Power module PM-E DC24V/8A RO SIMATIC. ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface. Properties.

Similar documents
Power module PM-E DC24V HF SIMATIC. ET 200S distributed I/O Power module PM-E DC24V HF (6ES7138-4CA60-0AB0) Preface. Properties.

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V (6ES7138-4CA50-0AB0) Preface. Properties 1. Parameters 2. Diagnostics 3.

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V/AC V (6ES7138-4CB11-0AB0) Preface. Properties 1. Parameters 2.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

ET 200S distributed I/O system 4DO DC24V/2A ST digital electronic module (6ES7132-4BD32-0AA0)

ET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0)

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3.

SIMATIC. ET 200S distributed I/O. 4 IQ-SENSE module (6ES7138-4GA00-0AB0) Preface. 4 IQ-SENSE module (6ES7138-4GA00-0AB0) Parameters 2.

SIMATIC. ET 200S distributed I/O 2AO U HF analog electronic module (6ES7135-4LB02-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200S distributed I/O 2AO U ST analog electronic module (6ES7135-4FB01-0AB0) Preface. Properties 1. Parameters 2.

DI 8x24VDC ST digital input module SIMATIC. ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Preface. Documentation guide

ST (6ES7132-6FD00-0BB1)

Use with 0 to 70 C ambient. temperature SIMATIC. Process Control System PCS 7 Use with 0 to 70 C ambient temperature. Preface 1. Product combination 2

IO-Link Master (6ES7147-4JD00-0AB0) SIMATIC. ET 200pro IO-Link Master (6ES7147-4JD00-0AB0) Preface. Documentation guide. Product overview.

Siemens Drives & PLCs

Product Information Mixed. Configuration ET 200SP / ET 200AL SIMATIC. ET 200SP Product Information Mixed Configuration ET 200SP / ET 200AL.

SIMATIC. Digital Input Module SM DI, DC24V - Sinking/Sourcing. Product information. Product Information

BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) SIMATIC. ET 200SP BaseUnits. Preface. Guide to the documentation 1. Product overview 2

SIMATIC. ET 200SP DQ 4x VAC/2A ST digital output module (6ES7132-6FD00-0BB1) Preface. Guide to documentation. Product overview.

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of "Inter Project Engineering"

Digital output module. DQ 16x24VDC/0.5A BA (6ES7522-1BH10-0AA0) SIMATIC

S7-300 Getting Started - Commissioning a CPU 31xC: Closed-loop control

Readme SiVArc V14 SP1 Update 6

PROFIenergy product information SIMATIC. ET 200SP PROFIenergy product information. PROFIenergy 1. Product Information 12/2015 A5E AH

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library 1. Deleting program block Main [OB1]

Technological Functions SIMATIC. ET 200S Technological Functions. Preface 1. 1Count24V. 1Count5V 3 1SSI 4 2PULSE. Operating Instructions

Class documentation. COMOSKDictionary COMOS. Platform Class documentation COMOSKDictionary. Trademarks. General. KDictionary. Programming Manual

Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) SIMATIC. S7-1500/ET 200MP Power supply module PS 25W 24VDC (6ES7505-0KA00-0AB0) Preface

Digital input module. DI 16x24VDC 8xM12 6ES7141-5AH00-0BA0) SIMATIC. ET 200AL Digital input module DI 16x24VDC 8xM12 6ES7141-5AH00-0BA0) Preface

Key Panels Library SIMATIC HMI. Key Panels Library. Preface 1. Installation of Key Panels Library. Working with the Key Panels Library

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC

Getting Started - Startdrive. Startdrive SINAMICS. Introduction 1. Connecting the drive unit to the PC. Creating a project 3

ST (6ES7522-5HF00-0AB0)

Cycle and response times SIMATIC. S Cycle and response times. Preface. Documentation guide. Program processing 2. Cyclic program processing 3

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1) SIMATIC. ET 200SP Analog Output Module AQ 4xU/I ST (6ES7135-6HD00-0BA1) Preface

COMOS. Platform Class documentation RevisionMaster_dll. Class: RevisionInfo 1. Class: RevisionMaster 2. Programming Manual

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

SIMATIC. Process Control System PCS 7 VT Readme V8.2 (online) Security information 1. Overview 2. Notes on Installation 3. Notes on usage 4.

SIMATIC. Process Control System PCS 7 PCS 7 system documentation - Readme V8.0 SP2 (Update 1) Options for Accessing Documentation 1

SIMATIC. ET 200SP Digital output module DI 8x24VDC SRC BA (6ES7131-6BF61-0AA0) Preface. Documentation guide. Product overview.

CM PtP RS422/485 BA communication. module (6ES7540 1AB00 0AA0) SIMATIC. S7-1500/ET 200MP CM PtP RS422/485 BA communication module (6ES7540 1AB00 0AA0)

Industrial Controls. Motor management and control devices SIMOCODE pro. Introduction 1. Configuring a reversing starter. List of abbreviations

SIMATIC. S7/HMI SIMATIC Automation Tool V3.1 SP1 product information. SIMATIC Automation Tool features 1. Known problems. Product Information

Digital output module. DQ 16x230VAC/2A ST Relay (6ES7522-5HH00-0AB0) SIMATIC

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

RF-MANAGER simulator SIMATIC. RFID-Systems RF-MANAGER simulator. Simulating projects. Compact Operating Instructions 06/2010 A5E

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

ST (6ES7522-1BH00-0AB0)

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

MindSphere. Visual Explorer. Introduction. User roles for "Visual Explorer" Connecting "Visual Explorer" to MindSphere data. Creating Visualizations

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

SIMATIC. S7-1500/ET 200MP DI 16x230VAC BA Digital Input Module (6ES7521-1FH00-0AA0) Preface. Documentation guide. Product overview.

SIMATIC. S7-1500/ET 200MP Digital input module DI 16x24VDC BA (6ES7521-1BH10-0AA0) Preface. Documentation guide. Product overview.

SIMATIC. Communications processor CP 340 first commissioning steps. Getting Started 04/2005 A5E

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

SIMATIC. S7-1500/ET 200MP Technology Module TM NPU (6ES7556-1AA00-0AB0) Preface. Documentation guide. Product overview. Wiring

SIMATIC. ET 200S distributed I/O IM151-1 HIGH FEATURE interface module (6ES7151-1BA02-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200SP Digital input module DI 8x24VDC BA (6ES7131-6BF01-0AA0) Preface. Documentation guide 1. Product overview 2.

Digital output module. DQ 4x24VDC/2A ST (6ES7132-6BD20-0BA0) SIMATIC. ET 200SP Digital output module DQ 4x24VDC/2A ST (6ES7132-6BD20-0BA0) Preface

Analog output module AQ 2xI ST (6ES7135-6GB00-0BA1) SIMATIC. ET 200SP Analog output module AQ 2xI ST (6ES7135-6GB00-0BA1) Preface. Documentation guide

SIMATIC. Modifying the System during Operation via CiR. Requirements and Overview 1. CiR Objects and CiR Modules. User Interface 3

Digital input module. DI 8x24VDC HF (6ES7131-6BF00-0CA0) SIMATIC. ET 200SP Digital input module DI 8x24VDC HF (6ES7131-6BF00-0CA0) Preface

Industrial Controls. SIMOCODE pro SIMOCODE pro PCS 7 Library. Preface. Security information. Product specific security. information.

Performance data abgn SCALANCE W770/W730 SIMATIC NET. Industrial Wireless LAN Performance data abgn SCALANCE W770/W730.

Class: DocumentManager 1 COMOS. Platform Class documentation DocumentManager_dll. Programming Manual 03/2017 V10.2.

SIMATIC. Function modules FM 351 First Steps in Commissioning. Purpose of the Getting Started. Requirements 2

SIMATIC. ET 200SP Open Controller Product information on CPU 1515SP PC. Preface. Product Information. Technical update. Technical specifications 3

Validity 1. Improvements in STEP 7 2. Improvements in WinCC 3 SIMATIC. Readme. Readme

SIMATIC. Industrial software WinAC RTX F Introduction 1. Selecting suitable hardware 2. Installing/removing the WinAC RTX F 2009 software

Performance data abgn PCIe Minicard MPCIE-R1-ABGN-U3 SIMATIC NET

Configuration limits for products of the SIMATIC NET PC Software V8.1 SIMATIC NET

Digital output module. DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0) SIMATIC. ET 200SP Digital output module DQ 16x24VDC/0.5A ST (6ES7132-6BH00-0BA0)

SIMATIC. Process Control System PCS 7 Configuration McAfee Endpoint Security Security information 1. Preface 2.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Optional package printer driver V1.4

Block Library Motor Starter SIRIUS for SIMATIC PCS 7

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

SIMATIC Ident RFID systems MDS D423 Compact Operating Instructions

Digital output module. DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) SIMATIC. ET 200SP Digital output module DQ 8x24VDC/0.5A HF (6ES7132-6BF00-0CA0) Preface

Setting up securityglobal FW Rulesets SIMATIC NET. Industrial Ethernet Security Setting up security. Preface. Firewall in standard mode

ET 200pro Distributed I/O System - Fail- Safe Modules SIMATIC

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

SIMATIC. Process Control System PCS 7 PCS 7 Documentation (V8.1) Options for Accessing Documentation 1. Documentation for the Planning Phase 2

Siemens Spares. Setting up security in STEP 7. Professional SIMATIC NET. Industrial Ethernet Security Setting up security in STEP 7 Professional

Manual Edition 03/2010

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E

Sample project Filling Station SIMATIC. STEP 7 Professional / WinCC Advanced V11 for Sample project Filling Station. Overview of the Getting.

Siemens Industrial SIMATIC. Process Control System PCS 7 Configuration Trend Micro OfficeScan Server XG. Security information 1.

SIMATIC. Distributed I/O System Fail-Safe Engineering ET 200S Distributed I/O System - Fail-Safe Modules. Preface. Product Overview 1.

SIMATIC IPC Wizard for. Widescreen devices with multitouch SIMATIC. Industrial PC SIMATIC IPC Wizard for. Preface.

SITOP UPS1600 under STEP 7 V5. SITOP UPS1600 under STEP 7 V5. Introduction. Safety notes. Description 3. Assigning the IP address

S7-300 Programmable Controller

SIMATIC. ET 200SP BaseUnits (6ES7193-6BP.../3RK1908-0AP00 ) Preface. Guide to the documentation. New properties. Product overview 3

SIMATIC S Analog output module AQ 4xU/I ST (6ES7532-5HD00-0AB0) Manual. Answers for industry.

party software COMOS Platform Third-party software Trademarks 1 Requirements for the system environment Third-party software releases Operating Manual

SIMATIC. Process Control System PCS 7 Trend Micro OfficeScan (V8.0; V8.0 SP1) Configuration. Using virus scanners 1.

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

Transcription:

Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) SIMATIC ET 200S distributed I/O Power module PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Preface Properties 1 Parameters 2 Diagnostics 3 Configuring 4 Manual 06/2010 A5E02953719-01

Legal information Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed. Trademarks All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY A5E02953719-01 P 07/2010 Copyright Siemens AG 2010. Technical data subject to change

Preface Purpose of the manual This manual supplements the ET 200S Distributed I/O System Operating Instructions. General functions for the ET 200S are described in the ET 200S Distributed I/O System Operating Instructions (http://support.automation.siemens.com/ww/view/en/1144348). The information in this document along with the operating instructions enables you to commission the ET 200S. Basic knowledge requirements To understand these operating instructions you should have general knowledge of automation engineering. Scope of the manual This manual applies to this ET 200S module. It describes the components that are valid at the time of publication. Recycling and disposal Thanks to the fact that it is low in contaminants, this ET 200S module is recyclable. For environmentally compliant recycling and disposal of your electronic waste, please contact a company certified for the disposal of electronic waste. Additional support If you have any questions relating to the products described in this manual and do not find the answers in this document, please contact your local Siemens representative (http://www.siemens.com/automation/partners). A guide to the technical documentation for the various SIMATIC products and systems is available on the Internet. (http://www.siemens.com/simatic-docu). The online catalog and ordering systems are available on the Internet (http://www.siemens.com/automation/mall). Training center We offer courses to help you get started with the ET 200S and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in D - 90327, Nuremberg, Germany (http://www.siemens.com/sitrain). Manual, 06/2010, A5E02953719-01 3

Preface Technical Support You can contact Technical Support for all Industry Automation products by means of the Internet Web form for the Support Request (http://www.siemens.com/automation/csi_en_ww/support_request). Additional information about Siemens Technical Support is available on the Internet (http://www.siemens.com/automation/csi_en_ww/service). Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet (http://www.siemens.com/automation/csi_en_ww/support). There you will find: Our Newsletter, which constantly provides you with the latest information about your products. The right documentation for you using our Service & Support search engine. The bulletin board, a worldwide knowledge exchange for users and experts. Your local contact for Automation & Drives in our contact database. Information about on-site services, repairs, spare parts, and lots more. 4 Manual, 06/2010, A5E02953719-01

Table of contents Preface... 3 1 Properties... 7 1.1...7 1.2 Reduction of power consumption...12 2 Parameters... 15 2.1 Parameters for PM-E DC24V/8A RO...15 3 Diagnostics... 17 3.1 Diagnostics using LED display...17 3.2 Error types...18 4 Configuring... 19 4.1 Configuring the address space...19 Manual, 06/2010, A5E02953719-01 5

Table of contents 6 Manual, 06/2010, A5E02953719-01

Properties 1 1.1 Properties The PM-E DC24V/8A RO power module monitors the supply voltage for all electronic modules in the voltage group. The supply voltage is fed in by means of the TM-P terminal module. You can use all electronic modules except the 2DI AC120V ST, 2DI AC230V ST, and 2DO AC24..230V/1A in the voltage group of the PM-E DC24V/8A RO power module. Reduction of the energy consumption (during operational downtimes) by switching off the encoder and load supply of the voltage group of the power module (see chapter Reduction of energy consumption). (Page 12) The voltage group can be switched off by means of PROFIenergy commands on suitable interface modules (see Requirements for operation) or via the control byte in the process image output (PIQ). The current status of the power module is stored in the status byte in the process input image (PII). The update does not depend on a diagnostics release. Extended temperature range from 0 to 55 C with vertical installation. CAUTION If you do not adhere to the specified load voltage 24 VDC, you may risk creating dangerous plant conditions. The consequences may be damages to the ET 200S or minor injuries. This means you should only connect the specified load voltage of 24 VDC to the TM-P terminal module of the power module. The connected load voltage must correspond to the supply voltage of the electronic modules in the voltage group. Manual, 06/2010, A5E02953719-01 7

Properties 1.1 Requirements for operation It is possible to operate the PM-E DC24V/8A RO power module only using the following PROFINET interface modules and voltage group, which can be switched off, as of the order numbers specified. Interface module as of order number Firmware version (or higher) The voltage group can be switched off with PROFIenergy Control byte IM 151-3 PN 6ES7151-3AA23-0AB0 V7.0.0 IM 151-3 PN FO 6ES7151-3BB23-0AB0 V7.0.0 IM 151-3 PN HIGH FEATURE 6ES7151-3BA23-0AB0 V7.0.0 IM 151-3 PN HIGH SPEED 6ES7151-3BA60-0AB0 V3.0.0 IM 151-8 PN/DP CPU 6ES7151-8AB01-0AB0 V3.2.0 IM 151-8F PN/DP CPU 6ES7151-8FB01-0AB0 V3.2.0 Compatibility (spare part replacement for the interface modules listed above) You can use the PM-E DC24V RO power module as a replacement for the PM-E DC24V and PM-E DC24V HF. The following particularities apply in this case: The status byte is only present if you have parameterized the PM-E DC24V or PM-E DC24V HF with the suffix...s in HW Config. The control byte is not available: The PM-E DC24V/8A RO does not occupy any address space in the process image of the outputs. It is not possible to switch off the voltage group of the PM-E DC24V/8A RO in conjunction with the control byte. In case of spare part replacement, you can turn off the power module with PROFIenergy commands. Maximum current-carrying capacity of the PM-E DC24V/8A RO = 8A Maximum configuration per voltage group The number of modules that can be connected depends on the total current of all modules in a voltage group. This total must not exceed the maximum current carrying capacity. Address space of inputs/outputs Address space of inputs/outputs by selecting the following as an option (entries in HW- Config): Options Address space of the inputs Address space of the outputs "PM-E DC24V/8A RO" 1 --- --- "PM-E DC24V/8A RO S" 1 byte (status byte) 1 byte (control byte) 1 supports PROFIenergy 8 Manual, 06/2010, A5E02953719-01

Properties 1.1 General terminal assignment Note Terminals A4 and A8 are only available at specified terminal modules. Terminal assignment for PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Terminal Assignment Terminal Assignment Notes 2 L+ 6 L+ L+: Rated load voltage 24 VDC 3 M 7 M M: Chassis ground A4 AUX1 A8 AUX1 AUX1: Protective-conductor terminal or potential bus (freely usable up to 230 VAC) Usable terminal modules TM-P15C23-A1 (6ES7193-4CC30-0AA0) TM-P15S23-A1 (6ES7193-4CC20-0AA0) TM-P15N23-A1 (6ES7193-4CC70-0AA0) Usable terminal modules for PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) TM-P15C23-A0 (6ES7193-4CD30-0AA0) TM-P15S23-A0 (6ES7193-4CD20-0AA0) TM-P15N23-A0 (6ES7193-4CD70-0AA0) TM-P15C22-01 (6ES7193-4CE10-0AA0) TM-P15S22-01 (6ES7193-4CE00-0AA0) TM-P15N22-01 (6ES7193-4CE60-0AA0) Spring terminal Screw-type terminal Fast Connect Manual, 06/2010, A5E02953719-01 9

Properties 1.1 Block diagram Figure 1-1 Block diagram of the PM-E DC24V/8A RO power module 10 Manual, 06/2010, A5E02953719-01

Properties 1.1 Technical data of PM-E DC24V/8A RO (6ES7138-4CA80-0AB0) Dimensions and weight Dimension B (mm) 15 Weight Approx. 40 g Voltages, currents, potentials Rated load voltage 24 VDC Overvoltage protection No Protection with automatic circuit breakers Yes, tripping characteristic B, C Max. current-carrying capacity 8 A Minimum load current Short-circuit protection No Electrical isolation Between rated load voltage and backplane Yes bus Between the power modules Yes Insulation test voltage 500 VDC Current consumption From the load voltage L+ (no load) Max. 30 ma 1 Power dissipation of the module typ. 600 mw 1 Parameter length 3 bytes Status, interrupts, diagnostics Diagnostic function Yes Group error Red "SF" LED Terminal voltage monitoring Green LED "L+" Load voltage monitoring Green "PWR" LED Diagnostic information readable Yes 1 internal relay switched Additional information on the internal relay Internal relay Minimum load current 8 ma Switching frequency max. 0.3 Hz Mechanical service life 50 million switching cycles Electrical service life at the 24 VDC rated voltage 0.08 million switching cycles at 8 A 0.1 million switching cycles at 7 A 0.15 million switching cycles at 5 A 0.175 million switching cycles at 4 A 0.3 million switching cycles at 2 A 1.1 million switching cycles at 0.5 A Maximum switching capacity 240 W with ohmic load (power factor = 1) 170 W with inductive load (power factor = 0.4 L/R = 7 ms) Manual, 06/2010, A5E02953719-01 11

Properties 1.2 Reduction of power consumption 1.2 Reduction of power consumption Properties The PM-E DC24V/8A RO power module enables the voltage group to be switched off by an internal relay. All encoder and load supplies of the following electronic modules will be switched off in the voltage group. This step results in a reduction of the power consumption during operational downtimes. 12 Manual, 06/2010, A5E02953719-01

Properties 1.2 Reduction of power consumption Principle of operation The procedure and behavior when switching on/off the voltage group of the PM-E DC24V/8A RO is described in the following: Proced ure Voltage group (encoder and load supplies) Input module Output module Energy saving 1 activated Measuring Data output No 2 deactivated Encoder supply Load supply switched Yes switched off off Inputs zero current/voltage Outputs zero current/voltage 3 activated Measuring Data output No The voltage group of the PM-E DC24V/8A RO power module can be switched off using two methods: via PROFIenergy or via the user program in the process image output (PIQ) with the control byte. Note To prevent undesired switching states of the encoder and load supply, you should not additionally switch off the terminal voltage when the voltage group is switched off. PROFIenergy commands Properties The voltage group of the power module is switched on and off with PROFIenergy commands. The procedure for using PROFIenergy commands is explained using an example application. You can download this example from the Internet under Service & Support. Prerequisites Interface module (see Requirements for operation) PM-E DC24V/8A RO power module Configuration in HW Config with the entry "PM-E DC24V/8A RO" Optionally: Application example of PROFIenergy For further information PROFIenergy: See PROFINET System Description (http://support.automation.siemens.com/ww/view/en/19292127) Application example of PROFIenergy See Service & Support in the Internet (http://support.automation.siemens.com/ww/view/en/41986454). Manual, 06/2010, A5E02953719-01 13

Properties 1.2 Reduction of power consumption Control byte in the process image of outputs (PIQ) Properties The voltage group of the power module is switched on and off via bit 0 in the control byte of the PIQ (see chapter Configuration (Page 19)). For this step you have to program the respective access in your user program. Requirements Interface module (see Requirements for operation) PM-E DC24V/8A RO power module Configuration in HW Config with the entry "PM-E DC24V/8A RO S" User program Example In the following example the voltage group is switched on and off in the control byte (PIQ) with the user program: STL Explanation // switch off voltage group SET RLO=1 S A0.0 Set bit 0 of the control byte to 1 STL Explanation // switch off voltage group SET RLO=1 R A0.0 Set bit 0 of the control byte to 0 Configuring instructions The entire voltage group of the PM-E DC24V/8A RO power module is always switched off using the PROFIenergy commands or the control byte. Recommendation: Configure all ET 200S electronic modules whose encoder and load supplies are to be switched off in the voltage group of the PM-E DC24V/8A RO. Program the required states of the inputs and outputs for all electronic modules in the switched off voltage group with a user program. Place all I/O modules whose encoder and load supplies may not be switched off behind a different ET 200S power module, for example, PM-E DC24V. 14 Manual, 06/2010, A5E02953719-01

Parameters 2 2.1 Parameters for PM-E DC24V/8A RO Parameters The following table lists the power module parameters. Table 2-1 Parameters for power modules PM-E DC24V/8A RO Range of values Default setting Applicability Diagnostics: Terminal voltage (L+) Disable/enable Disable Power module missing Diagnostics: No load voltage (PWR) Disable/enable Disable Power module The parameters are explained below. Diagnostics: Terminal voltage (L+) missing This parameter triggers a diagnostic message if there is no encoder and load supply at the voltage group (root). If there is no terminal voltage (L+ < 15V), only the diagnostic message of the affected power module will be sent to the IO controller. The SF error LEDs of all modules in the relevant voltage group light up. Diagnostics: No load voltage (PWR) This parameter is used to release a diagnostic message if there is no rated load voltage 24 VDC at the power module or if the voltage group was switched off. If there is no load voltage (PWR < 15V), only the diagnostic message of the affected power module will be sent to the IO controller. The SF error LEDs of all modules in the relevant voltage group light up. Manual, 06/2010, A5E02953719-01 15

Parameters 2.1 Parameters for PM-E DC24V/8A RO 16 Manual, 06/2010, A5E02953719-01

Diagnostics 3 3.1 Diagnostics using LED display Power module LED displays on the power module: 1 2 3 1 Batch error (red) 2 Terminal voltage (green) 3 Load voltage (green) Status and error displays by means of LEDs on power modules The table below shows the status and error displays on the power module. Event (LEDs) SF L+ PWR On Cause A diagnostic message is pending. No parameter assignment or incorrect module plugged in. Off Off There is no terminal voltage at the power module. On Off Voltage group (encoder and load supplies) switched off. Remedy Evaluate the diagnostics. Check the parameter assignment. Check the applied terminal voltage of 24 VDC. Switch on the voltage group with a PROFIenergy command or control byte. Manual, 06/2010, A5E02953719-01 17

Diagnostics 3.2 Error types 3.2 Error types Power module error types The diagnostic message is reported on channel 0 and applies to the entire module. The table below shows the types of errors in power modules Table 3-1 Power module error types 17D 24D Error type Meaning Remedy 10001: Encoder or load voltage missing 11000: Actuator disconnection Terminal voltage not present or too low. Terminal voltage not present or too low Voltage group switched off (The encoder and load supply of the connected sensors and actuators are switched off) Correct the process wiring. Check the rated load voltage. Switch on the voltage group with the PROFIenergy command or the control byte. 18 Manual, 06/2010, A5E02953719-01

Configuring 4 4.1 Configuring the address space Address area for control and status byte You can switch off the voltage group via the control byte and evaluate the status byte of the power module using the control (PIO) and feedback interface (PII). The address range of the control (PIO) and feedback interface (PII) depends on how the corresponding entry in the configuration software is configured, or which entry has been selected. This table shows the PII feedback interface and the PIO control interface for different entries. Table 4-1 PII feedback interface and PIO control interface With STEP 7, HW Config PII feedback interface PIO control interface or COM PROFIBUS or other configuration software "PM-E DC24V/8A RO" --- --- "PM-E DC24V/8A RO S" EB x Status byte AB x Control byte Manual, 06/2010, A5E02953719-01 19

Configuring 4.1 Configuring the address space Status byte for power modules Figure 4-1 Assignment of status byte for power modules Note The bit 0 = "0" (load voltage missing), if bit 4 = "1" (terminal voltage missing), bit 5 = "1" (feedback voltage missing) or bit 6 = "1" (encoder or load voltage missing) Control byte for power modules Figure 4-2 Assignment of control byte for power modules 20 Manual, 06/2010, A5E02953719-01