SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION

Similar documents
Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

B. System Design and Performance Requirements

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

SECTION SURGE PROTECTIVE DEVICES

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

1. This section describes the materials and installation requirements for surge protective devices (SPD) for the protection of all AC electrical

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

Liebert TVSS: The First Line of Defense - Product Overview. Jim Tiesi

TDX Series. Transient Discriminating TM TVSS

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

SECTION PANELBOARDS

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

Specifications, Installation, and Operating Instructions

Emery County Senior Center Green River 06/07

White Paper October 2009

GE Digital Energy. Power Quality

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation

PDI Modular Compact Remote Power Panel

SECTION DISTRIBUTION SWITCHBOARDS

Surge Protective Devices. STV100K Series. Instruction Manual

SECTION VARIABLE FREQUENCY MOTOR CONTROLLERS (VFD)

Surge Protective Devices. STV100K Series. Instruction Manual

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect.

THE SURGE PROTECTION SOLUTION

The City of Winnipeg Dry Type Transformers up to 600 V Primary Section Bid Opportunity No Page 1 of 2

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

ZoneMaster Series Surge Protection Devices

SECTION WIRING DEVICES PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

BSPD Surge Protective Devices

Protect your facility from the destructive effects of power surges with a fully

Surgelogic Surge Protective Device I-Line Plug-On Unit Series

Internal Modular SPDs

SECTION ELECTRIC METERING

White Paper Surge Protective Devices in Automatic Transfer Switches

Innovative Technology TVSS Products

SECTION ( ) LIGHTING CONTROL PANELBOARD

AC Surge Protection Devices

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

1510 MOTOR CONTROLLERS

I-Line SPDs Square D TM Internally Mounted Surge Protective Devices

SECTION WIRING DEVICES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Powerware TVSS (Transient Voltage Surge Suppression) ZoneMaster, ZoneSentinel, ZoneDefender

Total Home Surge Protection for Point-of-Entry. FirstSurge TM. User Manual - Canada (English)

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD)

Secondary Surge Arrester Instruction Manual Page 1 of 5

US Catalog March Surge protective devices (SPDs) UL range

Surge Protection Systems Performance and Evaluation

C. New or replacement products installed in existing facilities shall be consistent with existing equipment.

SECTION DISCONNECT SWITCHES

Clipper Power System Visor Series

SECTION SWITCHBOARDS

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

SECTION 16450: NON-AUTOMATIC TRANSFER SWITCH / QUICK CONNECT GENERATOR SWITCHBOARD <S> <OM>

TransGuard. Electrical Transient Suppression Filter Systems. Installation, Operation and Maintenance Manual PN ,

MIL STD 220a (50 Ohm) Model Ordering: 400LS - 277Y - DS - UFP - MX

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

SECTION WIRING DEVICES

TVSS Series STABILINE Transient Voltage Surge Suppressors

GE TR7000 Series Wall Mounted Surge Protective Device (SPD)

Always "On" UPS Systems Inc. USER MANUAL

Eaton s SPD Series for integration into electrical distribution equipment

PowerPak 2 Power Distribution Unit. Flexible. Configurable. Intelligent. Safe.

SECTION WIRING DEVICES

White Paper Surge Current Characteristics: 570 Hybrid Surge Protective Device

Application Techniques CENTERLINE 2100 Motor Control Centers

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

Surge & Filter Protection Addressing your industrial power quality needs.

MICHIGAN DEPARTMENT OF TRANSPORTATION

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A.

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower.

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Surge Protective Devices (SPD)

Hubbell Surge Protective DeviceS

MASTERPLAN. TransGuard. Electrical transient suppression filter systems

Square D Homeline Load Centers and Circuit Breakers. Engineered for value

LIGHTNING AND SURGE PROTECTION

Surgelogic. Surge Protective Devices (SPDs) Residential. Catalog 6671CT9701R08/

Installation Notes TII Model 341 Protector

Instruction Manual IM E Table of Contents

White Paper Avoiding SPD Procurement Errors

Specifications 1 Installation Procedures 2 Wiring Diagrams 3 Installation Checklist 5 Maintenance 5 Warranty Information 6 Material Return Policy 6

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

SECTION WIRING DEVICES

1.2. Loadcenters and Circuit Breakers. Contents. Overview. Type BR Loadcenters and Circuit Breakers. Product Selection Guide.

Surge Protection for Surveillance Systems

Transcription:

SECTION 16709 TRANSIENT VOLTAGE SURGE SUPPRESSION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Transient Voltage Surge Suppression (TVSS) devices, also known as Surge Protective Devices (SPDs), for the protection of AC electrical circuits and electronic equipment from the effects of lightning induced transients, other externally generated transients, and internally generated transients. 1.02 REFERENCES A. ANSI/IEEE: 1. C62.33-82(89) Standard Test Specifications for Varistor Surge-Protective Devices. 2. C62.41-91 Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits. 3. C62.45-87 Guide on Surge Testing for Equipment Connected to Low-Voltage AC Power Circuits. 4. 142-82 Recommended Practice for Grounding of Industrial and Commercial Power Systems (IEEE Green Book). B. Underwriters Laboratories (UL): 1. UL 1449 Standard for Safety, Transient Voltage Surge Suppressors. 2. UL 1283 Electromagnetic Interference Filters. C. National Fire Protection Association (NFPA): 1. NFPA 70 National Electrical Code. 2. NFPA 75 Standard for the Protection of Electronic Computer/Data Producing Equipment. 3. NFPA 780 Lightning Protection Standard. D. Federal Information Processing Standards 94 (FIPS PUB 94). E. National Electrical Manufacturer s Association LS-1, 1992 (NEMA LS-1). Project No. SPECIFICATION GUIDELINES 16709-1

1.03 QUALITY ASSURANCE A. The manufacturer shall submit a written statement indicating that a factory authorized representative inspected the installation. The installing contractor shall submit a checkout memorandum to the manufacturer indicating the date the equipment was placed into service and the actual method of installation. Submit three copies to the specifying engineer. B. All SPDs for service entrance, distribution, and branch circuit protection within a facility shall be provided by a single manufacturer. 1.04 WARRANTY A. The SPD and supporting components shall be guaranteed by the manufacturer to be free of defects in material and workmanship for a period of 5 years from the date of substantial completion of service and activation of the system to which the suppressor is attached. B. An SPD that shows evidence of failure or incorrect operation during the warranty period shall be repaired or replaced at no expense to the Board including labor and materials. Since "Acts of Nature" or similar statements typically include the threat of lightning to which the SPD shall be exposed, any such clause limiting warranty responsibility in the general conditions of this specification shall not apply to this section. The warranty shall cover the entire device, not just the modules. C. The installation of SPDs in or on electrical distribution equipment shall in no way compromise or violate equipment listing, labeling, or warranty of the distribution equipment. 1.05 SUBMITTALS A. The transient voltage surge suppression submittals shall include, but not be limited to, the following information: 1. Data for each suppressor type indicating conductor sizes, conductor types, and connection configuration and lead lengths. 2. Manufacturer s certified test data indicating the Project No. SPECIFICATION GUIDELINES 16709-2

ability of the product to meet or exceed requirements of this specification. 3. Drawings, with dimensions, indicating SPD mounting arrangement and lead length configuration, and mounting arrangement of any optional remote diagnostic equipment and assemblies. 4. List and detail protection systems such as fuses, disconnecting means, and protective materials. 5. SPD wiring, bonding, and grounding connections shall be indicated on the wiring diagrams for each system. Include installation details demonstrating mechanical and electrical connections to equipment to be protected. 6. If requested, a sample of each suppressor type shall be submitted for use in testing and evaluation. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Transient Voltage Surge Suppression: 1. Advanced Protection Technologies, Clearwater, FL. 2. Atlantic Scientific. 3. Diversified Technology Group (DITEK). 4. EDCO. 5. Hubbell-Kellems, Milford, CT. 6. Intermatic, Spring Grove, IL. 7. LEA International by Power Logics, Apollo Beach, FL. 8. Transtector, Hayden Lake, ID. 2.02 PERFORMANCE A. General: 1. SPDs shall be listed according to UL 1449 Standard for Safety, Transient Voltage Surge Suppressors, and UL 1283, Electromagnetic Interference Filters. 2. There shall be 7 modes of protection: 3-modes (Line-to- Ground), 3-modes (Line-to-Neutral), and 1-mode (Neutral-to-Ground) for a 3-phase, 4-Wire plus ground voltage system. (Line-to-Neutral-to-Ground is not an acceptable substitute for Line-to-Ground). 3. The UL 1449 Clamping Voltage for the following configurations shall not exceed the following: Project No. SPECIFICATION GUIDELINES 16709-3

VOLTAGE CONFIGURATION L-G L-N N-G 120/208V 400V 400V 400V 277/480V 800V 800V 800V 4. The unit shall be UL 1283 listed as an electromagnetic interference filter. Standardized insertion loss data shall be obtained using MIL-STD E220A 50W insertion loss methodology. Minimum insertion loss shall be as follows: FREQUENCY[MHz] INSERTION LOSS[dB] 0.1 34 1.0 51 10.0 54 100.0 48 5. SPDs shall use a separate path to building ground, the equipment safety ground is not to be used as a transient ground path. 6. SPDs shall be constructed using MOV based modules. The SPD shall have a response time of less than one nanosecond with 6 inches or less of connected lead length for any individual protection mode. 7. Each MOV contained within a current diversion module shall be individually fused (component level safety fusing). For the assurance of safety purposes, this feature shall be a standard design feature and not an optional feature of the product. The individual component level fusing shall allow a reduction of protection rather than an automatic complete loss of protection. 8. The maximum continuous operating voltage (MCOV) of all components shall not be less than 125 percent for a 120V system and 115 percent for 220, 240, 277, and 480V systems. B. Service Entrance Protection: 1. The SPD for this location shall be referred to as [TVSS Type 1] on project drawings. 2. The service entrance TVSS equipment shall meet or exceed the minimum performance criteria as follows: a. The SPD shall be by, model, or accepted equivalent. b. The single-impulse surge-current rating shall be a minimum of Amps/phase. Project No. SPECIFICATION GUIDELINES 16709-4

c. SPD shall be provided with an integral fused disconnect. Switches shall have a fault withstand rating equal or greater than the AIC rating of the equipment being protected. The disconnect switch shall have an interlocking rotary type safety switch that turns power off to the device upon opening the enclosure for safe inspection and/or module replacement. d. Visual Indication of proper SPD connection and operation shall be provided both on the modules and redundant on the front door of the enclosure. The indicator lights shall indicate which phase as well as which module is operational. SPD that require a separate diagnostic test kit to determine proper module operation must be provided. e. SPD shall incorporate copper bus bars for the surge current path. Small round wiring or plug-in modules are not acceptable. Field-replaceable surge-current diversion modules shall be bolted to the bus bars for reliable low impedance connections. f. The enclosure type shall be rated NEMA 12. C. Distribution Panel Protection: 1. The SPD for this location shall be referred to as [TVSS Type 2] on project drawings. 2. The distribution panel TVSS equipment shall meet or exceed the minimum performance criteria as follows: a. The SPD shall be by, model, or accepted equivalent. b. The single-impulse surge-current rating shall be a minimum of Amps/phase. c. Visual indication of proper SPD connection and operation shall be provided both on the modules and redundant on the front door of the enclosure. The indicator lights shall indicate which phase as well as which module is operational. d. SPD shall incorporate copper bus bars for the surge current path. Small diameter round wiring and the use of plug-in modules is not acceptable. Surge current diversion modules shall use bolted connections to the bus bars for reliable low impedance connections. e. The enclosure type shall be rated NEMA 12. D. Subpanel Protection: Project No. SPECIFICATION GUIDELINES 16709-5

1. The SPD for this location shall be referred to as [TVSS Type 3] on project drawings. 2. The subpanel TVSS equipment shall meet or exceed the minimum performance criteria as follows: a. The SPD shall be by, model, or accepted equivalent. b. SPD shall be of compact non-modular design. The mounting position of the SPD shall allow a straight and short lead-length connection between the SPD and the point of connection in the panelboard. c. The single-impulse surge-current rating shall be a minimum of Amps/phase. d. Visual indication of proper SPD connection and operation shall be easily viewed through the front door of the enclosure. The indicator lights shall indicate the presence of protection on each phase. e. The enclosure type shall have minimum rating of NEMA 12. PART 3 EXECUTION 3.01 INSTALLATION A. The installing contractor shall install the parallel SPD with short and straight conductors as practically possible. B. The contractor shall follow the SPD manufacturer s recommended installation practice as found in the equipment installation manual. C. The installation shall apply to all applicable codes. END OF SECTION Project No. SPECIFICATION GUIDELINES 16709-6