HAT270A ATS (Automatic Transfer Switch) CONTROLLER OPERATING MANUAL Smartgen Electronics

Similar documents
HAT260 ATS (Automatic Transfer Switch) Controller USER MANUAL. Smartgen Technology

HAT530 ATS CONTROLLER USER MANUAL

ATS CONTROLLER OPERATING MANUAL

HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL

HAT162 ATS CONTROLLER USER MANUAL

HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL

HAT160 ATS CONTROLLER USER MANUAL

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

HAT72 ATS CONTROLLER USER MANUAL

HVD300 VOLTAGE DETECTION RELAY MULTIFUNCTIONAL PROTECTION MODULE USER MANUAL

Manual TU510A. Auto Transfer Controller HM1043ER1

CMM366-3G CLOUD MONITORING COMMUNICATION MODULE USER MANUAL

DIN16A DIGITAL INPUT MODULE USER MANUAL

Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus

Zelio Control - modular measurement and control relays 1 Speed control relays RM35 S

EXPANSION PERIPHERAL CVM-R10 C. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

Switched Mode Power Supply Operating manual PAP800

DATA SHEET Compact Genset Controller, CGC 200

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

Switching module for AC V and up to three load stages, with manual switching

DALI Professional Controller-4. Control unit Operating instructions

PCM SLK- Series Inverter Specification

User Guide Automatic Transfer Switch (ATS)

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Protector Trip Relays ENERGY DIVISION

4100 and 4100/R Controllers

Temperature controller Ducted systems

Quantum III. Compact DC Drive Package. Slitter DC Drive Package. Quantum III

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

EEET 2204 Industrial Automation

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

EH21 DVP

INSTRUCTION SHEET. Eaton Logic Controller ELCB Controllers

Installation Manual for D244X Series 24-volt Power Supplies

Zelio Control-modular measurement and control relays 1

SELECTRONIX, INC. SUPERSTEP SERIES 4000 SEQUENCING STEP CONTROLLERS WOODINVILLE, WA INSTALLATION & OPERATING ADDENDUM LOAD LIMIT INPUT CONFIGURATIONS

SED2 Variable Frequency Drives with Electronic (E) Bypass Options

ict contactors EN 61095, IEC 1095 Interference

Circuit Breaker Analyzer & Timer CAT65

HMC9000A DIESEL ENGINE CONTROLLER (With J1939 Interface) USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO.,LTD.

Contents. Temperature & Process Measurement Indicators Setup Guide

HPT300 POWER CONVERT MODULE USER MANUAL

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

XTM1250SA DIN rail three phase four wire LCD display energy meter

GS400. Electronic Auto-Ranging DIN Panel Mounted Positioner

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

Comprehensive Modular Genset Controller

02/11/2015

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL

Operating instructions only for authorized, skilled electricians with EIB training

Signal conditioning instruments for level switches. Conductive VEGATOR 256C VEGATOR 532 VEGATOR 631. Product Information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

100% electricity. Automatic transfer switch controllers ATL series

F1000 User's Manual. (Version: V1.01)

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

Circuit Breaker Analyzer & Timer CAT66

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

Quick Start Guide TS A

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Zelio Control Measurement Relays Multifunction 3-phase supply control relays RM17T 00

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

Tension Controller - Feedback. System

SED2 Variable Frequency Drives Conventional Bypass (C-Bypass) Options

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

Circuit Breaker Analyzer & Timer CAT126

Digital Speed Controller User Manual

Compact Universal Controllers

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

Circuit Breaker Analyzer & Timer CAT126

Expansion Module HZS 541-1S

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Installation & Operation and Maintenance

DEEP SEA ELECTRONICS PLC

The Single Dimmer Board

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

UH28C. High Voltage Tester. Product Information Sheet V AC / 100 ma

CA-A480-A Elevator Controller. Reference & Installation Manual

PRO-75 SERIES. User manual

Chassis Power Supplies

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

EWCH 485 Electronic Pulse Counter

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

DEEP SEA ELECTRONICS PLC

Series 230 Automatic Transfer Switch

AUTOMATIC TRANSFER SWITCH CONTROLLERS ATL SERIES

CFW-09HD LINE DC LINK POWER SUPPLY

SIGUARD Safety Combinations and Safe Load Feeders. safety INTEGRATED

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

Content. Time delay relays mounting position. Multifunctional time delay relay Clock-pulse generator time delay relay... 3.

HGM9510 Genset Parallel (With Genset) Unit USER MANUAL. Smartgen Technology

DALI RM 8/16. Datasheet. DT7 Relay Module. Relay Module for the integration of non-dimmable ballasts in DALI lighting systems (DT7)

DIGITAL DISPLAY. for Industry Applications. Series PAXD. Key-Features:

IDE Load break switches for machine control Remotely trippable switch from 32 to 160 A

PC2004 PRESSURE CONTROLLER

Transcription:

HAT270A ATS (Automatic Transfer Switch) CONTROLLER OPERATING MANUAL Smartgen Electronics

CONTENT 1 SUMMARY... 4 2 FEATURES... 4 3 SPECIFICATION... 5 4 PANEL OPERATING INSTRUCTION... 6 5 PANEL OPERATION AND WIRING... 6 5.1 PANEL DELAY ADJUSTMENT... 6 5.2 CONTROL SETTINGS... 6 6 AC OPTION ELECTRICITY REGULATION... 9 7 PROGRAMMED PARAMETER AND RANGE... 9 8 TERMINAL FUNCTIONS... 10 9 TYPICAL WIRING DIAGRAMS... 11 10 OVERALL AND MOUNTING DIMENSIONS... 14 11 FAULT FINDING... 14 HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 3 of 14

1 Summary HAT270A ATS controller has microprocessor as its core, can accurately monitor 2 ways-3 phase, and also can make accurate judgment conditions of abnormal voltage (loss of electricity, over voltage, under voltage, loss of phase); control ATS to transfer after delay. Controller also has a function of sending start signal to genset when one way power is abnormal. HAT270A is suited for SOCOMEC VS, VE, ATyS3, ATySM3s model and other analogy function ATS switch. 2 FEATURES The controller can monitor two ways 3phase voltage (it possibly is two ways mains, two ways gens, or is 1 mains-1 gens) and control ATS to transfer. Its performance and characteristics show as following: Realizing the computer programming control, can use computer to set abnormal voltage delay, switch priority, genset shutdown delay, the voltage correction and other functions, fully graphical interface operation. When programming by computer, the controller front panel must be opened, then use SG72 interface module (USB to LINK) via the PC test software. About PC software s operation, please refer to software manual of HAT270A. #I power supply or #II power supply normal delay can be set range (0~60) seconds. Genset start delay can be set range (0~60) seconds; #I power supply or #II power supply abnormal delay can be set range (0~60) seconds. Genset stop delay can be set range (0~90) seconds; Design of 2 ways N line isolate; The controller design have breaking off compulsorily input port, when input is active, ATS will transfer compulsorily to OFF position; Panel LED can clearly show switch working position; Have a dual power supply change-over circuit output, the output LO, NO (5A 250V AC) can be applied directly to the power supply as ATS; Genset start relay(gens START) output contact capacity for 7A/28VDC, passive normally close contact; Controller has strong ability for anti-electromagnetic interference, and very suitable for using in strong electromagnetic interference of complex environment. Modular configuration design, Flame Retardant ABS plastic shell, inserted type connection terminals, flush type installation, compactness, compact structure, easy installation. HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 4 of 14

3 SPECIFICATION Power supply input The controller AC power supply: AC230V±20% (50/60Hz) (sensing from #I and #II A, N phase) Measure voltage: rated 380V 50/60Hz 3-phase 4-wire, and other measure voltage class, please consults before ordering. Threshold setting point Over-voltage threshold: 264V (adjust only via PC). Under voltage threshold: 172V (adjust only via PC). Action time Closing breaker time: 5 seconds, if detected during the closing breaker the closing status signal is active, then immediately disconnected. Opening breaker time: 3 seconds, if detected during the open breaker the open status signal is active, then immediately disconnected. Voltage normal delay: (0~60) seconds (via controller panel potentiometer adjustment). Voltage abnormal delay (0~60) seconds, default: 5 seconds (only via controller panel potentiometer adjustment). Genset start delay: when #I confirmed abnormally, delay for (0~60) seconds, (default: 10 seconds, can be adjusted on the panel.) Genset stop delay: when #I confirmed normally, delay (0~60) seconds, (default: 90 seconds, can via controller panel potentiometer or PC adjustment). I /#II closing status monitoring (can via controller panel key-press programmed) Default: detect #I/II closing status input port, the controller must access the closing status signal. Power supply consumption Device voltage looping at rated voltage of the power supply consumption of less than 2VA. Environment condition Temperature: (-30~+70)ºC Humidity: (20~95)% Weight Net weight: 0.47Kg HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 5 of 14

4 PANEL OPERATING INSTRUCTION 5 PANEL OPERATION AND WIRING 5.1 PANEL DELAY ADJUSTMENT #I power supply normal delay potentiometer: judgment time (0~60) seconds. #II power supply normal delay potentiometer: judgment time (0~60) seconds. 5.2 CONTROL PARAMETERS SETTINGS a) Automatic/ Manual status operating When controller is running, press key, controller will be changed into Automatic mode or Manual mode (via automatic status indication lamp, manual status indication lamp mark). In Manual mode, press the key, load will be transferred to #I power supply side, press key, load will be transferred to #II power supply side. b) #I/II voltage abnormal delay, genset start/stop delay, #I/II transfer priority, breaker on feedback settings: HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 6 of 14

When controller is running, press and hold key and key simultaneously, #I power supply indication lamp, automatic status indication lamp, #II power supply indication lamp flashes, as shown that have entered into setting status. The setting steps as follows: Press button to cycle to the selection you set the item, different of settings items for the different of flashing LED on the panel lamp, the setting the item as follows: Item LED indication Indication Confirmation After adjustment "#I power supply normal #I/#II Power supply abnormal delay #I power supply LED flash #I power supply abnormal delay #II power supply abnormal delay delay" potentiometer, press the key, #I power supply indication lamp illuminate, shown that the adjustable potentiometer value (0~60) seconds have be saved successfully. After adjustment "#II power supply normal delay" potentiometer, press the key, #I power supply indication lamp illuminate, shown that the adjustable potentiometer value (0~60) seconds have be saved successfully. Restore factory values Press the key, #I power indication lamp illuminate, shown to restore the default factory values. (Default #I, #II power supply abnormal delay is 5 seconds.) After adjustment "#I power supply normal Genset start/stop delay Automatic status LED flash Genset start delay delay" potentiometer, press the key, automatic status indication lamp illuminate, shown that the adjustable potentiometer value (0~60) seconds have be saved successfully. After adjustment "#II power supply normal Genset stop delay delay" potentiometer, press the key, automatic status indicator lamp illuminate, shown that the adjustable potentiometer value (0~60) seconds have be saved HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 7 of 14

successfully. Restore factory values Press the key, automatic status indication lamp illuminate, shown to restore the default factory values. (Default genset stop delay is 90 seconds.) #I power supply priority Press the key, #II power supply indication lamp illuminate, show #I power supply as main power to supply for the load. I/#II power supply priority(*1) #II power supply LED indication lamp flash #II power supply priority Press the key, #II power supply indication lamp illuminate, show #II power supply as main power to supply for the load. Select #I/#II breaker on feedback (*2) #I close breaker LED indication lamp flash #I/#II power supply no priority Not check breaker on feedback Check breaker on feedback Press the key, #II power supply indication lamp illuminate; show #I/#II power supply no priority supply for the load. Press the key, does not detect #I, #II breaker on feedback input port. Press the feedback input port. key, detect #I, #II breaker on *1 Note: Every time the controller power on, the following three conditions can judgement the priority of transfer. 1) If #I power supply indication lamp flashes rapidly for three times, indicate #I power supply for priority transfer. 2) If #II power supply indication lamp flashes rapidly for three times, indicate #II power supply for priority transfer. 3) If #I and #II power supply indication lamp simultaneously flashes rapidly for three times, for no priority transfer. *2 Note: Every time the controller power on, #I/ #II closing breaker lamp illuminate at the same time, show checking the breaker on feedback, if extinguishment, indicate not detect the breaker on feedback. Detection of the breaker on feedback: Controller will really indicate #I, #II closing status according to breaker on feedback input port status. Does not detect the breaker on feedback: Controller will indicate #I and #II closing status via the built-in control process ignore the breaker on feedback. After the parameter settings are completed, pressing #I and #II close press-key HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 8 of 14

simultaneously, all the controller panel lamps will illuminate, loosen these press-keys, and this setting is completed. 6 AC VALID OPTION User can actually use, and set the rules for an electric. NUM Rule description 1 Phase B, C can not lose of phase. Phase A must 2 Phase B, C can lose of one phase. have voltage 3 Phase B, C can all lose. 4 Phase A must not Phase A, B, and C can lose of one phase. 5 have voltage Phase A, B, and C can lose of two phases. 7 PROGRAMMED PARAMETER AND RANGE Num Name Range Default Remark 1 2 #I voltage normal delay #II voltage normal delay (0~60)s (0~60)s 3 Genset start delay (0~60)s 4 #I voltage abnormal delay (0~60)s 5s 5 #II voltage abnormal delay (0~60)s 5s 6 Genset stop delay (0~90)s 90s 7 Voltage upper limit value (50~300)V 264V 8 Voltage lower limit value (50~300)V 172V 9 Power supply transfer priority setting 10 AC valid option 11 Breaker on feedback detection 1# priority, 2# priority, no priority See AC valid option Via controller panel potentiometer setting 1#priority Phase A, B and C can not loss of phase Detection Only adjust via controller front panel potentiometer Adjust via controller front panel potentiometer or PC Only adjust via PC test software. Adjust Via controller panel front potentiometer or PC test software. Only adjust via PC test software. Only adjust via controller front panel potentiometer HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 9 of 14

8 TERMINAL FUNCTIONS Terminal A1, B1, C1, N1 is separately connected to A, B, C, N of #I AC power supply. Terminal A2, B2, C2, N2 is separately connected to A, B, C, and N of #II AC power supply. Terminal S1: #I power supply breaker on feedback input port.(volt-free contact connection, connecting GND activate) Terminal S2: #II power supply switch close status input port.( volt-free contact connection, connecting GND activate) Terminal FO(VIN):this is a superposition port for controller DC power supply positive pole and compulsory breaking off input,when this port connect with GND, the breaker will force into OFF position. When this port connect with DC power supply, if the port connect with to GND, it will be short circuit of DC power supply, only when DC power supply disconnect with DC power supply positive pole, allow to connect with GND and achieve compulsory breaking off function. When this port is connected to GND, whether in manual or automatic mode, ATS will be switched to OFF position, manual or automatic operation is prohibited. Only when ATS have OFF position i.e. SOCOMEC VE type, ATyS3 type, and ATySM3S type, the compulsory breaking off function is valid, but SOCOMEC VS type is invalid. HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 10 of 14

Terminal GND: the controller DC power supply cathode. Terminal M1, M2 (GENSET START): for genset start output relay (passive normally close contactor, capacity for 7A). Terminal LO, NO: supply working power supply for ATS, LO/NO separately come from #I, #II power supply A, N phase, when any one way phase A, N is normal, these two terminals will output equal power supply (capacity for 5A/250VAC). Terminal COM: SOCOMEC ATS close and open input common terminal. Terminal O: SOCOMEC OFF position control (contactor capacity for 3A/250VAC). Terminal I: SOCOMEC #I close control capacity for 3A/250VAC. Terminal II: SOCOMEC #II closes control (contactor capacity for 3A/250VAC). 9 TYPICAL WIRING DIAGRAMS SOCOMEC VS type switch HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 11 of 14

SOCOMEC VE type switch SOCOMEC ATyS3e type switch HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 12 of 14

SOCOMEC ATySM3s type switch SOCOMEC ATyS3s type switch Note: 81, 84: ATyS3s types switch 1# close normally open auxiliary port; 91, 94: ATyS3s types switch 2# close normally open auxiliary port; HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 13 of 14

The small capacity SOCOMEC ATyS3s type switch not label closing status auxiliary port, the specific auxiliary port position refer to switch wiring diagram. 10 CASE AND DIMENSIONS 11 FAULT FINDING Symptom Controller isn t work Controller normal display but switch inaction #I or #II normal lamp flash. In automatic mode, I/II # normal indicate lamp illuminate but switch not act. Genset not start Possible remedy Check #I and #II power supply wiring. Check #I and #II power supply fuse. Check ATS mechanism. Check the connection between the ATS and the controller. Check 3 phase voltage whether normal.(overvoltage, under voltage, loss of phase[include loss of N wire]) Set the controller in manual mode, testing whether act. Check voltage normal delay, shorten the delay time. Check the connection wires between the ATS and the controller. Genset start signal output only when #I voltage abnormal. Check genset start delay, shorten the delay time. HAT270A ATS Control Module ISSUE 2011-05-20 Version1.1 Page 14 of 14