MRA1 Trip circuit supervision. Manual MRA1 (Revision A)

Similar documents
IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

MRT1 Test Unit. Manual MRT1 (Revision A)

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

XG2 Generator-/Mains Monitor. Manual XG2 (Revision A)

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

BN1-400 Mains decoupling relay. (February 2000) Manual BN1-400 (Revision New)

Model Number Structure

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Electronic timer CT-ERD.12

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

Solid-state Timer. Ordering Information. Specifications. Miniature Timer Compatible with the MY Relay. Accessories. Time Ranges

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

Binary output and supervision 520CSD01 Data sheet

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

TeSys protection components

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

Electronic timer CT-AHD.22

Contact protection relay

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

QUINT-BUFFER/24DC/24DC/40

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

MRU4 Profibus DP HighPROTEC. Data point list. Manual DOK-TD-MRU4PDE

11 Series - Light Dependent Relay A. Features pole 17.5 mm wide. 1 pole zero hysteresis 4 position selector

Electronic timer CT-ARS.11

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

DI561 Digital Input Module

MRP2-S3 Apparent Power Relay. Manual MRP2-S3 (Revision A)

TRIO-DIODE/12-24DC/2X10/1X20

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

For Transmission, Distribution and Machinery protection.

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

02/11/2015

Arc protection relay. Features Three-phase overcurrent function. Application

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Industrial Power Supplies

DI572 Digital Input Module

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

Electronic timer CT-ERS.21

Phase loss monitor CM-PBE Phasemonitor for over and undervoltage CM-PVE Ordering details

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

NI REM Remote I/O Overview DATASHEET. Digital Output Module for Remote I/O

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Conforms to VDE0435/2021 C/250, VDE0110, VDE0106/P100 Conforms to EN , pren

Solid-state Timer H3YN

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Solid-State Contactors

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

Model Number Structure

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Switching relay CT-IRE with 1 c/o (SPDT) contact

1 pole 17.5 mm wide 2,000 2, ,000 1,000 halogen W DC / / / / 30

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)

Residual overvoltage relay

Feeder protection relay SPAA 121 C. Product Guide

DC561, digital input/output module,

MINI MCR-SL-UI-REL(-SP)

Technical specifications

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Universal Power Supplies

STEP-PS/1AC/24DC/1.75

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

TU531, TU532 Terminal Unit

Synchro-check relay. Application

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Relion 611 series. 611 series Type Test Certificate

High impedance protection relay

DC562, digital input/output module,

RE Product data sheet Characteristics. universal plug-in timing relay - flashing s..60 mn V AC - 2 OC. Main.

RE22R2QTMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

DX561 Digital Input/Output Module

Three-phase monitoring relay

Functional configuration Rated input voltage Power ratings Output voltage Output current Part number Non-PFC

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Arc protection relay. Features Three-phase overcurrent function. Application

PHOENIX CONTACT - 01/2007

SRT2-ROC08, SRT2-ROC16

Output Voltage* (nom.)(adjustable)

02/11/2015

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

MRI4 Profibus DP HighPROTEC. Data point list. Manual DOK-TD-MRI4PDE

MINI-PS AC/10-15DC/8

Solid-state Timer. Ordering Information. Ultra-slim Timer for G2R Relay Socket. H3RN-jj. Accessories (Order Separately) Connecting Socket

TeSys IEC Contactors and Overload Relays

Power supply CP-C 24/5.0

PHOENIX CONTACT - 07/2006

Transcription:

MRA1 Trip circuit supervision Manual MRA1 (Revision A)

Woodward Manual MRA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is assumed by Woodward Governor Company unless otherwise expressly undertaken. Woodward 1994-2008 2 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward Contents 1. Introduction and application... 4 2. Features and characteristics... 4 3. Design... 5 3.1 Connections... 5 3.2 Coding plug... 6 3.3 Coding of the LED function... 7 3.4 Coding Auto/Manual Reset... 8 4. Functions... 9 4.1 Supervision of the voltage supply of the protection devices... 9 4.2 Cable break supervision... 9 4.3 Front plate... 10 4.4 LEDs... 11 4.5 Status indicator... 11 4.6 Resetting... 11 4.7 Terminal block... 12 5. Testing the relay and commissioning... 14 5.1 Connecting the auxiliary voltage... 14 5.2 Testing the supervision circuits... 14 5.3 Testing the AUTO-RESET function... 15 5.4 Testing the external RESET inputs... 15 5.5 Testing the LED function... 15 6. Technical Data... 16 7. Order form... 18 DOK-TD-MRA1 Rev.A 3

Woodward Manual MRA1 GB 1. Introduction and application The MRA1 - relay of the HIGH TECH LINE is used to supervise the tripping circuit of protective devices taking into consideration the following protective criteria: supervision of the auxiliary voltage for the tripping circuit and for the supply of protective devices supervision of the tripping circuit with regard to cable break supervision of the mechanical functions of the circuit breaker 2. Features and characteristics high breaking capacity of the relay contacts in compliance with the requirements as per BS 142 and IEC 255 manual/automatic reset coil resistance of tripping coil may be up to 12 kω supervision independent of the circuit breaker position wide range power supply for all nominal supply voltages 4 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward 3. Design 3.1 Connections Figure 3.1: Connection diagram MRA1 Version "A" Application with opener and shutter contacts of the circuit breaker Figure 3.2: Connection diagram MRA1 Version "B" Trip supervision with a shutter contact DOK-TD-MRA1 Rev.A 5

Woodward Manual MRA1 GB 3.2 Coding plug Switching thresholds of the input circuitry The MRA1 has a wide-range power pack for all commonly used voltage values. For this reason the pick-up thresh-olds of the internal relays K1, K2, K3 and the reset input must be adjusted to the existing rated voltage. There are 4 switching thresholds available which can each be changed by 2 coding plugs. Switching threshold Coding plug A Coding plug B 9V plugged plugged 30V Not plugged plugged 65V plugged Not plugged 100V Not plugged Not plugged This means that each input can be switched separately. (Refer to set-ting lists on last page) The coding plugs are located inside the device on the bottom side of the relay card. Figure 3.3: Coding of the pick-up thresholds of the internal relays K1, K2, K3 and the reset function 6 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward 3.3 Coding of the LED function The MRA1 can be used for two different monitoring concepts. a) Supervision of the circuit breaker by two supervision circuits. The opener and the shutter contacts of the circuit breaker are supervised separately. (P = parallel connection) b) Supervision of the circuit breakers by one supervision circuit (S=serial connection) For this reason the switch position indication, which is shown by LEDs on the front plate of the MRA1, must be coded. In circuit version "A" the coding plug must be in position "P" and for the circuit version "B" it must be in position "S". The coding plugs are located inside the device on the bottom side of the relay card. Figure 3.4: Coding plug MRA1 LED function DOK-TD-MRA1 Rev.A 7

Woodward Manual MRA1 GB 3.4 Coding Auto/Manual Reset Behind the front plate of the MRA1, on the bottom side, there is a coding plug for pre-setting the reset behavior of the output relay. If the coding plug is plugged in, the output relay and the indicator are set back if the fault, e.g. line break, has been corrected. If the coding plug is not plugged in, the output relays and the must be reset manually by activating the reset key or the external reset function. Figure 3.5: Position of coding plugs 8 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward 4. Functions 4.1 Supervision of the voltage supply of the protection devices Relay K1 is released if the voltage drops below the voltage pre-set with the coding plugs (refer to Chapter 3.2).The relay is energized in steps of 5 V each above the release point of the coded switch point. In order to bridge brief drops (up to approx. 200 ms), an RC circuit is connected in parallel. The "OK" LED lights up green if the tripping circuit is free of faults. Relay K1 is in pick-up condition if the entire tripping circuit is in order. 4.2 Cable break supervision The MRA1 can be used for two different monitoring concepts. a) Supervision of the circuit breaker by two supervision circuits. The opener and shutter contacts of the circuit breaker are supervised separately. (P=parallel connection) b) Supervision of the circuit breakers by one supervision circuit (S=serial connection). Version "A": Depending on the position of the circuit breaker, K2 or K3 will be energized and thus switch relay K1 on. The LEDs OK and CB OFF light up green. The LED CB ON lights up red. In case of a cable break, the relevant relay (K2 or K3) and K1 are released. Position of the circuit breaker: Circuit breaker OFF: The aux. contact (opener) of the circuit breaker is closed and K3 is active. In case of supply voltage failure, K1 is released and the relay trips. If the tripping coil of the circuit breaker is interrupted, K3 is re-leased and consequently also K1, and the relay trips. Circuit breaker ON: K3 releases with delay. K2 is energized undelayed via the aux. contact (shutter) of the circuit breaker and K1 remains active. Protection trips: K2 release is delayed about 400 ms, which thus bridges the protection relay contact time-wise. If the circuit breaker does not switch off despite the switch-off command, the contact of the protection relay remains closed. After approx. 400ms K2 and K2 are released. The trip relay K1 is then in trip position. (Refer Figure 3.1) Version "B": With this With this version relays K2 and K3 are energized. In case of a cable break K2 and K3 are released and subsequently also K1. Position of the circuit breaker: Circuit breaker OFF: Switch position indication only re-quires one shutter contact of the circuit breaker. If the circuit breaker is switched off, K2 and K3 are active. In case of supply voltage failure K1 releases and the relay trips. If the trip coil of the circuit breaker is interrupted, K2 and K3 are released and consequently also K1, and the relay trips. DOK-TD-MRA1 Rev.A 9

Woodward Manual MRA1 GB Circuit breaker ON: K3 is released with delay action by short-circuiting the circuit breaker by means of aux. contact (shutter). K1 remains active as K2 remains energized. Protection trips: Tripping of the protection relay will bridge K2. On account of the release delay by 400 ms, the protection relay contact is bridged timewise. If the circuit breaker does not switch off despite switch-off command, the con-tact of the protection relay remains closed. After approx. 400ms K2 and K1 will be released. The trip relay K1 is then in release position. (Refer to Figure 3.2) 4.3 Front plate Figure 4.1: Front plate MRA1 10 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward 4.4 LEDs Located on the front plate of the MRA1 are three light-emitting diodes. The LED OK serves for indicating readiness for operation and emits a green light. The LEDs CB ON and CB OFF signal that the circuit breaker is switched on or off. The LED CB ON emits a red light, the LED CB OFF emits a green light. The correct indication of the LEDs must be coded in accordance with the circuitry version. (refer to chapter 3.3) Note: With version "B" a cable break may lead to over-functioning of the LEDs "CB ON" and "CB OFF" (switch position indication). If there is a cable break at terminals A5 or A6 (refer to Figure 3.2) while the circuit breaker is switched on, the MRA1 will signal this fault, but simultaneously dis-play the circuit breaker in position "OFF". LED "CB OFF" will emit light although the circuit breaker is still switched on. 4.5 Status indicator The status indicator or visual signal indicates, whether the MRA1 has tripped or not. Red means that the MRA1 has tripped. A dark display means that there is no fault. If the internal supply voltage of the device fails, the status indication will al-ways switch to the position released. 4.6 Resetting The MRA1 must be reset at every trip-ping action, also after the protection relay is switched on for the first time. The tripping relay is energized and the indicator moves into position dark. There are three possible ways of resetting the protection relay. RESET key The Reset key permits resetting of the output relay and the indicator once the fault has been corrected. External RESET By applying the supply voltage, the output relay and the indicator can be reset via input terminals A2 E9, when the fault has been eliminated. Automatic RESET Once the fault has been corrected, the output relays and indicators are reset without delay. The function is activated by means of the coding plug which is located behind the front plate. (refer to Chapter 3.4) DOK-TD-MRA1 Rev.A 11

Woodward Manual MRA1 GB 4.7 Terminal block The plug-in module MRA1 has a very compact base with plug connectors and screw-type connectors: 8 screw-type terminals (connection plug row A) for voltage inputs 27 poles tab terminals for relay outputs, supply voltage etc. (terminal connectors series C, D and E, max. 6A current carrying capacity). Connection with tabs 6.3 mm x 0.8 mm for cable up to max. 1.5 mm2 or with tabs 2.8 mm x 0.8 mm for cable up to max. 1 mm2. By using 2.8 x 0.8 mm tabs a bridge connection between different poles is possible. Figure 4.2: Terminal block 12 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward Figure 4.3: Dimensional drawing Please observe: A distance of 50 mm is necessary when the units are mounted one below the other for the front cover to be easily opened. The front cover can be opened downwards. DOK-TD-MRA1 Rev.A 13

Woodward Manual MRA1 GB 5. Testing the relay and commissioning The following testing instructions serve for testing the functions of the device and for commissioning it. In order to prevent destruction of the device and to ensure correct functioning, the following points must be adhered to: The rated auxiliary voltage of the device must be the same as the auxiliary voltage available at site. All control and measuring circuits as well as the output relays must be connected correctly. The coding plugs for the switch-on thresholds of the relays must be adjusted to the respective rated voltage. 5.1 Connecting the auxiliary voltage Please note! Before connecting the device to the auxiliary voltage it must be ensured that this voltage is the same as the rated auxiliary voltage of the device stated on the type plate. 5.2 Testing the supervision circuits The MRA1 must be connected as shown in the test circuit diagram. Testing circuit MRA1 The coding plug for the LED function must be set to position "P" (refer to Chapter 3.3). The coding plug for the reset function should not be plugged in. After the supply voltage has been switched on, the indicator remains in the position "tripped". Actuating switch S1 energizes the relay K2. The LED»CB ON«emits a red light. After switch S1 has been re-set, relay K2 is released again with delay action (approx. 400ms). LED»CB ON«extinguishes again. Actuating switch S2 energizes the relay K3. The LED»CB OFF«emits a green light. After switch S2 has been reset, relay K3 is released again with delay action (approx. 400ms). LED»CB OFF«extinguishes again. Actuate switch S1 or S2 again. After switch S3 has been actuated, nothing happens at first. It is only after the Reset key has been pressed that the LED»OK«lights up green and the indicator is set back. Reset S3. After approx. 200ms the»ok«led goes out and the indicator shows the fault status. 14 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward Figure 5.1: Testing circuit MRA1 5.3 Testing the AUTO-RESET function If the coding plug Auto-Reset located behind the front plate is set (refer to Chapter 3.4), the»ok«led lights up immediately when switch S3 and switch S1 or S2 are set. The indicator is then reset automatically. 5.4 Testing the external RESET inputs The external Reset function is to be tested. The coding plug for automatic reset must not be plugged in. Switches S3 and S2 or S1 must be set. The auxiliary voltage must be con-nected to terminals A2 and E9. The»OK«LED lights up and the indicator is reset. 5.5 Testing the LED function The MRA1 has two possible ways of monitoring. For this reason there are two possible functioning methods for the LEDs»CB ON«and»CB OFF«. The coding plug is located on the upper side of the relay card (refer to chapter 3.3). Position "P" was al-ready tested when the supervision circuits were tested (refer to chapter 5.2). Set coding plug for the LED function to position "S". After the auxiliary voltage has been switched on, the LED»CB ON«lights up. Actuate switch S3. The LED»CB ON«extinguishes and LED»CB OFF«lights up. DOK-TD-MRA1 Rev.A 15

Woodward Manual MRA1 GB 6. Technical Data Supply voltage: 16 360 V/DC 16 270 V/AC Output relays: Output contacts: Breaking capacity AC: Breaking capacity DC: ohmic: inductive (L/R < 40 ms): 4 change-over contacts 2000 VA / max. 250 V 30 V / 8 A 110 V / 0.5 A 300 V / 0.3 A 24 V / 1 A 110 V / 0.2 A 230 V / 0.15 A Power consumption: at 24 V: max. 9.2 W at 110 V: max. 9.4 W at 220 V: max. 9.8 W Measuring inputs: Operating time: Reset: Tripping: Trip coil: < 100 ms at switching failure >400 ms at failure of supply voltage >200 ms coil resistance 0-12 kω System data: Design standards: Generic standard: EN 50082-2, EN 50081-1 Product standard: EN 60255-6, BS142 Specified ambient service temperature limits in operation: at storage: Moisture-carrying capacity class F as per DIN 40040 and per DIN IEC 68, part 2-3: Insulation test voltage, inputs and outputs between themselves and to the relay frame as per EN 60255-6, IEC 255-5: Impulse test voltage, inputs and outputs between themselves and to the relay frame as per EN 60255-6, IEC 255-5: High frequency interference test voltage, inputs and outputs between themselves and to the relay frame as per EN 60255-6, IEC 255-22-1: -10 C to +55 C -25 C to +70 C rel. humidity <95 % at 40 C for 56 days 2.5 kv (eff.) / 50 Hz.; 1 min. 5 kv; 1.2 / 50 s, 0.5 J 2.5 kv / 1 MHz 16 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward Electrical discharge (ESD) test as per EN 61000-4-2, IEC 255-22-2: Electrical fast transient (Burst) test as per EN 61000-4-4, IEC 255-22-4: Radiated electromagnetic field disturbance test as per ENV 50140, IEC 255-22-3: Guided radiated electromagnetic field disturbance test as per ENV 50141: Surge immunity test as per EN 61000-4-5: Radio interference suppression test as per EN 55011: Radio interference radiation test as per EN 55011: 8 kv air discharge, 6 kv contact discharge 4 kv / 2.5 khz, 15 ms electric field strength: 10 V / m electric field strength: 10 V / m 4 kv limit value class B limit value class B Mechanical tests: Shock class 1 as per DIN IEC 25-21-2 Vibration class 1 as per DIN IEC 25-21-1 Degree of protection (front of the device): IP 54 at closed front cover (only D-version single housing) Vibration test: 0.5 g, 10-300 Hz DOK-TD-MRA1 Rev.A 17

Woodward Manual MRA1 GB 7. Order form Trip circuit supervision Housing (12 TE) 19 - rack Flush mounting MRA1- A D 18 DOK-TD-MRA1 Rev.A

Manual MRA1 GB Woodward Setting list MRA1 Project: Woodward-Job.-No.: Function group: = Location: + Relay code: - Relay function: Password: All settings must be checked at site and should the occasion arise, adjusted to the object/item to be protected. Device coding Function Default settings Actual settings Code plug plugged A and B B A No code plug A und B B A No code plug Threshold value 9V 30V 65V 100V 9V 30V 65V 100V Relay K2 (CB_ON) X Relay K3 (CB_OFF) X Threshold value 16V 38V 80V 140V 16V 38V 80V 140V Relay K1 (Ok) X External Reset X Recommended device coding at different rated voltages and operation modes Function Circuit version A Circuit version B Code plug/ rated voltage A and B B A No code plug A and B B A No code plug 24V DC X X 48V DC X X 60V DC X X 110V DC X X 220V DC X X DOK-TD-MRA1 Rev.A 19

Woodward Manual MRA1 GB Woodward Kempen GmbH Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet www.woodward.com Sales Phone: +49 (0) 21 52 145 216 or 342 Telefax: +49 (0) 21 52 145 354 e-mail: salesemea_pgd@woodward.com Service Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455 e-mail: SupportEMEA_PGD@woodward.com 20 DOK-TD-MRA1 Rev.A