PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

Similar documents
PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

PGR-3200 MANUAL INSULATION MONITOR

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

PGR-2601 MANUAL DC GROUND-FAULT RELAY

SE-701 MANUAL GROUND-FAULT MONITOR

SE-703 MANUAL EARTH-LEAKAGE MONITOR

SE-601 MANUAL DC GROUND-FAULT MONITOR

PGM-8325 MANUAL NEUTRAL GROUNDING MONITOR

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

PGM-8134 MANUAL GROUND CONTINUITY MONITOR

SB6100 MANUAL INDUSTRIAL SHOCK-BLOCK

EL731 PROFIBUS INTERFACE

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

STBEHC3020KC counter kit STB - 1 CH Hz - 2 I

PRODUCT SPECIFICATION. PC Board Relays. Series.

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

Zelio Control-modular measurement and control relays 1

CompactBlock Guard I/O EtherNet/IP Safety Modules

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

ZBRN1 access point- 2 RJ V AC/DC-4 displays-5 LEDs-Eth-Modbus-wireless radio

02/11/2015

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

RM35TF V AC

PLT. Breaker-based transfer switch open, closed or soft transition amps. Specification sheet

CurrentWatch Current Sensors. EGF Series Ground Fault Sensors. Ground Fault Sensors with Solid-State or Mechanical Relay Outputs.

Section 4 Ground-Fault Protection Devices

Conductive Level Controller

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

RM4TR31 three-phase network control relay RM4-T - range V

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

em4 Accessories Digital expansions

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

BUFFER MODULE SHORT-FORM DATA MARKINGS

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

PM Series Power Meter

EL731 DEVICENET INTERFACE

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

PHOENIX CONTACT Features

PROCESS AUTOMATION. MANUAL Z-System. Zener Barriers ISO9001

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

ZBRN1 access point- 2 RJ V AC/DC-4 displays-5 LEDs-Eth-Modbus-wireless radio

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

ISOMETER isoev425/isoev425hc with coupling device AGH420

Zener Barriers Bulletin 937Z

RM4TA32 three-phase network control relay RM4-T - range V

IES User Manual. 8 FE + 1 MM SC Unmanaged Switch -40 to 75, DIN-rail. v

USB-PDISO8 Specifications

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

ZBRN1. Main. Device short name

XPSMCMDI Input expansion module with screw term

OTB1C0DM9LP I/O distributed module OTB - CANopen bus m

CSI 6300 SIS Overview

24/48/120 VAC Interface Card Instruction Manual

T M. IRDH375 Series. Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems. Technical Bulletin NAE / 09.

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

24973 Circuit Breaker MINIATURE CIRCUIT BREAKER, 440VAC, 10A, CIRCUIT BREAKER TYPE: STANDARD

D64RP18 INSTRUCTION MANUAL N.O. N.C V AC/DC TEST/ RESET

Switching Power Supply S8E1. Ordering Information. Compact and Economical Switching Power Supply

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

PanelView Plus/VersaView CE Terminals and Display Modules

RM17UB3. Price* : USD

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

Quick Start Guide TS A

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

100% electricity. Automatic transfer switch controllers ATL series

LXM32SD18M2 motion servo drive - Lexium 32-single phase supply voltage 115/230V - 0.5/1.kW

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

SE-330 MANUAL NEUTRAL-GROUNDING-RESISTOR MONITOR

OTB1C0DM9LP. Main , length of segment <= 185 m , length of segment <= 160 m. 3.4 kohm for I8...I kohm I0...I1 5.7 kohm I6...

XPSMCMCO0000EM Modbus TCPIP diagnostic expansion module with screw term

MODEL: R1M-A1. PC Recorders R1M Series. SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.)

OVERLOAD RELAYS POWER & ACTUATION PROVEN. series

LXM28AU07M3X motion servo drive - Lexium 28 - single and three phase V W

CK3W-PD048 CSM_CK3W-PD048_DS_E_DITA_1_2

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

Ultra Slim Relays 24

1492-SP Supplementary Protectors

SR2B201FU compact smart relay Zelio Logic - 20 I O V AC - clock - display

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

Contact protection relay

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

SE-134C MANUAL GROUND-FAULT GROUND-CHECK MONITOR

Safety Relay Unit (I/O Unit Type)

User Manual - Canada. TPS3 03 DC For DC Photovoltaic Applications. Surge Protective Device

Transcription:

Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY REVISION 3-B-041318 Copyright 2018 by Littelfuse, Inc. All rights reserved. Document Number: PM-1030-EN Printed in Canada.

PGR-4300 Generator Ground-Fault Relay Page i This page intentionally left blank.

PGR-4300 Generator Ground-Fault Relay Page ii SECTION TABLE OF CONTENTS PAGE FIGURE LIST OF FIGURES PAGE 1 General... 1 2 Operation... 1 2.1 System Selection... 1 2.2 Front-Panel Controls... 1 2.2.1 Ground-Fault Trip Level... 1 2.2.2 Ground-Fault Trip Time... 1 2.2.3 Reset... 1 2.2.4 Test... 1 2.3 Front-Panel Indication... 1 2.3.1 Power... 1 2.3.2 > I... 1 2.3.3 N-G... 1 2.4 Analog Output... 3 2.5 Remote Reset... 3 2.6 Relay Operating Mode... 3 3 Installation... 3 4 Technical Specifications... 7 5 Ordering Information... 7 6 Performance Test... 8 Appendix A PGR-4300 Revision History... 9 1 PGR-4300 Outline and Mounting Details... 2 2 Three-Pole Transfer Switch Typical Connection Diagram... 3 3 Four-Pole Transfer Switch Typical Connection Diagram... 4 4 PGA-0500 Analog Percent Current Meter... 4 5 PMA-55 Panel-Mount Adapter... 5 6 PMA-60 Panel-Mount Adapter... 6 7 PGR-4300 Performance Test Circuit... 8 TABLE LIST OF TABLES PAGE 1 Ground-Fault-Test Record... 8 DISCLAIMER Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.

PGR-4300 Generator Ground-Fault Relay Page iii This page intentionally left blank.

PGR-4300 Generator Ground-Fault Relay Page 1 1. GENERAL The PGR-4300 Generator Ground-Fault Relay provides a simple method for detecting a ground-fault condition on a generator-supplied system, without the need for a current transformer. It continuously monitors for ground-fault current and neutral-to-ground continuity. It can be applied on a three phase system with a three-pole or four-pole transfer switch and can be used in a dedicated generator application. In a three-pole transfer-switch application, the generator neutral and system neutral are connected to ground at the service entrance. The connection between the generator neutral and service-entrance ground is assumed to have a resistance of 2 mω and voltage across this conductor is measured to calculate ground-fault current. See Fig. 2. The selection of a neutral-bonding conductor can be made using NEC 250.102(D) and 250.122, and calculating the conductor length needed for a 2 mω resistance. In a four-pole transfer-switch application the ground connection to earth is at the generator. See Fig. 3. The resistance of the bonding cable between the generator neutral and ground is assumed to have a resistance of 0.2 mω. The voltage across this conductor is measured to calculate ground-fault current. A 0.9 m (3 ) length of AWG 3/0 copper cable is recommended per NEC 250.102(C). In a dedicated generator application, to ensure proper operation of the PGR-4300 there can be only one ground connection to earth. If the earth connection is at the generator, configure the PGR-4300 as a four-pole system. If the earth connection is at the load or service entrance, configure as a three-pole system. The PGR-4300 has one output relay with normally open / normally closed contacts for use in a control circuit. Additional features include LED trip and power indication, front-panel and remote reset, 0- to 1-mA analog output, a level-selector switch, and a trip-time setting. An epoxy-filled enclosure provides the PGR-4300 protection against vibration. The trip level of the ground-fault circuit is switch selectable from 100 to 1,200 A. Trip time is selectable from 0 to 1.0 s. 2. OPERATION 2.1 SYSTEM SELECTION For a four-pole system, connect terminals 11 and 12. For a three-pole system, leave terminals 11 and 12 open. 2.2 FRONT-PANEL CONTROLS 2.2.1 GROUND-FAULT TRIP LEVEL The I selector switch is used to set the ground-fault trip level from 100 to 1,200 A. Unbalanced single-phase currents returning through the bonding conductor will appear as ground-fault current. To avoid nuisance tripping, set the trip-level setting above these currents. 2.2.2 GROUND-FAULT TRIP TIME The PGR-4300 has a definite-time trip characteristic. In tripping systems, the TIME DELAY selector is used to set the ground-fault trip time for coordination with downstream ground-fault devices. Trip time is selectable from 0 to 1.0 s. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault. 2.2.3 RESET The front-panel RESET button is used to reset latching trips. When remote-reset terminals 4 and 5 are connected, a trip remains latched until the RESET button is pressed or the remote-reset terminals are opened. Cycling the supply voltage will also reset the PGR-4300. If the remote-reset terminals are not connected, the PGR-4300 operates in the non-latching mode and a trip will reset when the fault is removed. 2.2.4 TEST The TEST button is used to test the ground-fault circuit, the indication, and the output relay. When the TEST button is pressed, the circuit will trip, the >ΔI LED will light, the output relay will energize, and the analog output will indicate full scale (1 ma). 2.3 FRONT-PANEL INDICATION 2.3.1 POWER The green LED labelled PWR indicates the presence of supply voltage. 2.3.2 > I The red LED labelled > I indicates a ground-fault trip. It also lights when the neutral connection is open. 2.3.3 N-G The red LED labelled N-G indicates a neutral-to-ground trip. When continuity between the generator neutral and ground is broken, the N-G and > I LED s will be on and the output relay will be energized.

FIGURE 1. PGR-4300 Outline and Mounting Details. PGR-4300 Generator Ground-Fault Relay Page 2

PGR-4300 Generator Ground-Fault Relay Page 3 2.4 ANALOG OUTPUT A non-isolated, 0- to 1-mA output (terminals 9 and 10) indicates ground-fault current. Full-scale corresponds to the ground-fault level setting. For example, if the ground-fault level setting is 300 A, then 1 ma output will be indicated when the measured current is 300 A. The output is linear between zero and full scale. See Figs. 2, 3 and 4 for PGA-0500 meter details. 2.5 REMOTE RESET Terminals 4 and 5 are used for remote reset. A normally closed contact switch is required to configure the PGR-4300 for latching operation. See Section 2.2.3 and Figs. 2 and 3. 2.6 RELAY OPERATING MODE The output relay operates in the non-fail-safe mode only; it energizes when a trip occurs. 3. INSTALLATION This ground-fault monitoring system consists of a PGR-4300 Generator Ground-Fault Relay connected as shown in Figs. 2 and 3. A PGR-4300 can be surface, DIN-rail, or panel mounted. Panel mounting requires a PMA-55 or PMA-60 Panel-Mount Adapter. See Figs. 1, 5, and 6. Use terminal 1 (L1) as the line terminal on ac systems or the positive terminal on dc systems. Use terminal 2 (L2/N) as the neutral terminal on ac systems or the negative terminal on dc systems. For a three-pole system, connect terminal 8 to the generator neutral, and terminal 6 to the local ground. See Fig. 2. For a four-pole system, connect terminals 11 and 12, connect terminal 8 to the generator neutral, and terminal 6 to the ground side of the bonding conductor. See Fig. 3. Use AWG 14 wire to make connections from the PGR-4300 to the bonding conductor, neutral and ground. NOTE: Mounting, terminal block connections and wiring must conform to applicable local electrical codes. Check all applicable codes prior to installation. FIGURE 2. Three-Pole Transfer Switch Typical Connection Diagram.

PGR-4300 Generator Ground-Fault Relay Page 4 FIGURE 3. Four-Pole Transfer Switch Typical Connection Diagram. FIGURE 4. PGA-0500 Analog Percent Current Meter.

FIGURE 5. PMA-55 Panel-Mount Adapter. PGR-4300 Generator Ground-Fault Relay Page 5

FIGURE 6. PMA-60 Panel-Mount Adapter. PGR-4300 Generator Ground-Fault Relay Page 6

PGR-4300 Generator Ground-Fault Relay Page 7 4. TECHNICAL SPECIFICATIONS Supply: 12 Option... 3 W, 12 Vdc, (+16, -25%) 24 Option... 3 W, 24 Vdc, (+37, -25%) 120 Option... 4 VA, 120 Vac, (+10, -15%) 50/60 Hz Trip-Level Settings... 100, 150, 200, 250, 300, 450, 600, 750, 800, and 1,200 A Trip-Time Settings... 0 to 1.0 s Accuracies: Trip Level (1)... ±10% Trip Time (2)... 10% of Setting, 40 ms minimum Analog Output: Mode... % of Trip Level Range... 0 to 1 ma dc Reset... Front-Panel Button, Remote Momentary Open Contact Test... Front-Panel Button Output Relay: Contact Configuration... Form C Operating Mode... Non-Fail-Safe UL rating 5 A, 125 Vac Resistive Supplemental Contact Ratings: Carry Continuous... 5 A Trip Mode... Latching or Autoreset Terminals... Wire Clamping, 22 to 12 AWG (0.3 to 3.3 mm 2 ) Conductors Tightening Torque...0.40 N m (3.54 lbf in) Width... 55 mm (2.2 ) Depth... 115 mm (4.5 ) Shipping Weight... 0.45 kg (1 lb) Environment: Operating Temperature... -10 to 60 C (14 to 140 F) Storage Temperature... -40 to 80 C (-40 to 176 F) Humidity... 85% Non-Condensing Enclosure Rating... lp20 Altitude... 2,000 m (6,562 ft) maximum Overvoltage Category... II Pollution Degree... 2 Certification... UL Listed UL508 Industrial Control Equipment FCC NOTES: (1) Based on generator-neutral to service-entrance conductor resistance of 2 mω (three-pole transferswitch application) or 0.2 mω (four-pole transferswitch application). (2) At 3x trip-level setting. 5. ORDERING INFORMATION PGA-0500 Analog Percent Current Meter PMA-55 Panel-Mount Adapter, NEMA 1 PMA-60 Panel-Mount Adapter, NEMA 3, IP53 PMA-03 Adapter Plate, GEC/MCGG Consult factory for custom mounting adapters. Conductor Type... Copper, Solid or Stranded with Ferrules Conductor Rating... 60/75 C Vibration Protection... Fibreglass-reinforced Epoxy Dimensions: Height... 75 mm (3.0 )

PGR-4300 Generator Ground-Fault Relay Page 8 6. PERFORMANCE TEST Some jurisdictions require periodic ground-fault performance tests. A test record form is provided for recording the date and the result of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel. a) Evaluate the interconnected system in accordance with the overall equipment manufacturer s detailed instructions. b) Press the TEST and RESET buttons to ensure the monitor is functioning properly. c) Verify proper reaction of the device in response to a simulated ground-fault current. To simulate groundfault current, set up a voltage-divider circuit as shown in Fig. 7. Select 9 kω for R TEST resistance and do not connect terminals 11 and 12 for 3-pole systems. Select 99 kω for R TEST resistance and connect terminals 11 and 12 for 4-pole systems. For each leakage current setting (0, 6, 9), verify that the unit trips at each V TEST voltage shown within the selected trip time. Voltage V N represents the voltage at terminal 8 if the actual leakage current was flowing through the bonding cable between the generator neutral and ground; See Section 1. d) Record the date and the results of the test on the attached test-record form. TABLE 1. Ground-Fault-Test Record DATE TEST RESULTS Retain this record for the authority having jurisdiction. FIGURE 7. PGR-4300 Performance Test Circuit.

PGR-4300 Generator Ground-Fault Relay Page 9 MANUAL RELEASE DATE April 13, 2018 July 31, 2015 APPENDIX A PGR-4300 REVISION HISTORY MANUAL PRODUCT REVISION REVISION (REVISION NUMBER ON PRODUCT LABEL) 3-B-041318 3-A-073115 00 MANUAL REVISION HISTORY REVISION 3-B-041318 SECTION 4 Specifications updated. REVISION 3-A-073115 SECTION 2 Fig. 1 updated. SECTION 3 Fig. 6 updated. SECTION 7 Fig. 7 updated. APPENDIX A Revision history added. PRODUCT REVISION HISTORY PRODUCT REVISION 00 UL Certification.

PGR-4300 Generator Ground-Fault Relay Page 10 This page intentionally left blank.