Troubleshooting Guide

Similar documents
Communications Card Operation

Instructions for Operation of S&C Test Accessory Catalog Number TA-2669

PS/IO Circuit Board Retrofit

Vista SD Portable Remote Control Pendant

S&C Micro-AT Source-Transfer Controls PHOTO SHEET. For use in S&C Metal-Enclosed Gear

Quick-Start Programming

AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number:

Product Description. S&C IntelliNode Interface Module. Table of Contents. Instruction Sheet

Trouble Shooting Leveling Control Box Electric Jacks. Touch Pad LED Probable Cause Solution

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

Phase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin:

Product Description. S&C 5800 Series Automatic Switch Control S&C ELECTRIC COMPANY TABLE OF CONTENTS

Specifications. S&C Micro-AT Source-Transfer Control. In Weatherproof Enclosure

DLA. DMX512 Analyzer. DLA Users Manual SV2_00 B.lwp copyright ELM Video Technology, Inc.

Installation NOTICE. S&C IntelliCap Automatic Capacitor Control. Table of Contents. Instruction Sheet

Resolver to Digital Expansion Board

Seven Channel Remote Control

Source-Transfer Application Guide

Troubleshooting with the control panel

EMS467 Monitoring System. Installation and Operations Manual Section 40

Troubleshooting Instructions

Ink-Dot Series II Driver

Model HM-535 Power Supply Installation and Service Instructions

Installing the Cisco MDS 9020 Fabric Switch

Model: CAM430MV Wired Multi-View Camera with License Plate / Rear Surface Mount Installation Manual Features

Instruction Sheet WPC 2000 Option 1

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

Install Motor Controller User Manual

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

* * Agilent Power Distribution Unit (PDU) Installation Guide

EPROM Replacement for Contrbl Systems

EMMS-T A00 SIERS. Siemens integrated electrical racking system instruction manual. usa.siemens.com/mvswitchgear

Installation. Section Page Section Page NOTICE

Blue Box BLUE BOX TM LTD PARTS REPLACEMENT GUIDE

OPERATING INSTRUCTIONS AND SERVICE MANUAL BASKETBALL SHOTCLOCK MODEL MP-5299

INDEX. Analog Board Boot and Voltage Test 2 Testing Input Channels 3 Testing Output Channels 4

Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

Configuration. S&C Scada-Mate Switching System Outdoor Distribution (14.4 kv through 34.5 kv)

AutoScan to MultiScan Replacement Kit

ZC Series Zone Monitoring Controllers

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

.2 Section General Commissioning (Cx) Requirements. .3 Section Common Work Requirements - Electrical

P1 PowerStation Backlight Bulb

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V Voltage 1, 2, 3 Pump Piston (D, E, F, G)

Operating Instructions & Service Manual FOULS

Allworx 24x Service and Troubleshooting Guide

Cerberus Division. Installation Instructions CERBERUS PYROTRONICS TM Model RDM-MXL. (Remote Diagnostics Module)

TD-700 FLUOROMETER SERVICE MANUAL

Type VR Electrically Operated Ground and Test Device

Primary Injection Test Procedure

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

Technical Manual SMART TRAC PS Card

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

CONTACTOR DRIVER BOARD. DS200CDBAG1A and DS200CDBAG1B

SECTION DISCONNECT SWITCHES

OPERATOR S MANUAL. Safety Notices... 1

Troubleshooting CHAPTER

PMDX-105. I/O Option Riser Board User s Manual. Document Revision: 1.1 Date: 7 September 2004 PCB Revision: PCB-443A

CONTROLLER BOARD CONVERSION KIT Rev Installation Instructions Part Number: PUPKIT

Pro-Flo System Digital Controller EPROM Upgrade

Installation, Field Programming, and Operation

XDBKITS5 Bus / DB Terminal Kit (Size 5) Installation Manual DPD00116

Installation Instructions

Replacing a Precision Controller Circuit Board

RGU Main Control Board Replacement Firmware Version 3.01

SECTION N -- ELECTROSTATIC DISCHARGE (ESD)

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

Electrical Demand Specification (Reference SOP: )

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

GPIB-232CT-A IBCL EPROM Installation Guide

Mitsubishi Electric Automation Instruction Manual FR-A5AC-01

Instruction Bulletin. Sepam Series 20 & 40 Relays Quick Start Guide

An ISO 9001 Company. BOP 1KW-MG FIRMWARE RETROFIT KIT

High Frequency Power Supply Board IS200HFPRG_A

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

Troubleshooting. S&C 5800 Series Automatic Switch Control. Table of Contents. Instruction Sheet

3a. IEM Indoor Metal Clad Medium Voltage Switchgear 25KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

CONTROL AND RECEIVING UNIT (CRU)

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

Model 7705 Control Module

1395 Node Adapter Board Troubleshooting

S Reclosers. Contents. Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions

INSTALLATION INSTRUCTIONS

Model NM512. TS1 Conflict Monitor Standard 12 Channel Unit. Naztec Operations Manual. For. Published by

INSTALLATION INSTRUCTIONS

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

B&W RearView Camera Installation & Operation

CIVACON A DOVER RESOURCES CO MATTOX RD. KANSAS CITY, MO 64150

2200 Series. Quick Start Guide SAFETY CHECKLIST. Safety Made Simple

PM Series Power Meter

E2460GS Oscilloscope Upgrade Kit

OTPC 150/225/260 Amp Transfer Switch

SC315 AC LED RRFB USER MANUAL COVERS MODELS SC315 AND SB435HP

Installation Manual Updated May 2017

Technical Manual SMART TRAC PG Card

Installation and Operation Manual

RAM Rail Mount Kit RAM 201U 5 Arm RAM 2461U Monitor Mount RAM 235U Base, Double U-Bolt

Maintaining the Cisco Catalyst 5500 Multiswitch Router

Transcription:

S&C Micro-AT Source-Transfer Controls Table of Contents Troubleshooting Guide Section Page Section Page Introduction.................................. 1 Chart I. Diagnosing The Problem............... 2 Chart II. Diagnosing Voltage Input Problems..... 4 Chart III. Diagnosing Current Input Problems.... 6 Chart IV. Diagnosing Data-Line Circuit Problems. 7 Layout of Circuit Cards.... 8 Introduction Ç CAUTION The equipment covered by this publication must be selected for a specific application and it must be operated and maintained by qualified persons who are thoroughly trained and who understand any hazards that may be involved. This publication is written only for such qualified persons and is not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment. The publication provides a troubleshooting guide for diagnosing operating problems experienced with an S&C Micro-AT Source Transfer Control that: 1. Was properly configured at the time of installation including having had the sources normalized, and 2. Had voltage-, current-, and time-related operating parameters properly set at the time of installation. Instructions for configuring, and for setting voltage-, current-, and time-related operating parameters are provided in Instruction Sheet 515-500, S&C Micro-AT Source- Transfer Controls: For use in S&C Metal-Enclosed Gear, and Instruction Sheet 515-600, S&C Micro-AT Source- Transfer Control: In Weatherproof Enclosure. It is assumed that normal conditions existed on the high-voltage system at the time the Micro-AT Source- Transfer Control was programmed. Where to Start... Before using the troubleshooting guide, follow the inspection procedures relating to switch operators; clock; lamps, display, and keypad; transfer on loss of source and return of source; event log; and optional overcurrent lockout feature contained in one of the following: 1. Instruction Sheet 620-592, S&C Power-Operated Metal- Enclosed Switchgear: Inspection Recommendations for Switchgear Equipped with Micro-AT Control; or 2. Instruction Sheet 663-590, S&C Source-Transfer PMH Pad-Mounted Gear: Inspection Recommendations for Units Equipped With Micro-AT or AT-12 Control. Then if you still can t pinpoint the nature of the problem, start at Chart I. Diagnosing the Problem. But if the problem appears to be attributable to a specific cause, start at one of the following charts, as appropriate: Chart II. Diagnosing Voltage Input Problems, Chart III. Diagnosing Current Input Problems, or Chart IV. Diagnosing Data-Line Circuit Problems. If the problem appears to involve the remote indication feature and the control is otherwise operating as expected replace the remote indication card. The positions of the various circuit cards are illustrated in Layout of Circuit Cards on page 8. Instructions for replacing a circuit card or front panel assembly of a Micro-AT Source-Transfer Control are provided in Instruction Sheet 515-525. As that instruction sheet points out, during the replacement procedure, precautions should be taken to prevent static charges, which can damage not only the existing component but the replacement component as well. Although spare circuit cards and front panel assemblies are furnished in staticshielded bags, the use of a static-dissipative work surface, such as the 3M 8501 Portable Static-Dissipative Field Service Kit (available from S&C as Catalog Number 9931-218), is highly recommended. This kit includes a static-dissipative work mat and a ground cord assembly with wrist strap, for connecting the mat along with the person changing the component to the same ground point. If, after following the diagnostic procedure, you still can t resolve the problem, or if the problem is intermittent in nature, contact your nearest S&C Sales Office. Should the problem turn out to be the result of nuisance voltageexcursion related events on the high-voltage system, you may wish to either: 1. Lower the loss-of-source voltage level setting and/or raise the unbalance-detect voltage level setting on the Micro-AT Source-Transfer Control, or 2. Investigate and remedy the system condition(s) causing these voltage excursions. June 30, 2008 S&C Electric Company Instruction Sheet 515-520

Chart I. Diagnosing The Problem Control operated unexpectedly. Control doesn t operate. Press the EVENT menu key. Scroll through items associated with the operation to determine if there was a system occurrence that should have led to a transfer. any lamp lit Are left source voltage and right source voltage lamps lit See CHART II. DIAGSING VOLTAGE INPUT PROBLEMS Press and hold for 5 seconds the TEST menu key. All lamps should flash 5 times. Did any lamp flash Open front panel of control. Measure voltages at test points on front of power supply card. The necessary voltage is shown at each test point. overcurrent lockout lamp lit and won t reset the ready lamp lit See CHART III. DIAGSING CURRENT INPUT PROBLEMS See CHART IV. DIAGSING DATA-LINE CIRCUIT PROBLEMS Are correct voltages present at test points liquid-crystal display off or is the display garbled Select TEST DISPLAY item in TEST menu and press ENTER. All dot segments should flash 5 times. Did each dot segment flash Check that connectors on wiring harnesses are properly inserted in receptacles on side or back of the control. If necessary, check that circuit cards are fully inserted and that ribbon connectors are fully inserted in their receptacles. If necessary, replace power supply card. Check switch operator control-source fuses. If necessary, check wiring between source-transfer control (and relays, if present) and switch operators. If necessary, open (or remove) front panel of control. Check that ribbon connector is properly inserted in receptacle on back of front panel. If necessary, check that circuit cards are fully inserted and that ribbon connectors are fully inserted in their receptacles. If necessary, replace relay output card. If necessary, check CPU card heartbeat lamp. It should be flashing. If it isn t, replace CPU card. Then reprogram control. Display may be bad. Replace front panel. 2 S&C Instruction Sheet 515-520

Chart I. Diagnosing The Problem the gear in an illogical state Refer to the appendix of Instruction Sheet 515-500 or 515-600 for event identification code numbers. For example, are switch operators cycling Or is a switch operator in an improper position * In pad-mounted gear which was originally furnished with a Type AT-12 Source-Transfer Control, open the door assembly of the Micro-AT control enclosure.. See Layout of Circuit Cards on page 8. If replacement is indicated, refer to Instruction Sheet 515-525. Note the precautions to be taken to prevent static charges, discussed therein. S&C Instruction Sheet 515-520 3

Chart II. Diagnosing Voltage Input Problems Left source voltage or right source voltage lamp isn t lit. Press and hold for 5 seconds the TEST menu key. All lamps should flash 5 times. Did the affected source voltage lamp flash Lamp may be bad. Replace front panel. Control operated unexpectedly and there was no system occurrence that should have led to a transfer. Left source voltage or right source voltage lamp isn't lit. Gear is not in an illogical state. Press the VOLTAGE menu key. this source-transfer pad-mounted gear 1-PHASE SENSING Read & record voltage settings for loss of source & return of source. 1-phase voltage sensing furnished on each source or is 3-phase voltage sensing furnished 3-PHASE SENSING Read & record voltage settings for loss of source, return of source, & (if installed) unbalance detect. operator discharged on affected source Contact your nearest S&C Sales Office Read & record voltages on left phase 2 & right phase 2. Read & record voltages on: left phase 1, right phase 1 left phase 2, right phase 2 left phase 3, right phase 3 & (if applicable) left unbalance & right unbalance. left unbalance a voltage or right unbalance voltage unbalance detect voltage setting I.e., switch operators aren t cycling. And each switch operator is in its proper position. (If the gear is in an illogical state, see Chart IV.). See Layout of Circuit Cards on page 8. If replacement is indicated, refer to Instruction Sheet 515-525. Note the precautions to be taken to prevent static charges, discussed therein. Different values may apply in metal-enclosed switchgear and source-transfer pad-mounted gear originally furnished with Type AT Source-Transfer Controls. Contact your nearest S&C Sales Office. a As of firmware version V2.5.3, zero sequence voltage of each source is also used in the determination of Unbalance Voltage for the respective source. The zero sequence voltages can be viewed in menu items within the EXAMINE menu. 4 S&C Instruction Sheet 515-520

Chart II. Diagnosing Voltage Input Problems CAUTION The phase voltage measurements listed below should be made quickly in source-transfer pad-mounted gear and metal-enclosed switchgear applications. Prolonged operation of unburdened voltage sensors may result in damage to the voltage sensors and voltage limiters. Be sure to replace the input plug in the input receptacle immediately after making the measurements. For source-transfer pad-mounted gear, measure and record phase voltages at input plug: pin 4 to pin 3 = left phase 1 pin 9 to pin 3 = left phase 2 pin 2 to pin 3 = left phase 3 pin 11 to pin 3 = right phase 1 pin 10 to pin 3 = right phase 2 pin 1 to pin 3 = right phase 3 Check positions of left source switch and right source switch. For each source switch note the following: OPEN source switch open or closed CLOSED For metal-enclosed switchgear, measure and record phase voltages at input plug: pin 9 to pin 3 = left phase 1 pin 13 to pin 3 = left phase 2 pin 4 to pin 3 = left phase 3 pin 10 to pin 3 = right phase 1 pin 12 to pin 3 = right phase 2 pin 11 to pin 3 = right phase 3 a phase voltage on that source return of source setting a phase voltage on that source < loss of source setting For weatherproof enclosure applications, measure and record phase voltages across voltage-transformer secondary fuse blocks: FB1 = left phase 1 FB2 = left phase 2 FB3 = left phase 3 FB6 = left phase 1 FB7 = left phase 2 FB8 = left phase 3 Replace relay output card. If necessary, replace CPU card. Then reprogram control. each phase voltage 130 to 180 Vac RMS (if voltage sensor is used) or 120 Vac RMS ( (if voltage transformer is used) Check wiring between input receptacle (or voltage-transformer secondary fuse blocks, in weatherproof enclosure applications) and Micro-AT control. If necessary, replace analog input card. Then normalize sources. If necessary, Replace burden card. Then normalize sources. Check wiring between voltage limiter and input plug (or between voltage transformers and secondary fuse blocks, in weatherproof enclosure applications). If necessary, replace voltage limiter. If necessary, replace voltage sensor. Then normalize sources. CAUTION It is imperative that the gear be de-energized and grounded in accordance with the user s operating and safety practices before any work is started. S&C Instruction Sheet 515-520 5

Chart III. Diagnosing Current Input Problems Overcurrent lockout lamp is lit and won t reset. Press CURRENT menu key. Read and record current setting for lockout level. THE FOLLOWING VISUAL INSPECTIONS SHOULD ONLY BE PERFORMED BY PERSONS QUALIFIED TO ACCESS HIGH-VOLTAGE COMPARTMENTS: CAUTION When inspecting energized gear, always use suitable protective equipment and observe proper operating and safety procedures. If the visual inspection indicates the need for servicing, it is imperative that the gear be de-energized and grounded in accordance with the user s operating and safety practices before any work is started. Visually check wiring between current sensors and control for open or intermittent connections. If necessary, visually check installation of current sensors and condition of current sensor burdens. If necessary, visually check cable terminations for evidence of tracking or overheating. Press EXAMINE menu key. Read and record currents on left neutral and right neutral. left neutral current or right neutral current > lockout level current setting Replace analog input card. Then normalize sources. If necessary, replace CPU card. Then reprogram control.. See Layout of Circuit Cards on page 8. If replacement is indicated, refer to Instruction Sheet 515-525. Note the precautions to be taken to prevent static charges, discussed therein. 6 S&C Instruction Sheet 515-520

Chart IV. Diagnosing Data-Line Circuit Problems Automatic-transfer ready lamp isn t lit. Control operated unexpectedly and there was no system occurrence that should have led to a transfer. Gear is in an illogical state. Press and hold for 5 seconds the TEST menu key. All lamps should flash 5 times. Lamp may be bad. Replace front panel. Did the ready lamp flash Use the or key to display message explaining why ready lamp isn t lit and correct condition(s) specified. If necessary, Press the EXAMINE menu key. Read and record the true/false operating responses to the discrete inputs from snap-action limit switches (and key interlocks, if applicable). Does each operating response correspond to the actual condition at the gear Refer to schematic diagram and check continuity of each snap-action limit switch data line circuit (and key interlock data line circuit, if applicable) Replace digital input card. If necessary, replace relay output card. Check wiring of data line circuit for open or intermittent connections, as well as pinched connections. there continuity in each data line circuit having a closed limit switch. See Layout of Circuit Cards on page 8. If replacement is indicated, refer to Instruction Sheet 515-525. Note the precautions to be taken to prevent static charges, discussed therein. For example, switch operators are cycling. Or a switch operator is in an improper position. S&C Instruction Sheet 515-520 7

Layout of Circuit Cards Ejector Ground wire Front panel Remote indication card (Catalog Number Suffix -Y4 ) Power supply card Ribbon connectors Digital input card CPU card Communications card Analog input card Ready output card #4 40 hex nut, lockwashers, and flat washer Burden card (includes test panel with Catalog Number Suffix -Y5 ) Hinged lower panel Positions of various circuit cards in Micro-AT Source-Transfer Control. In pad-mounted gear which was originally furnished with Type AT-12 Source Transfer Control, circuit cards are accessed by opening door assembly of Micro-AT control enclosure. Printed in U.S.A. 8 S&C Instruction Sheet 515-520