a generic serial interface for an HMI or Tool connection. The USB Device port does not support firmware flash upgrades. The program and database information stored in the UEC RAM memory is battery-backed. This eliminates the need for time-consuming program and database re-entry in the event of an extended power failure. The firmware, which includes the operating system, is stored in non-volatile flash ROM memory; this enables firmware upgrades in the field. Brownout protection and power recovery circuitry protect the controller board from power fluctuations. LEDs provide instant visual indication of overall operation, network communication, and low battery warning. Programmable Control with Application Flexibility The PXC Compact Series of high performance controllers provides complete flexibility, which allows the owner to customize each controller with the exact program for the application. The control program for each UEC is customized to exactly match the application. Proven Powers Process Control Language (PPCL), a text-based programming structure like BASIC, provides direct digital control and energy management sequences to precisely control equipment and optimize energy usage. Global Information Access The HMI port supports operator devices, such as a local user interface or simple CRT terminal. Devices connected to the operator terminal port gain global information access. Multiple Operator Access Multiple operators can access the network simultaneously. Multiple operator access ensures that alarms are reported to an alarm printer while an operator accesses information from a local terminal. Multiple operators may also access the controller through concurrent Telnet sessions and/or local operator terminal ports. Menu Prompted, English Language Operator Interface The UEC includes a simple, yet powerful, menudriven English Language Operator Interface that provides, among other things: Point monitoring and display Point commanding Historical trend collection and display for multiple points Event scheduling Program editing and modification via Powers Process Control Language (PPCL) Alarm reporting and acknowledgment Continual display of dynamic information Built-in Direct Digital Control Routines The UEC provides stand-alone Direct Digital Control (DDC) to deliver precise HVAC control and comprehensive information about system operation. It receives information from sensors in the building, processes the information, and directly controls the equipment. The following functions are available in the UEC: Adaptive Control, an auto-adjusting closed loop control algorithm, which provides more efficient, adaptive, robust, fast, and stable control than the traditional PID control algorithm. It is superior in terms of response time and holding steady state, and at minimizing error, oscillations, and actuator repositioning. Closed Loop Proportional, Integral and Derivative (PID) control. Logical sequencing. Alarm detection and reporting. Reset schedules. Built-in Energy Management Applications The following applications are programmed in the Unitary Equipment Controller and require simple parameter input for implementation: Automatic Daylight Saving Time switchover Siemens Industry, Inc. Page 3 of 6

Calendar-based scheduling Duty cycling Economizer control Equipment scheduling, optimization and sequencing Event scheduling Holiday scheduling Night setback control Peak Demand Limiting (PDL) Temperature-compensated duty cycling Temporary schedule override BACnet UEC Specifications Dimensions (L W D) PXC Unitary Equipment Controller, 16 point, BACnet MS/TP PXC Unitary Equipment Controller, 24 point, BACnet MS/TP 10.7" 5.9" 2.45" (272 mm 150 mm 62 mm) 10.7" 5.9" 2.45" (272 mm 150 mm 62 mm) Processor, Battery, and Memory Processor and Clock Speed Memory Battery backup of SDRAM (field replaceable) Battery backup of Real Time Clock Freescale MPC852T, 100 MHz 24 MB (16 MB SDRAM, 8 MB Flash ROM) AA (LR6) 1.5 Volt Alkaline (non-rechargeable) 180 days (accumulated) Rooftop (Extended Temperature) Models: 330 days (accumulated) AA (LR6) 3.6 Volt Lithium (non-rechargeable) 10 years (32 F to 122 F (0 C to 50 C)) Coin cell (BR2032) 3 Volt lithium Rooftop (Extended Temperature) Models 18 months Communication A/D Resolution (analog in) D/A Resolution (analog out) BACnet MS/TP Automation Level Network (ALN) BACnet MS/TP Field Level Network (FLN) Human-Machine Interface (HMI) USB Device port (for non-smoke control applications only) Prior to June 2013 16 bits 10 bits 9600 bps to 115.2 Kbps, up to 10 nodes per MS/TP ALN 9600 bps to 115.2 Kbps RS-232 compliant, 1200 bps to 115.2 Kbps USB 1.1 (12 Mbps) and 2.0 (480 Mbps), Type B female connector. Self-powered, does not use or supply USB power. USB 1.0 (1.5 Mbps) and 1.1 (12 Mbps) Electrical Power Requirements 24 Vac ±20% input @ 50/60 Hz Power Consumption (Maximum) 20 VA @ 24 Vac A/D Resolution (analog in) 16 bits D/A Resolution (analog out) 10 bits AC Power and Digital Outputs NEC Class 1 Power Limited Communication and all other I/O NEC Class 2 Page 4 of 6 Siemens Industry, Inc.

Electrical Digital Output Analog Outputs Universal Inputs (UI) and Universal Inputs/Outputs (U) Analog Inputs Voltage (0-10 Vdc) Current (4-20 ma) 1K Ni RTD @ 32 F (Siemens, JCI, DIN Ni 1K) 1K Pt RTD (375 or 385 alpha) @ 32 F 10K NTC Type 2 or Type 3 Thermistor 100K NTC Type 2 Thermistor Class 1 Relay, Form C (NO and NC contacts) Voltage (0-10 Vdc) Digital Inputs Pulse Accumulator Contact Closure Sensing Dry Contact/Potential Free inputs only Digital Input (10 ms settling time) Supports counter inputs up to 20 Hz, minimum pulse duration 20 ms (open or closed) Super Universal (X) Analog Outputs 0 to 10 Vdc @ 1 ma max Analog Inputs Voltage (0-10 Vdc) Current (4-20 ma) 1K Ni RTD @ 32 F (Siemens, JCI, DIN Ni 1K) 1K Pt RTD (375 or 385 alpha) @ 32 F 10K NTC Type 2 or Type 3 Thermistor 100K NTC Type 2 Thermistor Digital Inputs Pulse Accumulator Contact Closure Sensing Dry Contact/Potential Free inputs only Digital Input (10 ms settling time) Supports counter inputs up to 20 Hz, minimum pulse duration 20 ms (open or closed) Analog Outputs 0 to 10 Vdc @ 1 ma max 0 to 20 ma @ 650 Ω max Digital Output 0 to 24 Vdc, 22 ma max. (using external relay) Ambient Conditions Shipping & Storage Operating Temperature Operating temperature with rooftop (extended temperature) option Relative Humidity Mounting Surface -13 F to 158 F (-25 C to 70 C) 32 F to 122 F (0 C to 50 C) Operate in a dry location, which is protected from exposure to salt spray or other corrosive elements. Exposure to flammable or explosive vapors must be prevented. -40 F to 158 F (-40 C to 70 C) 5 to 95% rh non-condensing Direct equipment mount, building wall, or structural member CE Compliance Must be installed inside a metal enclosure rated at IP20 minimum Agency Listings UL UL916 PAZX UL916 PAZX7 Siemens Industry, Inc. Page 5 of 6

Agency Listings Agency Compliance OSHPD Seismic Certification Ordering Information PXC Compact Series FCC Compliance CFR47 Part 15, Subpart B, Class B Australian EMC Framework European EMC Directive (CE) European Low Voltage Directive (LVD) BACnet Testing Laboratories (BTL) Certified RoHS Compliant Product meets OSHPD Special Seismic Preapproval certification (OSH-0217-10) under California Building Code 2010 (CBC2010) and International Building Code 2009 (IBC2009) when installed within the following Siemens enclosure part numbers: PXA-ENC18, PXA- ENC19, or PXA-ENC34. Part Number PXC16.3-UCM.A PXC16.3-UCMR.A PXC24.3-UCM.A PXC24.3-UCMR.A PXC Unitary Equipment Controller, 16 point, BACnet MS/TP PXC Unitary Equipment Controller, 16 point, BACnet MS/TP, Rooftop Model PXC Unitary Equipment Controller, 24 point, BACnet MS/TP PXC Unitary Equipment Controller, 24 point, BACnet MS/TP, Rooftop Model Accessories Product Number PXM10S PXM10T PXA-HMI.CABLEP5 Controller mounted Operator Display module with point monitor and optional blue backlight Controller mounted Operator Display module Serial cable required for PXM10T/S connection to non-rooftop variants of the 16-point and 24-point Compact Series (pack of 5) Service Boxes and Enclosures Product Number PXA-SB115V192VA PXA-SB115V384VA PXA-SB230V192VA PXA-SB230V384VA PXA-ENC18 PXA-ENC19 PXA-ENC34 PX Series Service Box 115V, 24 Vac, 50/60 Hz, 192 VA PX Series Service Box 115V, 24 Vac, 50/60 Hz, 384 VA PX Series Service Box 230V, 24 Vac, 50/60 Hz, 192 VA PX Series Service Box 230V, 24 Vac, 50/60 Hz, 384 VA 18" Enclosure (Utility Cabinet) (UL Listed NEMA Type 1 Enclosure) 19 Enclosure (UL Listed NEMA Type 1 Enclosure) 34 Enclosure (UL Listed NEMA Type 1 Enclosure) Disposal The devices are considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage. Dispose of the devices through channels provided for this purpose. Comply with all local and currently applicable laws and regulations. Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. APOGEE and Insight are registered trademarks of Siemens Industry, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. 2018 Siemens Industry, Inc. Siemens Industry, Inc. Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 USA Tel. 1 + 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com. Document No. 149-837 Printed in the USA Page 6 of 6