Version Action Author Date

Similar documents
IQ Home Modbus-RTU Master

VISY-Command. Technical Documentation. with Modbus Protocol. Edition: Version: 1 Art. no.:

Modbus Protocol For FTS/FTM 3x&8x

User Module. Modbus TCP2RTU. Application note

[ 公司地址 ] Modbus Protocol. For THS/THM 30X&80X_Temp.&Humididy & THS8X/THM8X_Dew Point Series V7.0

COMMUNICATION MODBUS PROTOCOL

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM102(1739) For 4511 devices from ser. no:

Modbus Protocol For TGP03 / THP03

B Interface description 12.01/

Conto D2 COMMUNICATION PROTOCOL CONTENTS 1.0 INTRODUCTION

Optidrive VTC Modbus RTU Register Map

TORRIX RS485. Technical Documentation. with MODBUS Protocol. Edition: Version: 2 Art. no.:

SC2004MBS 20x4 Characters MODBUS RTU Slave LCD

Modbus Protocol For PMX / PXM3X

CE4DMID01 COMMUNICATION PROTOCOL CONTENTS 1.0 INTRODUCTION

Interface design document MODBUS Protocol. Ab s t r a c t Description of the MODBUS implementation for the Modbus I/O board

For more information Contact with details of the application.

TORRIX RS485. Technical Documentation. with MODBUS Protocol. Edition: Version: 3 Art. no.:

EMS_ _Measure_MonoPh_R_2P_ModbusTable_LG_EN_v1.01.xlsx

FnIO S-Series. FnIO MODBUS Adapter Specification Rev 1.00 NA-9473 (MODBUS/RS485) Page 1 of 30. NA-9473 (MODBUS/RS485) Adapter

Modbus on tsense. Table of contents:

Rev 2.00 NA-9286 (EtherCAT) Page 1 of 31. FnIO S Series: NA EtherCAT Adapter

TECH TIP. Tritex Modbus Protocol Specification

GIGAVAC Contactors J1939 Protocol

Modbus. Interface. Description ISO 9001:2008

PRE32 RS232 protocol v1.21 Tomas Andersson

IF96017 MODBUS COMMUNICATION PROTOCOL

Data Communication Protocol Host Computer to FAS-A

Modbus User Manual APPLIED MOTION PRODUCTS, INC. Modbus is a registered trademark of Schneider Electric, licensed to the Modbus Organization, Inc.

3GV M Modbus RTU Register Map

T7 Modbus Communication User Guide

Elotech Standard Protocol. for Single R8200 SC

FnIO S Series: NA MODBUS/TCP(UDP) Adapter. with Two RJ-45

BQ & BQ370-01N MODBUS ANALOG INPUT DEVICE USER MANUAL

DMTME Multimeters. Communication protocol. Technical specification V1.2 ABB

VPGate Manual PROFIBUS to serial

MODBUS Message Protocol MODEL FT3

MODBUS MESSAGE PROTOCOL FOR MODEL FT2 THERMAL MASS FLOWMETER & TEMPERATURE TRANSMITTER

MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1a CONTENTS

NA-9171 / 9173 (RS-232) (RS-485) User Manual. MODBUS Adapter CREVIS Co.,Ltd. Version FnIO MODBUS Adapter NA-9171, NA-9173 FnIO S-Series

JUMO ctron 04/08/16. Compact controller with timer and ramp function. B Interface Description Modbus /

EMDX3 Multifunction meter Cat No ModbusTable LGR EN v1.01.xls

JDICON 1000 JDICON B Interface Description 3.99/ Universal Process Controller. Universal Profile Controller

Venstar Thermostat Adapter

S u p p l e m e n t TQS3 MODBUS. Description of product modification with MODBUS RTU. 31. March 2008 w w w. p a p o u c h.

RS232-ADC16/24 Manual

Beijer Electronics has no obligation to supply the holder with updated versions.

COMMUNICATION MODBUS PROTOCOL

Modbus Register Map: Galaxy 5000 & Galaxy 5500

DULCOMETER Multi-parameter Controller dialog DACa

AFRecorder 4800R Serial Port Programming Interface Description For Software Version 9.5 (Last Revision )

General Monitors S5000 Modbus Specification. Order No.: MANS5000M/00. MSAsafety.com

Modbus on S8. Modbus is a simple, open protocol for both PLC and sensors. Details on Modbus can be found on

The power supply input should be connected via a rated VAC/VDC power supply and properly isolated from the line voltage.

COMMUNICATION MODBUS PROTOCOL MF96001 / 021 NEMO 96HD

Modbus Manual Version Modbus Manual for Clean Room Panel CRP5

Modbus on S8. Modbus is a simple, open protocol for both PLC and sensors. Details on Modbus can be found on

MCW Application Notes 24 th February 2017

MODBUS Protocol. The ecode Encoders contain both single register (16 bit) and double register (32 bit) values.

M2M/DMTME Instruments Communication protocol. Technical specification V.2.1 2CSG445011D0201

Protocol VIT5. Communications RS485. Version 1.0. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.Up ENTER. Pg.

KCD-HP. KCD-HP200x, 300X. [Figures] Top : 1% Sensor probe Bottom left : 10% / 20% Sensor probe Bottom right : Holding bracket(optional) Measurement

NXIO S Series: NXIO-MNA232, MNA485. MODBUS Adapter

This document is for information purposes only and is subject to change without notice.

User Manual version 1.04 TLM8 COMMUNICATION PROTOCOLS

JUMO Quantrol LC100/LC200/LC300

Golander Peristaltic Pump MODBUS Communication Instruction

RS485 MODBUS Module 8AO

Modbus Register Map: Galaxy 300

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

Modbus Manual Version Modbus Manual for PF4/5

Modbus on SenseAir S8

Modbus on CO 2 Engine and esense

ENGLISH ENGLISH ENGLISH ENGLISH

Emotron Fieldbus HMS Gateway Anybus Communicator

Sommario. COMMUNICATION PROTOCOL PR 150 Rev. A 31/01/2018 Pag 1 Multifunction Firmware NEMO 96 EA ModBus

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

Winsonic MODBUS Remote IO user manual Rev. 1.0

Input Channels: 4 differential or four single-ended. Address / Baud rate / range configurable by the user

KL4001, KL4002 and KL4004

INTELLIS. Modbus Direct Network Monitor

1. Implemented CM11 protocol

This document is for information purposes only and is subject to change without notice.

SOFTWARE FUNCTIONAL REQUIREMENTS SPECIFICATION. Athena DeviceNet Interface Module Revision /26/2001

Specification E2 Interface

Host Controller Systems. Instruction Manual

Mapping Modbus Registers to BACnet Objects

MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b3 CONTENTS

In-Situ Modbus Communication Protocol Version 5.8

Modbus Map: Conext System Control Panel (SCP) Device

NMEA2000 to Modbus Gateway Part No User Manual

Modbus TCP + Ethernet EN

KL Channel Resistor Bridge Input Terminal Configuration Instructions

Gastrack Gas Analyser

ENGLISH ENGLISH ENGLISH ENGLISH

This command can be used for reading the current value of one or several input channels, according to the table below.

MTR-4. C8 Command to MODBUS Bridge User Manual F-1, No. 631, Chung Der Road, Sec 1, Taichung Taiwan.

MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b3 CONTENTS

C192PF8-RPR. Power Factor Manager & Reactive Power Regulator Reference Guide. Modbus. Communications Protocol. BG0348 Rev. A1

E2 Modbus RTU Register Map

Transcription:

Version Action Author Date 1.0 Initial document KP 25.08.2013 1.1 Document review, description and register update GP 26.08.2013 1.2 Status bits, current noise floor GP 29.08.2013 1.3 Using EG100 as a Modbus TCP/RTU bridge GP 28.10.2013 1.4 Separate document for each device GP 07.07.2014 1.5 Brand changed to etactica, names of meters changed, the command register was updated. ÁH 20.06.2016

All etactica hardware devices are interconnected using the Modbus/RTU protocol over halfduplex RS485 serial interface. For a complete etactica installation, the etactica gateway EG- 100 is always the Modbus master and all other measurement devices are pre-configured as Modbus slaves. The etactica measurement devices are as follows: The etactica Power Meter, EM-xxx The etactica Current Bar, EB-2xx The etactica Current Meter, ES-xxx The etactica measurement devices implement a register table with both configurable and readonly parameters. These parameter values are accessible via standard Modbus requests. The etactica measurement devices can be part of any 3 rd party data collection installation that supports Modbus/RTU. This means that a 3 rd party Modbus master can be used instead of the etactica gateway EG-200. For this purpose, you can either connect directly via Modbus/RTU over RS485 or via Modbus/TCP using the EG-200 as a standalone Modbus TCP/RTU bridge. To use 3 rd party data collector, simply configure your Modbus Master for the etactica devices as described in this document and note that: You must allow up to 500 msec for response The minimum read-request interval from the Modbus Master, on each device, must be set to 100 msec or longer The Modbus protocol specification: http://modbus.org/docs/modbus_application_protocol_v1_1b3.pdf All etactica hardware devices have default settings for the RS485 serial interface: 19200 baud rate 8 data bits Even parity 1 stop bit These settings are editable by writing to given registers, limited to devices with firmware version 3.2 and above. All etactica hardware devices support the following Modbus function codes: 0x03 Read Holding Registers 0x10 Write Multiple Registers

Unless otherwise noted, each register value is an unsigned 16-bit integer. Signed values are regular 2's Complement Signed. According to the Modbus protocol specification the Big-Endian representation of both data and addresses is used. This means that the most significant byte (MSB) is sent first. The first data entry in the Modbus table for every etactica measurement device, is at data address 0x2000 (the vendor ID) or 8192. This is not 40001 or 0x9C41, as you might expect for accessing the first entry of analog holding registers. If you are using one of many Modbus software drivers (PC or PLC masters) that expect 40001 as the first entry for holding registers, you need to remember to add the offset of 8192. See these pages for more of an explanation: The Register Map below lists the data addresses to use when forming the Modbus request (ADU message format) to each of the etactica measurement devices. As specified in Section 4.2 of the Modbus Application Protocol Specification, all values are stored in Big Endian, MSB first order. All register addresses in this document are "PDU Addresses" as per Section 4.4. In other words, the first register (Vendor ID) is accessed at register address 0 (plus the offset of 8192 (0x2000)). Note that some Modbus applications refer to this first register as "Modbus Data Model" register 1, which is then at address 0. Values marked as 32bit, are also stored in Big Endian, MSB first, as would be implied by a sensible reading of section 4.2. 64 bit values are also stored Big Endian, MSB first.

Read a 16-bit value, Line frequency on EM-xxx, data address 0x200F. PDU Function code Starting address 0x03 0x200F Quantity of registers 1 PDU message 0x03 0x20 0x0F 0x00 0x01 Final Value Value Stored Register high byte Register low byte 50.42 Hz 50420 (Register stores mhz) 0xC4 0xF4 Read a 32 bit value, Current on Channel 0 on ES-xxx or EB-xxx, data address 0x2016. Register 0 = 0x2016, Register 1 = 0x2017 PDU Function code Starting address 0x03 0x2016 Quantity of registers 2 PDU message 0x03 0x20 0x16 0x00 0x02 Final Value Value Store Register 0 high Register 0 low Register 1 high Register 1 low 320.123 Amps 320123 (Value in ma) (0x4E27B) 0x00 0x04 0xe2 0x7b

Below you find the registers, common to all etactica measurement devices. Register Address R/W Description 0x2000 R Vendor id (0x524d) 0x2001 R Product id 0x2002 R Firmware version 0x2003 R Serial number bytes 0..1 0x2004 R Serial number bytes 2..3 0x2005 R Serial number bytes 4..5 0x2006 R/W Command 0x2007 R Total register count 0x2008 R/W Serial communication settings 0x2009 R/W Modbus slave ID 0x200A 0x200B 0x200C 0x200D

The Modbus register map for the family of etactica sensor boxes. Register Address R/W Description 0x200E R Temperature 0x200F 0x2010 R/W total number of breakers 0x2011 R/W disabled breakers (bitmap) 0x2012 0x2013 0x2014 0x2015 0x2016 R current breaker 0 (ma) (31..16) 0x2017 R current breaker 0 (ma) (15..0) 0x2018 R current breaker 1 (ma) (31..16) 0x2019 R current breaker 1 (ma) (15..0) 0x201A R current breaker 2 (ma) (31..16) 0x201B R current breaker 2 (ma) (15..0) 0x201C R current breaker 3 (ma) (31..16) 0x201D R current breaker 3 (ma) (15..0) 0x201E R current breaker 4 (ma) (31..16) 0x201F R current breaker 4 (ma) (15..0) 0x2020 R current breaker 5 (ma) (31..16) 0x2021 R current breaker 5 (ma) (15..0) 0x2022 0x2023 0x2024

Register Address R/W Description 0x2025 0x2026 0x2027 0x2028 0x2029 0x202A 0x202B 0x202C 0x202D 0x202E 0x202F 0x2030 0x2031 0x2032 0x2033 0x2034 0x2035 0x2036

The command register is a 16 bit value. You use this register to permanently store new configuration settings in EEPROM or reload factory default. The meaning of each bit and bit combination is described in the table below. Bit # Description 15 14..6 unused 5 "Frequency mode", Enable this bit to have a 60 Hz digital filter, or leave it at 0 to keep the 50 Hz digital filter.(just for EB and ES with firmware version 3.14 or higher. ) 4 3 LED Control State (1 == LED on, 0 == LED off) 2 LED Control State Valid (1 == bit 3 is valid, 0 == bit 3 is ignored) 1 Enable this bit to reload default device configuration to RAM (use in conjunction with bit 0 to reset EEPROM to factory defaults) 0 Enable this bit to store current configuration to EEPROM and restart device The serial communication register is a 16 bit value. It allows you to edit the protocol settings for the RS485 serial interface. Take care modifying these settings. It can be tedious to rediscover what the settings are, for an unknown device. Default settings for all devices is: 19200-8 - Even - 1

Firmware Limitation The editable feature is only available for devices with firmware version 3.2 or above. After writing a value to this register, you must write to the Command register (0x2006) to store settings in EEPROM and reinitialize the device. This will make the new settings take effect. Bit # Description 15..12 Stop Bits (normally 1, 2 is also allowed) 0001 (0x01) : 1 stop bit 0010 (0x02) : 2 stop bits 11..8 Parity (0: None, 1: Odd, 2: Even) 0000 (0x00) : Parity none 0001 (0x01) : Parity odd 0010 (0x02) : Parity even 7..0 Baud rate value (See table below) Values to write as the lowest byte in this register that represent pre-defined baud rates. Lowest Byte of 0x2008 Baud Rate 0000 (0x00) default (19200 at present) 0001 (0x01) 600 0010 (0x02) 1200 0011 (0x03) 2400 0100 (0x04) 4800 0101 ( 0x05) 9600 0110 (0x06) 19200 0111 (0x07) 38400 1000 (0x08) 57600 1001 (0x09) 115200

Contents of register 0x2008 Description 0x1200 Factory Default, 1 Stop bit, Even Parity, Default Baud Rate (19200) 0x1005 0x1209 0x1101 0x0044 1 Stop Bit, No Parity, 9600 Baud 1 Stop Bit, Even Parity, 115200 Baud 1 Stop bit, Odd Parity, 600 Baud Don't do this! (Unexpected values will be converted to 1 Stop bit, No Parity, 115200) The Modbus slave ID register, is a 16 bit value. It is a configurable register where you can modify the default slave ID for your device. Only the lower byte for this 16 bit value is valid for the slave ID. Take care to preserve the upper byte as is. According to the Modbus protocol, it is only allowed to use addresses from 1-247. Bit # Description 15..8, do not modify contents 7..0 Modbus slave ID (values from 1 to 247)