KOBOLD PDA Series Digital Pressure Transmitter

Similar documents
KOBOLD TDA Series Digital Temperature Transmitter

KOBOLD Compact Electronics

TPE 1464 Series Pressure Transducer

NT PRESSURE TRANSDUCER MODELS 4100, 4210, 4130, 4230

Installation and Maintenance Instructions for GC55 Differential Pressure Transducer Version 1.0 5/11

Model 675 DREXELBROOK. Shark Cage Submersible Level Transmitter DATA SHEET. Description. Features. Applications.

HIGH ACCURACY PRESSURE TRANSDUCERS

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2

DRH. Paddle Wheel Flow Sensor

Product Data. Model 675 Shark Cage Submersible Level Transmitter ELECTRONIC PRESSURE MEASUREMENT PRODUCTS DESCRIPTION FEATURES APPLICATIONS

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

IRIDIUM INTELLIGENT MODULAR FLEXIBLE SERIES FLOW CONTROL C1 Configuration Liquid Applications

Instruction Sheet Board Style Low Water Cutoff

DP DP2500 DP0250

NEW product. Large digital pressure sensor 31series. Easily viewable LCD dual displays. High level visibility with 3-color display.

Fusion of electronic pressure sensor and analogue display.

Differential Pressure Transmitter STK336

MPS-32. Pressure Sensors MPS-32 2-Color Panel Mount. Features. Green Display. MPS-32 Programming Options

Series ULT Ultrasonic Level Transmitter

Fusion of electronic pressure sensor and analogue display.

NEW product. Large digital pressure sensor 31series. Easily viewable LCD dual displays. High level visibility with 3-color display.

Installation and Operating Manual FM50 IOM 2-18 DRAFT

Signet 2552 Metal Magmeter Flow Sensors

DPC DPC PRECISION DIGITAL MASS FLOW CONTROLLER WITH MULTI-GAS FUNCTIONALITY

MODEL 8000MP LEVEL SENSOR

Model 601CM. Metal Sealed. Product Features:

Pressure Switch CE40. Digital settings available via IR data communication without actually applying pressure to the unit

Installation and Maintenance Instructions for GC31 Ultra-Compact Digital Pressure Sensor

Operation Manual SRZ Helical Flow Meters

Differential Pressure ( P) Transducer US Patent

DMP 333 DMP 333. Industrial Pressure Transmitter For High Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial

PRESSURE TRANSMITTER

M5100 Heavy Industrial Pressure Transducer

Differential Liquid/Gas Pressure Transmitter

Model SST Slimline Submersible Pressure Transmitter

KUHLMAN INSTRUMENT COMPANY 5000K WARRANTY

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

Pressure sensor For highest pressure applications to 15,000 bar Model HP-2

Users Manual Ocean Sensor Systems Wave Staff III

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

Manual of Electrical Installation for Pressure Probes KS and KS-SIL2 series

1. Installation. 2. Configuration - Operation. 3. Specifications. Safety

EPWR Series. RoHS. Product Description. Available Products. Installation Instructions 01

Explosion-Proof Gauge Pressure Transmitter

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

M7100 Pressure Transducer

JT400 Multivariable Transmitter

RT2Y Compact temperature switch intrinsic safety

DVZ - Vortex Flowmeter and Switch

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5

Zone Pressure Touch (ZPT) Sensor - Standard Range

DPM DPM MULTI PARAMETER - MULTI GAS MASS FLOW METER

Level-Lance Model 5400A

Operating and installation instructions Differential pressure monitor

DRH. Paddle Wheel Flow Sensor

Echotouch, EchoSpan & EchoSwitch Ultrasonic Liquid

Scanner 2000 Steam Mass Flow Transmitter

P027 Series Pressure Transducer Installation & Operation Manual

Operating instructions Electronic pressure sensor. PM205x /01 09/2011

DCT 531. Industrial Pressure Transmitter with RS485 Modbus RTU. Stainless Steel Sensor

Installation and Maintenance Instructions for GC35 Heavy Duty Digital Pressure Sensor Version 1.0 6/06/09

Easy Flow Indicator Magnetisch-Induktiver Durchflussmesser. Type 8024 For Insertion Fittings. Analog Flow Rate Indicator, 1/2"-16"; P=87 PSI

Operating Instructions for Level Switch for Liquids. Model: RFS

ZFM ZFM DIGITAL MASS FLOW METER

Sono-Trak Transit Time Clamp-on Ultrasonic Flow Meter

Sidewinder Pumps Inc. AC Timer/Controller

High Voltage DC Meter

3-step setting 2. 2-Color Display High-Precision Digital Pressure Switch. ZSE30A(F)/ISE30A Series. Added vacuum range.

Digital Indicator Solutions

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

F-1000 DIGITAL PADDLEWHEEL FLOWMETER

MIST Version 2.0 USER S GUIDE. Preliminary Version. INTRODUCTION...2 General Description...2 Models Available...2

CDD4 Duct Carbon Dioxide Transmitter

H290 HUMIDITY TRANSMITTER INSTRUCTION MANUAL

Installation & Operation Manual

Multi-range pressure and differential pressure transmitter

Installation, Operation & Maintenance Instructions / Technical Document

Control IT Booster Pump Controller

VM 6.1. Capacitive Air Gap Measuring Chains User s Manual P/N: M7A-110

Zenith DS9000 Dispensing System

MODEL 245 / 345 DigiComp

Operating Instructions for Low Volume Rotating Vane Flow Meter. Model: DPL-1P... DPL-1V... DPL-1E...

P30-2. Overview. Pressure Transmitter Datasheet. *High Quality* 3 Years Warranty. At a Glance. Function. Application

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

Advanced Test Equipment Rentals ATEC (2832)

KOBOLD Series RCD Installation and Operating Instructions

350 SMART MANOMETER OPERATING INSTRUCTIONS

LMP 308. Separable Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO / 0.

Voltage Output IMPACT MELT PRESSURE TRANSMITTERS IN SERIES TECHNICAL SPECIFICATIONS

S66 Series Electronic Fan Speed Control

Miniaturised pressure sensor Model M-10, standard version Model M-11, version with flush diaphragm

red-y industrial series product information Thermal Mass Flow Meters and Controllers for Gases with IP67 & Ex Protection

Operating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505

SFY Functional Safety Frequency-to-DC Transmitter with Display

Platinum RTD Thermometer MODEL NO

MP 101A HUMIDITY TEMPERATURE PROBE INSTRUCTION MANUAL

Operating Instruction for Turbine-wheel Flow Meter. Model: DRS

PX Series Balances. Quick Start Guide. Please download the user manual from

Transcription:

KOBOLD PDA Series Digital Pressure Transmitter PDA-153 Series User Instructions KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205 Phone (412) 788-2830 Fax (412)-788-4890 www.koboldusa.com

PDA Table Of Contents KOBOLD PDA Series Digital Pressure Transmitter General.............................................. 1 Specifications........................................... 1 Mechanical Installation.................................... 3 Electrical Installation..................................... 4 Operation............................................. 5 Programming Functions................................... 5 Programming Menu Item Descriptions........................ 8 Maintenance........................................... 10 List Of Diagrams Diagram 2.1 Dimensions....................................... 3 Diagram 3.1 Electrical Connections............................... 4 Diagram 5.1 Displays and Controls............................... 5 Diagram 5.2 Programming Functions............................. 5 Diagram 5.3 Sequence to Change a Value......................... 6 Diagram 5.4 Programming Flowchart............................. 7 Diagram 5.5 Start Current and End Current Example................. 9 List of Tables Table 2.1 Part Number Identification............................ 2 FM Rev. 7/15/01

PDA CAUTION: For safety reasons, please read the cautionary information located at the end of the manual, before attempting installation. 1.0 General The KOBOLD PDA Series is a solid state, electronic pressure transmitter which employs a ceramic sensor element as the heart of the sensing system. The ceramic sensing element provides excellent corrosion resistance and very high cycle life with virtually no calibration drift over its service life. The PDA s microprocessor based electronics allow the user to program zero point, transmitter span, dampening and lockout code. In addition to the analog output, the PDA has a digital display for local indication of pressure. 2.0 Specifications Available Measuring Ranges: -30 Hg to 5800 PSIG Display Type: 3 Digit LED Accuracy: ±0.5% of full scale Sensor Element: Piezoresistive ceramic element Operating Temperature Range Process Medium: -4 to 176 F Ambient: -4 to 140 F Overpressure Ratings -30 HG to 1450 PSIG: 2X max range >1450 to 5800 PSIG: 1.5X max range Process wetted parts Sensing Element: Ceramic Connection: 316L stainless steel O-ring: Viton Housing Material: 304 SS Electrical Data Output Type: 4-20 ma, 3 wire Max. Loop Burden: 500 ohms Response Time: 50 msec. Power Supply Requirement: 24 VDC ±20%, 80 ma Max. Electrical Connection: M-12, Micro-DC connect male Electrical Protection: NEMA 4X/IP 65 FM Rev. 7/15/01

PDA 2 Table 2.1 Part Number Identification PDA = Compact Electronic Pressure sensor 153 = 4-20 ma, three-wire Output Type N2 = 1/4 NPT Fitting N4 = 1/2 NPT Available Measuring Ranges H315 = -30 to 0 Hg P025 = 15 PSIG P045 = 30 PSIG P055 = 50 PSIG P065 = 100 PSIG P075 = 150 PSIG P085 = 200 PSIG P095 = 350 PSIG P105 = 600 PSIG P115 = 1000 PSIG P125 = 1450 PSIG P135 = 2300 PSIG P145 = 3600 PSIG Range P155 = 5800 PSIG E = Special Range Accessories Part# 807.002 = Mating connector w/ 10 feet of cable PDA - 153 - N4 - P065 Example FM Rev. 7/16/01

3 PDA Diagram 2.1 Dimensions 1.56 0.93 2.0 N1.75 3.2 1.0 4.25 N1.25 0.47 1/2 or 1/4 NPT 3.0 Mechanical Installation The following general installation instructions and precautions must be followed to insure proper, reliable operation: 1. Select a suitable location on the piping system for installation. Installation in a location where sediments can collect in the pressure sensing port (such as the underside of a horizontal piping run) will cause sluggish or faulty operation. 2. The ambient temperature range which the sensorsensor can withstand is -4 F to +140 F. If the sensor is located outdoors in a cold environment the sensor must be protected from excessively cold temperatures with insulated heat tracing or by other suitable means. In hot environments the sensor should be located in an area where the ambient temperature does not exceed 140 F. 3. If installing in a liquid process with pressure spikes and/or pressure pulsations, install the sensor with a suitable pressure snubber or damage to the pressure sensing element may result. FM Rev. 7/15/01

PDA 4 4.0 Electrical Installation The following electrical installation instructions and precautions must followed to insure proper sensor and analog output operation. Failure to follow these instructions may result in irreparable damage to the sensor: 1. This device requires a power supply rated at 24 VDC ±20%. The current requirement is 80 ma maximum. Ensure that the power supply used is capable of providing this current and voltage. 2. In order to minimize electromagnetic noise pickup, a jacketed instrument and control cable with shield should be used. The shield should be connected to the power system earth ground at one end of the cable only. Diagram 4.1 Electrical Connections Typical Wiring Optional Mating Connector Not Connected -DC 2 3 1 4 + DC Supply 24 VDC ±20% 4-20 ma Out Brown = 1 = +DC White = 2 = Not Connected Blue = 3 = -DC Black = 4 = 4-20 ma out 1 4 PDA-153... 3 +DC 4-20 ma out + Input Device - -DC FM Rev. 7/16/01

5 PDA 5.0 Operation Diagram 5.1 Displays and Controls Hold for 3 seconds to enter programming menu. Press to step through menu. Press to enter a menu programming branch, or change a display value 5.1 Programming Functions The PDA digital pressure transmitter is programmed via membrane push-buttons on the faceplate of the device as shown in the following figure. Diagram 5.2 Programming Functions During Normal Operation : Press for 3 Sec to Enter Setup Mode : During Setup Mode : Next Step : Change Values Press 3 sec Or for 20 sec Press no buttons Exit Setup FM Rev. 7/15/01

PDA 6 5.1.1 Changing Values in Setup Mode When in the Setup Mode the actual values of zero, span, dampening and other functions are adjusted as required by the user. From the main menu (e.g. Change Code CCo ), press the button to adjust that functions value. The following diagram shows the sequence of steps required to change a value. Diagram 5.3 Sequence to Change a Value Press to get from the main menu Set the first digit Set the second digit Set the third digit reset value Set the decimal point location or Save Value Speichern FM Rev. 7/16/01

7 PDA 5.1.2 Programming Flow Chart Diagram 5.4 Programming Flowchart TO BE ADDED IN FUTURE REVISION FM Rev. 7/15/01

PDA 8 5.2 Programming Menu Item Descriptions After the Button is depressed for three seconds to enter the setup mode, and the lockout code is entered (if lockout is enabled), the programming menu is accessed. Diagram 5.4 provides a flowchart of the programming menu. Section 5.1.1 and diagram 5.2 and 5.3 provide details on how to change the value of each menu item parameter. The following is a detailed description of each menu item. 5.2.1 Cod - Code If the lockout feature was enabled during a prior setup, the user code which was selected at that time must be entered. Section 5.1.1 Changing Values in Setup Mode on page 6 provides steps required to enter the value. 5.2.2 S - C - Start Current This menu item allows the user to input the pressure which corresponds to the current transmitter s zero point (4 ma or 0 ma point). Typically this value is zero (i.e. zero PSIG = 4 ma). Any number between -199 and 999 within the measuring range of the devise can be entered. Additionally, a decimal point can be added if desired. To perform the Start Current adjustment, if desired, use the button to get to the S - C menu item. Then press the button and hold down for 7 seconds to enter the S - C branch. After entering, Section 5.1.1 Changing Values in Setup Mode on page 6 provides steps required to change a value. The transmitter output will remain at its zero point (4 ma or 0 ma) until the system pressure rises above the Start Current setting. 5.2.3 E - C - End Current This menu item allows the user to input the pressure which corresponds to the current transmitter s maximum span (20mA point). The device is preset at the factory with this value set to the transmitters full scale measuring range. Any number between -199 and 999 within the measuring range of the device can be entered. Additionally, a decimal point can be added if desired. To perform the End Current adjustment, if desired, use the button to get to the E - C menu item. Then press the button and hold down for 7 seconds to enter the E - C branch. After entering, Section 5.1.1 Changing Values in Setup Mode on page 6 provides steps required to change a value. 5.2.4 SCS - Start Current Select This menu item allows the user to select a transmitter zero point of either 0 ma or 4 ma. A zero point of 4 ma is preset at the factory. To change this setting, if desired, use the button to get to the SCS menu item. Then press the button and hold down for 7 seconds to enter the SCS branch. Use the button to change the value. Use the button to accept the value. Use the button to proceed through the programming menu FM Rev. 7/16/01

9 PDA Example: A PDA series pressure transmitter is purchased with a measuring range of 0-150 PSIG (The Max. measuring range can be determined by the model number code, or by applying power to the device. When power is first applied the Max. measuring range flashes on the display for 3 seconds.) From the factory, the Start Current (S - C) value is preset at 00.0 and the End Current (E - C) value is preset at 150. The Start Current Select (SCS) value is set at 4 for 4 ma. It is desired to field program the transmitter s output such that the zero point is at 10 PSIG (S - C adjusted to 10.0) and the span point is at 100 PSIG. (E - C adjusted to 100). The transmitter output Vs. pressure for the factory settings and the field modified settings are shown in Diagram 5.5 Figure 5.5 Start Current and End Current Example Current (ma) Factory Setting Field Setting 20 4 0 10 100 150 Pressure (PSIG) 5.2.5 Filt - Filtering This menu item allows the user to average the measured output over 1, 2, 4, 8, 16, 32 or 64 samples. Section 5.1.1 Changing Values in Setup Mode on page 6 provides steps required to change a value. Adding filtering provides a more stable display and output for systems in which pressure pulsations are a problem. The larger the number of samples the more stable the display and output. A Filt value of 1 shuts off the filtering. When filtering is being used, the PDA series employs an integrated overshoot function which detects any overshoot above 6.25% and processes that measured value without filtering. This feature allows the sensorsensor to differentiate between pulsations and actual system pressure changes and process the pressure change signals without filtering. This greatly enhances the sensor s response time when the filtering function is being used. FM Rev. 7/15/01

PDA 10 5.2.6 S -A - Zero Adjust This menu item allows the user to zero the pressure sensing element if desired. The ceramic pressure sensing element used by the PDA series takes about 15 minutes for the zero to stabilize after power is applied. Therefore if zeroing is desired, for best results wait for at least 15 minutes after power is applied to do so. To perform the zero adjust, use the button to get to the S - A menu item. Then press the button and hold down for 7 seconds. The display will flash 000. Then press the button to continue through the setup menu. 5.2.7 CCo - Change Code This menu item allows the user to set a pass code which will lock out the programming functions. This protects the device from un-authorized access to the setup menu. Section 5.1.1 Changing Values in Setup Mode on page 6 provides steps required to change a value. The code can be any value from 000 to 999. A code of 000 disables the lockout function. A value other than 000 will require entry of that code to access the setup menu. 6.0 Maintenance The PDA series pressure sensorsensors have no moving parts therefore are virtually maintenance free. Depending on the type of media, the pressure sensing port may become clogged over time. Sluggish response to changes in system pressure would be evidence of this. If clogging occurs, remove the sensor from the system and clean the pressure sensing port using compressed air or a water stream. If clogging occurs frequently, installation of a diaphragm seal should be considered. FM Rev. 7/16/01

CAUTION PLEASE READ THE FOLLOWING WARNINGS BEFORE ATTEMPTING INSTALLATION OF YOUR NEW DEVICE. FAILURE TO HEED THE INFORMATION HEREIN MAY RESULT IN EQUIPMENT FAILURE AND POSSIBLE SUBSEQUENT PERSONAL INJURY.

PDA 12 User's Responsibility for Safety: KOBOLD manufactures a wide range of process sensors and technologies. While each of these technologies are designed to operate in a wide variety of applications, it is the user's responsibility to select a technology that is appropriate for the application, to install it properly, to perform tests of the installed system, and to maintain all components. The failure to do so could result in property damage or serious injury. Proper Installation and Handling: Use a proper thread sealant with all installations. Take care not to overtighten the fittings. Always check for leaks prior to system start-up. Wiring and Electrical: Section 2.0, Specifications and Section 4.0, Electrical Connections, provide the voltage and current limitations and the wiring for the various sensor types. The sensor electrical ratings should never be exceeded. Electrical wiring of the sensor should be performed in accordance with all applicable national, state and local codes. Temperature and Pressure: Section 2.0, Specifications, provides the temperature and pressure limits for each model. Operation outside these limitations will cause damage to the unit and can potentially cause personal injury. Fluid should never be allowed to freeze inside the sensor. Material Compatibility: Make sure that the model which you have selected is chemically compatible with the application liquids. While the meter is liquid and spray resistant when installed properly, it is not designed to be immersed. Flammable, Explosive and Hazardous Applications: The PDA series is not an intrinsically safe or explosion proof design. They should not be used in installations in which an instrinsically safe or explosion proof design is required. Make a Fail-safe System: Design a fail-safe system that accommodates the possibility of device or power failure. In critical applications, KOBOLD recommends the use of redundant backup systems and alarms in addition to the primary system. FM Rev. 7/16/01